8. RANGE OF USAGE & LIMITATIONS
Operating temperature range
See next page.
When used below -5˚C, install a snow hood (prepared on site).
Recommendable area to install
Considering to get sufficient heating capacity, the area where the averaged lowest ambient
air temperature in day time during winter is above 0˚C, and it has no accumulation of snow.
Installation site
The limitations of installation space are shown in the page for exterior dimensions.
Install the indoor unit at least 2.5m higher than the floor surface.
Temperature and humidity conditions surrounding the
indoor unit (Note 2)
Model FDE, FDF, SRK : Dew point temperature : 23˚C or less, relative hummdity : 80% or less
Other models : Dew point temperature : 28˚C or less, relative hummdity : 80% or less
Limitations on unit and piping installation
See page 40
Compressor
ON-OFF cycling
Cycle time
10 minutes or more (from OFF to OFF) or (from ON to ON)
Stop time
3 minutes or more
Power source
Voltage range
Rating ±10%
Voltage drop at start-up
Min.85% of rating
Phase-to-phase imbalance
3% or less
Note 1. Do not install the unit in places which :
1) Flammable gas may leak.
2) Carbon fiber, metal particles, powder, etc. are floating.
3) Cosmetic or special sprays are used frequently.
4) Exposed to oil splashes or steam (e.g. kitchen and machine plant).
5) Exposed to sea breeze (e.g. coastal area) or calcium chloride (e.g. snow melting agent).
6) Exposed to ammonia substance (e.g. organic fertilizer).
7) Matters affecting devices, such as sulfuric gas, chlorine gas, acid, alkali, etc. may generate or accumulate.
8) Chimney smoke is hanging.
9) Sucking the exhaust gas from heat exchanger.
10) Adjacent to equipment generating electromagnetic waves or high frequency waves.
11) There is light beams that affect the receiving device of indoor unit in case of the wireless specification.
12) Snow falls heavily.
13) At an elevation of 1000 meters or higher.
14) On mobile machine (e.g. vehicle, ship, etc.)
15) Splashed with water to indoor unit (e.g. laundry room).
Note 2. If ambient temperature and humidity exceed the above conditions, add polyurethane foam insulation on the outer plate (10mm or thicker) of
indoor unit.
Note 3. Both gas and liquid pipes need to be coverd with 20mm or thicker heat insulation materials at the place where relative humidity exceeds
70%.