139
-
'16 • PAC-T-240
(d) Outdoor fan control at low outdoor temperature
(i) Cooling
1) Operating conditions:
When the outdoor air temperature (TH2) is 22ºC or lower continues for 30 seconds while the
compressor command speed is other than 0 rps.
2) Detail of operation:
After the outdoor fan operates at A speed for 60 seconds; the corresponding outdoor heat
exchanger temperature shall implement the following controls.
a) Outdoor heat exchanger temperature =< 22ºC
After the outdoor fan speed drops (down) to 1 speed for 60 seconds; if the outdoor heat exchanger temperature is
lower than 22ºC, gradually reduce the outdoor fan speed by 1 speed. (Lower limit 1st speed)
b) 22ºC < Outdoor heat exchanger temperature =< 40ºC
After the outdoor fan speed maintains for 20 seconds; if the outdoor heat exchanger temperature is 22ºC-40ºC,
maintain outdoor fan speed again.
c) Outdoor heat exchanger tempeature > 40ºC
After the outdoor fan speed rises (up) to 1 speed for 60 seconds; if the outdoor heat exchanger temperature is higher
than 40ºC, gradually increase outdoor fan speed by 1 speed. (Upper limit 3rd speed)
3) Reset conditions:
When either of the following conditions is satisfied
a) The outdoor air temperature (TH2) is 24ºC or higher and fan speed is 3rd speed.
b) The compressor command speed is 0 rps.
4) Outdoor unit fan speed and fan motor speed
(ii) Heating
1) Operating conditions:
When the outdoor air temperature (TH2) is 3ºC or lower continues for 30 seconds while the
compressor command speed is other than 0 rps.
2) Detail of operation:
The outdoor fan is stepped up by 2 speed step at each 20 seconds. (Upper limit 8th speed)
3) Reset conditions:
When either of the following conditions is satisfied
a) The outdoor air temperature (TH2) is 5ºC or higher.
b) The compressor command speed is 0 rps.
(e) Outdoor fan control at overload
(i) Cooling
1) Operating conditions:
When the outdoor air temperature (TH2) is 41ºC or higher continues for 30 seconds while the
compressor command speed is other than 0 rps.
2) Detail of operation:
The outdoor fan is stepped up by 3 speed. (Upper limit 8th speed)
3) Reset conditions:
When either of the following conditions is satisfied
a) The outdoor air temperature (TH2) is 40ºC or lower.
b) The compressor command speed is 0 rps.
Outdoor air temperature > 10˚C
Outdoor air temperature <= 10˚C
2nd speed
Outdoor fan
1st speed
¡
Value of A