14
-
Item
Model
FDENA601R
FDCVA602HESRR
Nominal cooling capacity
(1)
kW
14.0 [6.7~14.5]
Nominal heating capacity
(1)
kW
16.0 [6.3~16.5]
Power source
3 Phase, 380-415V 50Hz/380V 60Hz
Cooling power consumption
kW
4.95/4.95
Running current (Cooling)
A
7.2/7.6
Power factor (Cooling)
%
99/99
Heating power consumption
kW
4.69/4.69
Running current (Heating)
A
6.8/7.2
Power factor (Heating)
%
99/99
Inrush current (L.R.A)
A
5
Noise level
dB(A)
Exterior dimensions
mm
250
×
1620
×
690
845
×
970
×
370
Height
×
Width
×
Depth
Net weight
kg
46
74
Refrigerant equipment
–
RM-B5125MDE31
Compressor type & Q’ty
Starting method
–
Direct line start
Heat exchanger
Louver fin & inner grooved tubing
Straight fin & inner grooved tubing
Refrigerant control
–
Electronic expansion valve
Refrigerant
R410A
Quantity
kg
–
3.8 [Pre-charged up to the piping length of 30m]
Refrigerant oil
r
–
0.7 (M-MA68)
Defrost control
Microcomputer controlled de-icer
Air handling equipment
Fan type & Q’ty
Centrifugal fan
×
4
Propeller fan
×
1
Motor
W
45
×
2
120
×
1
Starting method
Direct line start
Direct line start
Air flow
CMM
Cooling: 75, Heating: 73
Outside air intake
Unavailable
–
Air filter, Q’ty
Polypropylene net
×
2(washable)
–
Shock & vibration absorber
Rubber sleeve (for fan motor)
Rubber mount (for compressor)
Electric heater
W
–
20 (Crank case heater)
Operation control
Wireless remote control switch (Optional: RCN-E1R)
Operation switch
Wired remote control switch (Optional: RC-E1R)
– (Indoor unit side)
Room temperature control
Thermostat by electronics
–
Safety equipment
Internal thermostat for fan motor.
Internal thermostat for fan motor.
Frost protection thermostat.
Anomalous discharge temperature protection.
Installation data
mm
Liquid line:
φ
9.52 (3/8
″
) Gas line:
φ
15.88 (5/8
″
)
Refrigerant piping size
(in)
Connecting method
Flare piping
Drain hose
Connectable with VP20 (I.D.20mm, O.D.26mm)
–
Insulation for piping
Necessary (both Liquid & Gas lines)
Accessories
Mounting kit. Drain hose
Optional parts
–
Model FDENVA602HES2R
Operation data
(3)
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard. ISO-T1 “UNITARY AIR-CONDITIONERS”
(3) The operation data indicate when the air-conditioner is operated at 400V 50Hz or 380V 60Hz.
(4) Values in [ ~ ] show the minimum to maximum range.
Notes (1) The data are measured at the following conditions.
Item
Indoor air temperature
Outdoor air temperature
Standards
Operation
DB
WB
DB
WB
Cooling
27˚C
19˚C
35˚C
24˚C
Heating
20˚C
–
7˚C
6˚C
ISO-T1
FDENVA602HES2R
53
Powerful mode Hi:48 Me:46 Lo:44
Mild mode Hi:46 Me:44 Lo:43
Powerful mode Hi:31 Me:29 Lo:26
Mild mode Hi:29 Me:26 Lo:23