-
-
'16 • PAC-T-240
J
PJG000Z159
(4) Duct connected-Low / Middle static pressure type (FDUM)
Model
Item
FDUM100VNP1VF2
Indoor unit
FDUM100VF2
Outdoor unit
FDC100VNP
Power source
1 Phase 220-240V 50Hz / 220V 60Hz
Operation
data
Nominal cooling capacity (range)
kW
10.0 [ 2.8(Min.)— 11.2(Max.)]
Nominal heating capacity (range)
kW
11.2 [ 2.5(Min.)— 12.5(Max.)]
Power consumption
Cooling
kW
3.00
Heating
2.93
Max power consumption
4.60
Running current
Cooling
A
13.2 / 13.8
Heating
12.9 / 13.5
Inrush current, max current
5, 22.0
Power factor
Cooling
%
99
Heating
99
EER
Cooling
3.33
COP
Heating
3.82
Sound power level
Cooling
dB(A)
65
70
Heating
Sound pressure level
Cooling
P-Hi : 44 Hi : 38 Me : 36 Lo : 30
57
Heating
61
Silent mode sound pressure level
—
Cooling:50 / Heating:49
Exterior dimensions (Height × Width × Depth)
mm
280 × 1,370 × 740
845×970×370
Exterior appearance
( Munsell color )
—
Stucco white
(
4.2Y7.5/1.1
)
near equivalent
Net weight
kg
54
70
Compressor type & Q'ty
—
RMT5126MCE1 ( Twin rotary type )×1
Compressor motor (Starting method)
kW
—
Direct line start
Refrigerant oil (Amount, type)
—
0.90 MA68
Refrigerant (Type, amount, pre-charge length)
kg
R410A 2.55kg in outdoor unit (incl. the amount for the piping of : 15m)
Heat exchanger
Louver fin & inner grooved tubing
M shape fin & inner grooved tubing
Refrigerant control
Capillary tubes + Electronic expansion valve
Fan type & Q'ty
Centrifugal fan ×3
Propeller fan ×1
Fan motor (Starting method)
W
100 + 130 < Direct line start >
86 < Direct line start >
Air flow
Cooling
m
3
/min
P-Hi : 36 Hi : 28 Me : 25 Lo : 19
75
Heating
79
Available external static pressure
Pa
Standard
:
60 Max
:
100
0
Outside air intake
Possible
—
Air filter, Quality / Quantity
Procure locally
—
Shock & vibration absorber
Rubber sleeve(for fan motor)
Rubber sleeve (for fan motor & compressor)
Electric heater
W
—
—
Operation
control
Remote control
(option) wired : RC-EX1A , RC-E5 , RCH-E3 wireless : RCN-KIT3-E
Room temperature control
Thermostat by electronics
Operation display
—
Safety equipments
Compressor overheat protection, Overcurrent protection,
Frost protection, Serial signal error protection, Indoor fan motor error protection,
Heating overload protection( High pressure control ), Cooling overload protection
Installation
data
Refrigerant piping size ( O.D. )
mm
Liquid line: I/U
φ
9.52 (3/8") Pipe
φ
9.52(3/8")×0.8 O/U
φ
9.52 (3/8")
Gas line: I/U
φ
15.88 (5/8") Pipe
φ
15.88(5/8")×1.0 O/U
φ
15.88 (5/8")
Connecting method
Flare piping
Flare piping
Attached length of piping
m
—
—
Insulation for piping
Necessary (both Liquid & Gas lines)
Refrigerant line (one way) length
m
Max.30m
Vertical height diff. between O.U. and I.U.
m
Max.20m (Outdoor unit is higher)
Max.20m (Outdoor unit is lower)
Drain hose
Hose connectable VP25 (I.D.25,O.D.32)
Holes size
φ
20 × 3pcs
Drain pump, max lift height
mm
Built-in drain pump , 600
—
Recommended breaker size
A
—
L.R.A. (Locked rotor ampere)
A
5.0
Interconnecting wires Size × Core number
1.5
mm
2
×4 cores
(Including earth cable) / Termainal block (Screw fixing type)
IP number
IPX0
IPX4
Standard accessories
Mounting kit, Drain hose
—
Option parts
UM-FL3EF
Note (1) The data are measured at the following conditions.
The pipe length is 7.5m.
(2) This air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
(4) Select the breaker size according to the own national standard.
(5) When wireless remote control is used, fan is 3 speed setting (Hi-Me-Lo) only.
(6) The operation data indicate when the air-conditioner is operated at 230V 50Hz or 220V 60Hz.
(7) Static pressure of optional air filter "UM-FL3EF" is 5Pa initially.
(8) The external static pressure setting can be changed to 10-100Pa. (For RC-EX1A and RC-E5 only)
Item
Operation
Indoor air temperature
Outdoor air temperature
External static pressure
of indoor unit
Standards
DB
WB
DB
WB
Cooling
27˚C
19˚C
35˚C
24˚C
60Pa
ISO5151-T1
Heating
20˚C
—
7˚C
6˚C