147
-
'16 • PAC-T-240
(ii) Outdoor unit
Remote control
Indoor control PCB
Location of trouble
Description of trouble
Repair method
Reference
page
Error code Red LED Red LED
Green
LED
Keeps
flashing
Stays OFF
Keeps
flashing
Installation, operation status
• Higher outdoor heat exchanger temperature
Repair
187
Outdoor heat exchanger
temperature sensor
• Defective outdoor heat exchanger temperature sensor
Replacement, repair
of temperature
sensor
Outdoor control PCB
*• Defective outdoor control PCB (Defective temperature sensor input circuit)?
Replacement of
PCB
Stays OFF
Keeps
flashing
Installation, operation status
• Higher discharge temperature
Repair
188
Discharge pipe temperature
sensor
• Defective discharge pipe temperature sensor
Replacement, repair
of temperature
sensor
Outdoor control PCB
*• Defective outdoor control PCB (Defective temperature sensor input circuit)?
Replacement of
PCB
Stays OFF
Keeps
flashing
Outdoor heat exchanger
temperature sensor
• Defective outdoor heat exchanger temperature sensor, broken wire or poor
connector connection
Replacement, repair
of temperature
sensor
189
Outdoor control PCB
*• Defective outdoor control PCB (Defective temperature sensor input circuit)?
Replacement of
PCB
Stays OFF
Keeps
flashing
Outdoor air temperature sensor • Defective outdoor air temperature sensor, broken wire or poor connector connection
Replacement, repair
of temperature
sensor
190
Outdoor control PCB
*• Defective outdoor control PCB (Defective temperature sensor input circuit)?
Replacement of
PCB
Stays OFF
Keeps
flashing
Discharge pipe temperature
sensor
• Defective discharge pipe temperature sensor, broken wire or poor connector
connection
Replacement, repair
of temperature
sensor
191
Outdoor control PCB
*• Defective outdoor control PCB (Defective temperature sensor input circuit)?
Replacement of
PCB
Stays OFF
Keeps
flashing
Outdoor control PCB,
compressor
• Current cut (Anomalous compressor over-current)
Replacement of
PCB
192
・
193
Installation, operation status
• Service valve closing operation
Repair
Stays OFF
Keeps
flashing
Outdoor control PCB
• Over voltage
Repair
PCB replacement
194
• Defective active filter
Stays OFF
Keeps
flashing
Fan motor
• Defective fan motor
Replacement
195
Outdoor control PCB
• Defective outdoor control PCB
Stays OFF
Keeps
flashing
Power transistor error
(outdoor control PCB)
• Power transistor error
Replacement of
PCB
196
Stays OFF
Keeps
flashing
Operation status
• Shortage in refrigerant quantity
Repair
197
Installation status
• Service valve closing operation
Service valve
opening check
Stays OFF
Keeps
flashing
• Overload operation
• Overcharge
• Compressor locking
• Current safe stop
Replacement
198
Stays OFF
Keeps
flashing
Compressor, outdoor control PCB
• Anomalous compressor startup
• Voltage drop
Replacement
199
Stays OFF
Keeps
flashing
Compressor
• Anomalous compressor rotor lock
Replacement
200
Note (1) * mark in the description of trouble means that, in ordinary diagnosis, it cannot identify the cause definitely, and, if the trouble is repaired by replacing the
part, it is judged consequently that the replaced part was defective.
Remote control
Indoor control PCB
Location of trouble
Description of trouble
Repair method
Reference
page
Error code Red LED Red LED
Green
LED (1)
Keeps
flashing
1(2)-time
flash
Keeps
flashing
Fan motor
•
Defective by rotation speed of fan motor
Replacement, repair
184
Indoor power PCB
•
Defective indoor power PCB
Replacement
1-time
flash
Keeps
flashing
Panel switch detection
• Defective panel switch operation (FDT only)
Repair
185
Stays OFF
Keeps
flashing
Remote control temperature
thermistor
• Broken wire of remote control temperature thermistor
Repair
186
Notes (1)
Normal indicator lamp (Indoor unit: Green) extinguishes (or lights continuously) only when CPU is anomalous. It keeps flashing
in any trouble other than anomalous CPU.
(2) * mark in the description of trouble means that, in ordinary diagnosis, it cannot identify the cause definitely, and, if the trouble is repaired by replacing
the part, it is judged consequently that the replaced part was defective.