21
-
Model FDUMVA602HES2R
Item
Model
FDUMA602R
FDCVA602HESAR
Nominal cooling capacity
(1)
kW
14.0 [6.7~14.5]
Nominal heating capacity
(1)
kW
16.0 [6.3~16.5]
Power source
3 Phase, 380-415V 50Hz/380V 60Hz
Cooling power consumption
kW
4.95/4.95
Running current (Cooling)
A
7.4/7.7
Power factor (Cooling)
%
97/98
Heating power consumption
kW
4.75/4.91
Running current (Heating)
A
7.2/7.6
Power factor (Heating)
%
95/98
Inrush current (L.R.A)
A
5
Noise level
dB(A)
Hi:38 Me:36 Lo:33
Exterior dimensions
mm
350
×
1370
×
635
845
×
970
×
370
Height
×
Width
×
Depth
Net weight
kg
59
74
Refrigerant equipment
–
RM-B5125MDE31
Compressor type & Q’ty
Starting method
–
Direct line start
Heat exchanger
Louver fin & inner grooved tubing
Straight fin & inner grooved tubing
Refrigerant control
–
Electronic expansion valve
Refrigerant
R410A
Quantity
kg
–
3.8 [Pre-charged up to the piping length of 30m]
Refrigerant oil
r
–
0.7 (M-MA68)
Defrost control
Microcomputer controlled de-icer
Air handling equipment
Fan type & Q’ty
Centrifugal fan
×
3
Propeller fan
×
1
Motor
W
50
×
1, 100
×
1
120
×
1
Starting method
Direct line start
Direct line start
Air flow (Standard)
CMM
Hi: 34 Me: 31 Lo: 27
Cooling: 75, Heating: 73
Available static pressure
Pa
Standard: 60, Max 85
–
Outside air intake
–
–
Air filter, Q’ty
–
–
Shock & vibration absorber
Rubber sleeve (for fan motor)
Rubber mount (for compressor)
Electric heater
W
–
20 (Crank case heater)
Operation control
Wired remote control switch (Optional: RC-E1R)
Operation switch
Wireless kit (Optional: RCND-KIT-HER)
– (Indoor unit side)
Room temperature control
Thermostat by electronics
–
Safety equipment
Internal thermostat for fan motor.
Internal thermostat for fan motor.
Internal
thermostat for fan motor.
Frost protection thermostat.
Anomalous discharge temperature protection.
Installation data
mm
Liquid line:
φ
9.52 (3/8
″
) Gas line:
φ
15.88 (5/8
″
)
Refrigerant piping size
(in)
Connecting method
Flare piping
Drain hose
Connectable with VP25 (I.D.25mm, O.D.32mm)
–
Insulation for piping
Necessary (both Liquid & Gas lines)
Accessories
Mounting kit. Drain hose
Optional parts
Filter kit (UM-FL3E)
Operation data
(3)
Item
Indoor air temperature
Outdoor air temperature
Standards
Operation
DB
WB
DB
WB
Cooling
27˚C
19˚C
35˚C
24˚C
Heating
20˚C
–
7˚C
6˚C
ISO-T1
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard.
ISO-T1 “UNITARY AIR-CONDITIONERS”
(3) The operation data indicate when the air-conditioner is operated at 400V 50Hz or 380V 60Hz.
(4) Values in [ ~ ] show the minimum to maximum range.
Notes (1) The data are measured at the following conditions.
FDUMVA602HES2R
53