196
-
'16 • PAC-T-240
E51
Power transistor anomaly
Error code
Remote controller: E51
LED
Green
Red
Indoor
Content
Power transistor error
Keeps flashing Stays Off
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
2. Error detection method
3.Condition of error displayed
4. Presumable cause
Note:
If the power transistor primary
current exceeds the setting value
for 3 seconds, the compressor
stops.
Power transistor primary current
• Faulty outdoor control PCB
• Dust on outdoor control PCB
• Blown fuse
Check soldered
surfaces on the outdoor control PCB for
foreign matter like dust,
fouling,etc.
Isn
’t F8 fuse
(250V, 20A)blown?
Remove foreign matter
like dust, fouling, etc.
Replace fuse.
Defective outdoor control
PCB
ª
Replace.
YES
NO
NO
YES
Error code
Remote control:
LED
Green
Red
Content
Indoor
Stays OFF
Keeps flashing