41
-
'16 • PAC-T-240
Model FDT100VNP1VF2
Indoor unit FD100VF2 Outdoor unit FDC100VNP
9.SELECTION CHART
Correct the cooling and heating capacity in accordance with the operating conditions. The net cooling and heating capacity can be
obtained in the following way.
Net capacity = Capacity shown in the capacity tables (9.1) × Correction factors shown in the table (9.2) (9.3) (9.4).
Caution:
In case that the cooling operation during low outdoor air temperature below -5°C is expected, install the outdoor unit
where it is not influenced by natural wind. Otherwise protection control by low pressure will be activated much more
frequently and it will cause insufficient capacity or breakdown of the compressor in worst case.
9.1 Capacity tables
(1) Ceiling cassette-4way type (FDT)
Indoor air temperature
Indoor air temperature
Outdoor air
temperature
Outdoor air
temperature
18
℃
DB
21
℃
DB
23
℃
DB
26
℃
DB
27
℃
DB
28
℃
DB
31
℃
DB
33
℃
DB
℃
DB
12
℃
WB
14
℃
WB
16
℃
WB
18
℃
WB
19
℃
WB
20
℃
WB
22
℃
WB
24
℃
WB
℃
DB
℃
WB
16
18
20
22
24
TC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
11
13
-14.5
-15
15
-13.5
-14
17
-11.5
-12
19
-9.5
-10
21
-7.5
-8
23
-5.5
-6
25
-3.0
-4
27
-1.0
-2
29
1.0
0
31
2.0
1
33
3.0
2
35
5.0
4
37
7.0
6
39
9.0
8
41
11.5
10
43
13.5
12
15.5
14
16.5
16
℃
DB
SHC
Heating mode : HC
Cooling mode
Model FDE100VNP1VG
Indoor unit FDE100VG Outdoor unit FDC100VNP
(kW)
(kW)
Indoor air temperature
Indoor air temperature
Outdoor air
temperature
Outdoor air
temperature
18
℃
DB
21
℃
DB
23
℃
DB
26
℃
DB
27
℃
DB
28
℃
DB
31
℃
DB
33
℃
DB
℃
DB
12
℃
WB
14
℃
WB
16
℃
WB
18
℃
WB
19
℃
WB
20
℃
WB
22
℃
WB
24
℃
WB
℃
DB
℃
WB
16
18
20
22
24
TC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
11
13
-14.5
-15
15
-13.5
-14
17
-11.5
-12
19
-9.5
-10
21
-7.5
-8
23
-5.5
-6
25
-3.0
-4
27
-1.0
-2
29
1.0
0
31
2.0
1
33
3.0
2
35
5.0
4
37
7.0
6
39
9.0
8
41
11.5
10
43
13.5
12
15.5
14
16.5
16
℃
DB
SHC
Heating mode : HC
Cooling mode
(kW)
(kW)
Note(1) These data show average statuses.
Note(1)
Depending on the system control, there may be ranges where the operation is not conducted continuously.
Note(1)
These data show the case where the operation frequency of a compressor is fixed.
(2) Capacities are based on the following conditions.
(2)
Corresponding refrigerant piping length :7.5m
(2)
Level difference of Zero.
(3) Symbols are as follows.
TC : Total cooling capacity (kW)
SHC : Sensible heat capacity (kW)
HC : Heating capacity (kW)
(2) Ceiling suspended type (FDE)
6.20
6.18
6.16
6.14
6.11
9.71
8.14 10.21 8.62 10.46 8.54 10.66 8.44 11.06 8.85 11.46 8.63
6.26
6.23
6.21
6.19
6.16
9.71
8.14 10.21 8.62 10.46 8.54 10.66 8.44 11.06 8.85 11.46 8.63
6.36
6.34
6.31
6.29
6.26
9.71
8.14 10.21 8.62 10.46 8.54 10.66 8.44 11.06 8.85 11.46 8.63
6.47
6.44
6.42
6.39
6.36
9.71
8.14 10.21 8.62 10.46 8.54 10.66 8.44 11.06 8.85 11.46 8.63
6.58
6.55
6.52
6.49
6.46
9.65
