10
-
Item
Model
FDTA301R
FDCVA602HESAR
Nominal cooling capacity
(1)
kW
14.0 [7.0~14.5]
Nominal heating capacity
(1)
kW
16.0 [6.3~16.5]
Power source
3 Phase, 380-415V 50Hz/380V 60Hz
Cooling power consumption
kW
4.69/4.71
Running current (Cooling)
A
6.9/7.2
Power factor (Cooling)
%
98/99
Heating power consumption
kW
4.58/4.60
Running current (Heating)
A
6.7/7.1
Power factor (Heating)
%
99/98
Inrush current (L.R.A)
A
5
Noise level
dB(A)
35
52
Exterior dimensions
mm
Unit 270
×
840
×
840
845
×
970
×
370
Height
×
Width
×
Depth
Panel 30
×
950
×
950
Net weight
kg
31 (Unit:24 Panel:7)
74
Refrigerant equipment
–
RM-B5125MDE31
Compressor type & Q’ty
Starting method
–
Direct line start
Heat exchanger
Louver fin & inner grooved tubing
Straight fin & inner grooved tubing
Refrigerant control
–
Electronic expansion valve
Refrigerant
R410A
Quantity
kg
–
3.8 [Pre-charged up to the piping length of 30m]
Refrigerant oil
r
–
0.7 (M-MA68)
Defrost control
Microcomputer controlled de-icer
Air handling equipment
Fan type & Q’ty
Turbo fan
×
1
Propeller fan
×
1
Motor
W
20
×
1
120
×
1
Starting method
Direct line start
Direct line start
Air flow
CMM
Cooling: 75, Heating: 73
Outside air intake
Available
–
Air filter, Q’ty
Long life filter
×
1(washable)
–
Shock & vibration absorber
Rubber sleeve (for fan motor)
Rubber mount (for compressor)
Electric heater
W
–
20 (Crank case heater)
Operation control
Wired remote control switch (Optional : RC-E1R)
Operation switch
Wireless kit (Optional : RCN-T-35W-ER)
– (Indoor unit side)
Room temperature control
Thermostat by electronics
–
Safety equipment
Internal thermostat for fan motor.
Internal thermostat for fan motor.
Frost protection thermostat.
Anomalous discharge temperature protection.
Installation data
mm
Indoor branch pipe, Outdoor main pipe:
φ
9.52 (3/8
″
)
Refrigerant piping size
(in)
Indoor branch pipe, Outdoor main pipe:
φ
15.88 (5/8
″
)
Connecting method
Flare piping
Drain hose
Connectable with VP25 (I.D.25mm, O.D.32mm)
–
Insulation for piping
Necessary (both Liquid & Gas lines)
Accessories
Mounting kit. Drain hose
Optional parts
Decorative Panel
Operation data
(3)
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard. ISO-T1 “UNITARY AIR-CONDITIONERS”
(3) The operation data indicate when the air-conditioner is operated at 400V 50Hz or 380V 60Hz.
(4) Values in [ ~ ] show the minimum to maximum range.
(5) Indoor unit specifications show the specifications for one unit. Capacity and running characteristics values are shown for the case where two indoor units
are combined and run together.
Notes (1) The data are measured at the following conditions.
Item
Indoor air temperature
Outdoor air temperature
Standards
Operation
DB
WB
DB
WB
Cooling
27˚C
19˚C
35˚C
24˚C
Heating
20˚C
–
7˚C
6˚C
ISO-T1
FDTVA602HESP2R
Model FDTVA602HESP2R (Indoor unit: 2 units, Outdoor unit: 1 unit)
Powerful mode Hi:38 Me:35 Lo:33
Mild mode Hi:35 Me:33 Lo:31
Powerful mode Hi:20 Me:17 Lo:15
Mild mode Hi:17 Me:15 Lo:13
53
Liquid line
Gas line