'19 • PAC-DB-333
Model
Item
FDE100VNPWVH
Indoor unit
FDE100VH
Outdoor unit
FDC100VNP-W
Power source
1 Phase 220-240V 50Hz / 220V 60Hz
Operation
data
Nominal cooling capacity (range)
kW
10.0 [ 2.1(Min.) - 10.2(Max.)]
Nominal heating capacity (range)
kW
10.0 [ 1.7(Min.) - 10.4(Max.)]
Power consumption
Cooling
kW
3.00
Heating
2.36
Max power consumption
4.46
Running current
Cooling
A
12.8/13.4
Heating
10.1/10.5
Inrush current, max current
5, 19
Power factor
Cooling
%
98/98
Heating
98/98
EER
Cooling
3.33
COP
Heating
4.24
Sound power level
Cooling
dB(A)
64
68
Heating
67
Sound pressure level
Cooling
P-Hi: 48 Hi: 43 Me: 38 Lo: 34
56
Heating
54
Silent mode
sound pressure level
Cooling
—
52
Heating
50
Exterior dimensions (Height x Width x Depth)
mm
250 × 1,620 × 690
750 × 880(+88) × 340
Exterior appearance
(Munsell color)
(RAL color)
Plaster white
(6.8Y8.9/0.2) near equivalent
(RAL 9003) near equivalent
Stucco white
(4.2Y7.5/1.1) near equivalent
(RAL 7044) near equivalent
Net weight
kg
43
57
Compressor type & Q'ty
—
RMT5118SWP1 ( Twin rotary type )×1
Compressor motor (Starting method)
kW
—
Direct line start
Refrigerant oil (Amount, type)
L
—
0.675 ( DIAMOND FREEZE MB75 )
Refrigerant (Type, amount, pre-charge length)
kg
R32 1.7 in outdoor unit (Incl. the amount for the piping of 15m)
Heat exchanger
Louver fin & inner grooved tubing
M shape fin & inner grooved tubing
Refrigerant control
Electronic expansion valve
Fan type & Q'ty
Centrifugal fan ×4
Propeller fan ×1
Fan motor (Starting method)
W
80 < Direct line start >
86 < Direct line start >
Air flow
Cooling
m
3
/min
P-Hi: 32 Hi: 26 Me: 21 Lo: 16.5
63
Heating
55
Available external static pressure
Pa
0
—
Outside air intake
Not possible
—
Air filter, Quality / Quantity
Pocket plastic net ×2(Washable)
—
Shock & vibration absorber
Rubber sleeve (for fan motor)
Rubber sleeve (for fan motor & compressor)
Electric heater
W
—
—
Operation
control
Remote control
(Option) Wired : RC-EX3A,RC-E5,RCH-E3 Wireless : RCN-E-E3
Room temperature control
Thermostat by electronics
Operation display
—
Safety equipments
Compressor overheat protection, Overcurrent protection
Frost protection, Serial signal error protection, Indoor fan motor error protection
Heating overload protection( High pressure control ), Cooling overload protection
Installation
data
Refrigerant piping size (O.D)
Liquid line
mm
I/U
φ
9.52 (3/8") Pipe
φ
6.35(1/4")x0.8 O/U
φ
6.35 (1/4")
Gas line
φ
15.88 (5/8") Pipe
φ
15.88(5/8")x1.0
φ
15.88 (5/8")
Connecting method
Flare piping
Flare piping
Attached length of piping
m
—
—
Insulation for piping
Necessary (both Liquid & Gas lines)
Refrigerant line (one way) length
m
Max.30m
Vertical height diff. between
O
/U and I/U
m
Max.20m (Outdoor unit is higher) / Max.20m (Outdoor unit is lower)
Drain hose
Hose connectable with VP20(O.D.26)
Hole size
φ
20 x 4 pcs
Drain pump, max lift height
mm
—
—
Recommended breaker size
A
—
L.R.A. (Locked rotor ampere)
A
5
Interconnecting wires
Size x Core number
1.5
mm
2
x 4 cores(Including earth cable)/ Termainal block(Screw fixing type)
IP number
IPX0
IPX4
Standard accessories
Mounting kit, Drain hose
Drain elbow, Drain hole grommet
Option parts
Motion sensor : LB-E
PFA004Z088
H
The pipe length is 7.5m.
Notes (1) The data are measured at the following conditions.
(2) This air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
(4) Select the breaker size according to the own national standard.
(5) The operation data indicate when the air-conditioner is operated at 230V 50Hz or 220V 60Hz.
Item
Operation
Indoor air temperature
Outdoor air temperature
Standards
DB
WB
DB
WB
Cooling
27˚C
19˚C
35˚C
24˚C
ISO5151-T1
Heating
20˚C
—
7˚C
6˚C
ISO5151-H1
- 10 -