212
-
'16 • PAC-T-240
'09•SRK-DB-087D
(7) Inspection procedures corresponding to detail of trouble
Sensor error
Sensor temperature characteristics (Room
temp., indoor heat exchanger temp., out-
door heat exchanger temp., outdoor air
temp.)
Temperature (˚C)
Resistance (k
)
30
25
20
15
10
5
30
20
10
40
50
60
70
0
-10
Discharge pipe sensor temperature characteristics
Indoor fan motor error
control
Broken sensor wire,
connector poor connection
0
0
20
40
60
80
100
120 135
20
40
60
80
100
120
140
160
180
Temperature (˚C)
Resistance (k
)
Defective fan motor, connector poor
connection, defective indoor control PCB
215 for the fan motor and indoor control PCB
Power source reset
Is it normalized?
Malfunction by temporary noise
Replace fan motor. (If the
error persists after replacing
the fan motor, replace the
indoor control PCB.)
check procedure.
control
control
control