248
-
'16 • PAC-T-240
(2) Ceiling suspended type (FDE)
Information to identify the model(s) to which the information relates to:
If function includes heating: Indicate the heating season the
Indoor unit model name
FDE100VG
information relates to. Indicated values should relate to one
Outdoor unit model name
FDC100VNP
heating season at a time. Include at least the heating season 'Average'.
Function(indicate if present)
Average(mandatory)
Yes
cooling
Yes
Warmer(if designated)
No
heating
Yes
Colder(if designated)
No
Item
symbol
value
unit
Item
symbol
value
class
Design load
Seasonal efficiency and energy efficiency class
cooling
Pdesignc
10.0
kW
cooling
SEER
6.73
A++
heating / Average
Pdesignh
8.1
kW
heating / Average
SCOP/A
4.44
A+
heating / Warmer
Pdesignh
-
kW
heating / Warmer
SCOP/W
-
-
heating / Colder
Pdesignh
-
kW
heating / Colder
SCOP/C
-
-
unit
Declared capacity at outdoor temperature Tdesignh
Back up heating capacity at outdoor temperature Tdesignh
heating / Average (-10
℃
)
Pdh
8.1
kW
heating / Average (-10
℃
)
elbu
0
kW
heating / Warmer (2
℃
)
Pdh
-
kW
heating / Warmer (2
℃
)
elbu
-
kW
heating / Colder (-22
℃
)
Pdh
-
kW
heating / Colder (-22
℃
)
elbu
-
kW
Declared capacity for cooling, at indoor temperature 27(19)
℃
and
Declared energy efficiency ratio, at indoor temperature 27(19)
℃
and
outdoor temperature Tj
outdoor temperature Tj
Tj=35
℃
Pdc
10.00
kW
Tj=35
℃
EERd
3.76
-
Tj=30
℃
Pdc
7.37
kW
Tj=30
℃
EERd
5.30
-
Tj=25
℃
Pdc
4.80
kW
Tj=25
℃
EERd
8.14
-
Tj=20
℃
Pdc
3.50
kW
Tj=20
℃
EERd
11.67
-
Declared capacity for heating / Average season, at indoor
Declared coefficient of performance / Average season, at indoor
temperature 20
℃
and outdoor temperature Tj
temperature 20
℃
and outdoor temperature Tj
Tj=-7
℃
Pdh
7.20
kW
Tj=-7
℃
COPd
2.58
-
Tj=2
℃
Pdh
4.40
kW
Tj=2
℃
COPd
4.44
-
Tj=7
℃
Pdh
2.80
kW
Tj=7
℃
COPd
5.96
-
Tj=12
℃
Pdh
2.90
kW
Tj=12
℃
COPd
7.07
-
Tj=bivalent temperature
Pdh
8.10
kW
Tj=bivalent temperature
COPd
2.71
-
Tj=operating limit
Pdh
7.17
kW
Tj=operating limit
COPd
2.56
-
Declared capacity for heating / Warmer season, at indoor
Declared coefficient of performance / Warmer season, at indoor
temperature 20
℃
and outdoor temperature Tj
temperature 20
℃
and outdoor temperature Tj
Tj=2
℃
Pdh
-
kW
Tj=2
℃
COPd
-
-
Tj=7
℃
Pdh
-
kW
Tj=7
℃
COPd
-
-
Tj=12
℃
Pdh
-
kW
Tj=12
℃
COPd
-
-
Tj=bivalent temperature
Pdh
-
kW
Tj=bivalent temperature
COPd
-
-
Tj=operating limit
Pdh
-
kW
Tj=operating limit
COPd
-
-
Declared capacity for heating / Colder season, at indoor
Declared coefficient of performance / Colder season, at indoor
temperature 20
℃
and outdoor temperature Tj
temperature 20
℃
and outdoor temperature Tj
Tj=-7
℃
Pdh
-
kW
Tj=-7
℃
COPd
-
-
Tj=2
℃
Pdh
-
kW
Tj=2
℃
COPd
-
-
Tj=7
℃
Pdh
-
kW
Tj=7
℃
COPd
-
-
Tj=12
℃
Pdh
-
kW
Tj=12
℃
COPd
-
-
Tj=bivalent temperature
Pdh
-
kW
Tj=bivalent temperature
COPd
-
-
Tj=operating limit
Pdh
-
kW
Tj=operating limit
COPd
-
-
Tj=-15
℃
Pdh
-
kW
Tj=-15
℃
COPd
-
-
Bivalent temperature
Operating limit temperature
heating / Average
Tbiv
-10
℃
heating / Average
Tol
-15
℃
heating / Warmer
Tbiv
-
℃
heating / Warmer
Tol
-
℃
heating / Colder
Tbiv
-
℃
heating / Colder
Tol
-
℃
Cycling interval capacity
Cycling interval efficiency
for cooling
Pcycc
-
kW
for cooling
EERcyc
-
-
for heating
Pcych
-
kW
for heating
COPcyc
-
-
Degradation coefficient
Degradation coefficient
cooling
Cdc
0.25
-
heating
Cdh
0.25
-
Electric power input in power modes other than 'active mode'
Annual electricity consumption
off mode
Poff
10
W
cooling
Qce
521
kWh/a
standby mode
Psb
10
W
heating / Average
Qhe
2556
kWh/a
thermostat-off mode
Pto
36
W
heating / Warmer
Qhe
-
kWh/a
crankcase heater mode
Pck
0
W
heating / colder
Qhe
-
kWh/a
Capacity control(indicate one of three options)
Other items
Sound power level(indoor)
Lwa
64
dB(A)
Sound power level(outdoor)
Lwa
70
dB(A)
fixed
No
Global warming potential
GWP
1975
kgCO2eq.
staged
No
Rated air flow(indoor)
-
1920
m3/h
variable
Yes
Rated air flow(outdoor)
-
4500
m3/h
Contact details for obtaining
Name and address of the manufacturer or of its authorised representative.
more information
Mitsubishi Heavy Industries Air-Conditioning Europe, Ltd.
7 Roundwood Avenue, Stockley Park, Uxbridge, Middlesex, UB11 1AX,
United Kingdom
PFA004Z024
C