'16 • PAC-T-240
1) Operating conditions:
When the outdoor air temperature (TH2) is 13ºC or higher continues for 30 seconds while the
compressor command speed is other than 0 rps.
2) Detail of operation:
The outdoor fan stepped down to 3 speed.(Lower limit 2nd speed)
3) Reset conditions:
When either of the following conditions is satisfied
a) The outdoor air temperature (TH2) is 11ºC or lower.
b) The compressor command speed is 0 rps.
(f)
Outdoor fan motor protection
If the outdoor fan motor has operated at 75 rpm or lower for more than 30 seconds, the compressor and fan motor are stopped.
(a) Starting conditions (Defrost operation can be started only when all of the following conditions are satisfied.)
(i) After start of heating operation
When it elapsed 35 minutes. (Accumulated compressor operation time)
(ii) After end of defrost operation
When it elapsed 35 minutes. (Accumulated compressor operation time)
(iii) Outdoor heat exchanger sensor (TH1) temperature
When the temperature has been below
-
5ºC for 3 minutes continuously.
(iv) The difference between the outdoor air sensor temperature and the outdoor heat exchanger sensor temperature (TH2-TH1)
¡
The outdoor air temperature
≧
-
2ºC : 7ºC or higher
¡
-
15ºC
<
The outdoor air temperature
<
-
2ºC : 4/15 × The outdoor air tempe 7ºC or higher
¡
The outdoor air temperature
≦
-
15ºC :
-
5ºC or higher
-20
-20
-15
-10
-5
0
5
10
-15
-10
-5
0
Outdoor air temperature (
℃
)
Outdoor heat exchanger temperature (
℃
)
Defrost operation
start
Defrost operation start temperature
(v) During continuous compressor operation
In addition, when the speed command from the indoor control of the indoor unit during heating operation has counted 0 rps
10 times or more and all conditions of (i), (ii) above and the outdoor air temperature is 3ºC or less and the temperature for
outdoor heat exchanger sensor (TH1) is
-
5ºC or less: 62 rps or more,
-
4ºC or less: less than 62 rps are satisfied, defrost
operation is started.
(ii) Heating
(4) Defrost operation
Max. 18 minutes
Heating operation
¡
Defrost operation
̪
Depends on an operation condition, the time can be longer than 7 minutes.
2~7 minutes
̪
Hot start operation
(b) Ending condition (Operation returns to the heating cycle when either one of the following is satisfied.)
(i) Outdoor heat exchanger sensor (TH1) temperature: 13ºC or higher
(ii)
Continued operation time of defrost operation → For more than 18 minutes.