146
-
'16 • PAC-T-240
(1) Selfdiagnosis function
(a) Check indicator table
Whether a failure exists or not on the indoor unit can be know by the contents of remote control error code, indoor unit green
LED (power pilot lamp and microcomputer normality pilot lamp) or red LED (check pilot lamp).
(i) Indoor unit
In case of these indoor unit errors, the outdoor control PCB Red LED stays OFF.
Remote control
Indoor control PCB
Location of trouble
Description of trouble
Repair method
Reference
page
Error code Red LED Red LED
Green
LED (1)
No-indication Stays OFF
Stays OFF
Keeps
flashing
—
• Normal operation
—
—
Stays OFF Stays OFF
Indoor unit power source
• Power OFF, broken wire/blown fuse, broken transformer wire
Repair
167
*
3-time
flash
Keeps
flashing
Remote control wires
• Poor connection, breakage of remote control wire * For wire breaking at power ON, the LED is OFF.
Repair
168
Remote control
• Defective remote control PCB
Replacement of
remote control
WAIT
or
INSPECT I/U
Stays OFF
Keeps
flashing
Indoor-outdoor units connection
wire
• Poor connection, breakage of indoor-outdoor units connection wire
Repair
169
-
173
Remote control
• Improper setting of master and slave by remote control
Keeps
flashing
Stays OFF
*
Keeps
flashing
Remote control wires (Noise)
•
Poor connection of remote control signal wire (White)
•
Intrusion of noise in remote control wire
* For wire breaking at power ON, the LED is OFF
Repair
174
Remote control indoor control
PCB
*
• Defective remote control or indoor control PCB (defective communication circuit)?
Replacement of
remote control or
PCB
2-time
flash
Keeps
flashing
Indoor-outdoor units connection
wire
•
Poor connection of wire between indoor-outdoor units during operation
(disconnection, loose connection)
•
Anomalous communication between indoor-outdoor units by noise, etc.
Repair
175
2-time
flash
Keeps
flashing
(Noise)
•
CPU-runaway on outdoor control PCB
Power reset or
Repair
Outdoor control PCB
*
• Occurrence of defective outdoor control PCB on the way of power source (defective communication
circuit)?
Replacement of
PCB
2-time
flash
Keeps
flashing
Outdoor control PCB
•
Defective outdoor control PCB on the way of power source
Replacement
Fuse
•
Blown fuse
1-time
flash
Keeps
flashing
Indoor heat exchanger tempera-
ture thermistor
•
Defective indoor heat exchanger temperature thermistor
(defective element, broken wire, short-
circuit)
• Poor contact of temperature thermistor connector
Replacement, repair
of temperature
thermistor
176
Indoor control PCB
*
•
Defective indoor control PCB (Defective temperature thermistor input circuit)?
Replacement of
PCB
1-time
flash
Keeps
flashing
Indoor return air temperature
thermistor
•
Defective indoor return air temperature thermistor
(defective element, broken wire, short-circuit)
• Poor contact of temperature thermistor connector
Replacement, repair
of temperature
thermistor
177
Indoor control PCB
*
•
Defective indoor control PCB (Defective temperature thermistor input circuit)?
Replacement of
PCB
1-time
flash
Keeps
flashing
Installation or operating condi-
tion
•
Heating over-load
(Anomalously high indoor heat exchanger temperature)
Repair
178
Indoor heat exchanger tempera-
ture thermistor
•
Defective indoor heat exchanger temperature thermistor (short-circuit)
Replacement of
temperature therm-
istor
Indoor control PCB
*
•
Defective indoor control PCB
(Defective temperature thermistor input circuit)?
Replacement of
PCB
1-time
flash
Keeps
flashing
Drain trouble
•
Defective drain pump (DM), broken drain pump wire
, disconnected connector
Replacement, repair
of DM
179
Float switch
•
Anomalous float switch operation
(malfunction)
Repair
Indoor control PCB
*
•
Defective indoor control PCB
(Defective float switch input circuit)
*
•
Defective indoor control PCB
(Defective DM drive output circuit)?
Replacement of
PCB
Option
•
Defective optional parts
(At optional anomalous input setting)
Repair
Stays OFF
Keeps
flashing
Number of connected indoor
units
•
When multi-unit control by remote control is performed, the number of units is over
Repair
180
Keeps
flashing
Keeps
flashing
Address setting error
• Address setting error of indoor units
Repaie
181
1(2)-time
flash
Keeps
flashing
Fan motor
•
Defective fan motor
Replacement, repair
182
Indoor power PCB
•
Defective indoor power PCB
Replacement
1-time
flash
Keeps
flashing
Indoor control PCB
•
Improper operation mode setting
Repair
183
12. MAINTENANCE DATA
12.1 FDT, FDE, FDU, FDUM, FDF series
12.1.1 Diagnosing of microcomputer circuit