179
-
'16 • PAC-T-240
Error code
Remote control:
LED
Green
Red
Indoor
Content
E9
Drain trouble
(FDT, FDU, FDUM series)
Keeps flashing 1-time flash
1. Applicable model
5. Troubleshooting
FDT, FDU, FDUM series only
Diagnosis
Countermeasure
Is the humidifier connected?
NO
Drain motor ON from the remote control
YES
Does drain motor operate?
YES
NO
Check the error data in the remote control.
Is there any overflow?
Is DC 12V
at CNI connector.
Is the
CNI connected
firmly?
NO
YES
Is
there any
anomaly on the optional
equipment?
NO
YES
YES
Is the
humidifier drain motor
interlocked by the indoor unit function
setting of remote
control?
NO
YES
Is
DC12V
detected at CNR
connector?
NO
YES
Is the drain
piping unclogged? Is the
drain pipe slop
OK?
NO
YES
NO
YES
NO
Check float switch.
Defective indoor control
PCB
➞
Replace.
Defective indoor control
PCB
➞
Replace.
Check option equipment
Correct setting to
“Humidifier drain motor
interlock”.
Defective indoor control
PCB
➞
Replace.
Check wiring of drain
motor
Correct.
Check drain motor.
2. Error detection method
Float switch is activated
3. Condition of error displayed
If the float switch OPEN
is detected for 3 seconds
continuously or if float
switch connector or wire is
disconnected.
4. Presumable cause
• Defective indoor control or
power PCB
• Float switch setting error
• Humidifier drain motor
interlock setting error
• Optional equipment setting
error
• Drain piping error
• Defective drain motor
• Disconnection of drain motor
wiring
Note:
When this error occurred at power ON, disconnection of wire or connector of the float switch is suspected. Check and
correct it (or replace it, if necessary).