145
-
'16 • PAC-T-240
(20) Broken wire detection on temperature sensor
(a) Outdoor unit heat exchanger sersor, outdoor air sensor
If the following is detected for 5 second continuously within 2 minutes to 2 minutes and 20 seconds after the
compressor ON, the compressor stops. After a delay of 3 minutes, it restarts but, if the same is detected repeatedly 3
times within 40 minutes, the compressor stops with the anomalous stop. Or with in 20 seconds after power ON.
Note (1) During defrosting and for 3 minutes after the end of defrosting, it is not detected.
• Outdoor unit heat exchanger sensor: -55°C or lower
• Outdoor air temperature sensor: -55 or lower
(b) Discharge pipe temperature sensor
If the following is detected for 5 second continuously within 10 minutes to 10 minutes and 20 seconds after the
compressor ON, the compressor stops. After a delay of 3 minutes, it restarts but, if the same is detected repeatedly 3
times within 40 minutes, the compressor stops with the anomalous stop.
Note (1) During defrosting and for 3 minutes after the end of defrosting, it is not detected.
• Discharge pipe temperature sensor: -25°C or lower
(21) Base heater ON/OFF output control (Option)
(a) Base heater ON conditions
When all of following conditions are met, the base heater is turned ON.
(i) Outdoor air temperature (detected with Tho-A) is 3ºC or lower.
(ii) In the heating mode
(iii) When the compressor is turned ON
(b) Base heater OFF conditions
When either one of following conditions is met, the base heater is turned OFF.
(i) Outdoor air temperature (detected with Tho-A) is 5ºC or higher.
(ii) When the compressor stop has been detected for 30 minutes continuously
(iii) In the cooling or dehumidifying mode
Base heater ON
Base heater OFF
Outdoor air temperature (ºC)
5
3
(22) Reverse operation start for compressor protection
(a) Purpose : It is designed to prevent compressor failure at heating mode.
(b) Detail of operation
When the outdoor air temperature (TH2) is 10ºC or lower and compressor is not operated for long time,
the unit start cooling mode up to 7 minutes at heating mode.
(c) Method for disabling this operation.
When outdoor unit is installed higher than indoor unit, you can disable this control by cutting jumper (J2) of PCB of out-
door unit.
Notes(1) Unit may failure if you disable this control without above installation condition.