8.11 10.18 8.61 10.45 8.54 10.66 8.44 11.08 8.86 11.51 8.64
7.16
7.13
7.10
7.06
7.02
9.59
8.09 10.16 8.60 10.44 8.54 10.67 8.44 11.11 8.87 11.56 8.66
7.75
7.71
7.67
7.63
7.59
9.60
8.09 10.17 8.61 10.46 8.55 10.69 8.45 11.14 8.88 11.60 8.67
8.33
8.29
8.24
8.20
8.15
9.03
8.18
9.60
8.09 10.19 8.62 10.48 8.55 10.71 8.46 11.17 8.89 11.63 8.68
8.92
8.87
8.81
8.77
8.72
9.02
8.18
9.61
8.10 10.20 8.62 10.51 8.56 10.81 8.49 11.41 8.96
9.21
9.15
9.10
9.05
9.00
8.92
8.13
9.49
8.05 10.08 8.57 10.38 8.51 10.68 8.45 11.28 8.92
9.63
9.58
9.52
9.47
9.41
8.81
8.08
9.38
8.00
9.96
8.53 10.25 8.47 10.55 8.40 11.14 8.88
10.48 10.42 10.36 10.30 10.24
8.24
7.49
8.61
7.99
9.26
7.95
9.83
8.48 10.13 8.42 10.42 8.36 11.01 8.83
11.33 11.26 11.20 11.14 11.07
8.08
7.41
8.47
7.93
9.14
7.90
9.71
8.43 10.00 8.38 10.29 8.31 10.87 8.79
11.49 11.42 11.36 11.29 11.22
7.85
7.31
8.23
7.83
8.84
7.78
9.37
8.31
9.67
8.25 9.96
8.20 10.54 8.68
11.64 11.58 11.51 11.44 11.36
7.62
7.20
7.98
7.72
8.54
7.66
9.03
8.18
9.33
8.13 9.62
8.08 10.21 8.58
10.42 10.35 10.29 10.22 10.14
7.39
7.09
7.74
7.58
8.24
7.54
8.70
8.05
8.99
8.01 9.29
7.97
9.89
8.48
9.20
9.13
9.06
8.99
8.92
7.16
6.98
7.10
6.96
7.54
7.26
7.93
7.77
8.66
7.89 8.47
7.69
9.00
8.20
8.58
8.52
8.45
8.38
8.31
6.20
6.18
6.16
6.14
6.11
9.71
8.44 10.21 8.98 10.46 8.88 10.66 8.76 11.06 9.23 11.46 8.97
6.26
6.23
6.21
6.19
6.16
9.71
8.44 10.21 8.98 10.46 8.88 10.66 8.76 11.06 9.23 11.46 8.97
6.36
6.34
6.31
6.29
6.26
9.71
8.44 10.21 8.98 10.46 8.88 10.66 8.76 11.06 9.23 11.46 8.97
6.47
6.44
6.42
6.39
6.36
9.71
8.44 10.21 8.98 10.46 8.88 10.66 8.76 11.06 9.23 11.46 8.97
6.58
6.55
6.52
6.49
6.46
9.65
8.42 10.18 8.97 10.45 8.88 10.66 8.76 11.08 9.23 11.51 8.98
7.16
7.13
7.10
7.06
7.02
9.59
8.39 10.16 8.96 10.44 8.88 10.67 8.76 11.11 9.24 11.56 8.99
7.75
7.71
7.67
7.63
7.59
9.60
8.40 10.17 8.97 10.46 8.88 10.69 8.77 11.14 9.25 11.60 9.00
8.33
8.29
8.24
8.20
8.15
9.03
8.53
9.60
8.40 10.19 8.97 10.48 8.89 10.71 8.78 11.17 9.26 11.63 9.01
8.92
8.87
8.81
8.77
8.72
9.02
8.53
9.61
8.40 10.20 8.98 10.51 8.90 10.81 8.80 11.41 9.32
9.21
9.15
9.10
9.05
9.00
8.92
8.48
9.49
8.36 10.08 8.94 10.38 8.85 10.68 8.77 11.28 9.29
9.63
9.58
9.52
9.47
9.41
8.81
8.44
9.38
8.32
9.96
8.90 10.25 8.81 10.55 8.73 11.14 9.25
10.48 10.42 10.36 10.30 10.24
8.24
7.79
8.61
8.36
9.26
8.27
9.83
8.86 10.13 8.77 10.42 8.69 11.01 9.21
11.33 11.26 11.20 11.14 11.07
8.08
7.72
8.47
8.30
9.14
8.23
9.71
8.81 10.00 8.73 10.29 8.65 10.87 9.17
11.49 11.42 11.36 11.29 11.22
7.85
7.62
8.23
8.06
8.84
8.12
9.37
8.70
9.67
8.63 9.96
8.55 10.54 9.09
11.64 11.58 11.51 11.44 11.36
7.62
7.47
7.98
7.82
8.54
8.01
9.03
8.59
9.33
8.52 9.62
8.45 10.21 9.00
10.42 10.35 10.29 10.22 10.14
7.39
7.25
7.74
7.58
8.24
7.90
8.70
8.48
8.99
8.42 9.29
8.35
9.89
8.91
9.20
9.13
9.06
8.99
8.92
7.16
7.02
7.10
6.96
7.54
7.39
7.93
7.77
8.66
8.31 8.47
8.11
9.00
8.68
8.58
8.52
8.45
8.38
8.31
PJF000Z318
A
PFA004Z049
A