'19 • PAC-DB-333
Installation space
30mm
30mm
30mm
120mm
配線
30mm
30mm
30mm
120mm
Wiring
R/C temperature sensor
Secure minimum spaces for disassembling the case.
Upper left and Upper right sides
……30mm or more
Bottom side…120mm or more
If using L-shaped screwdriver, 50mm or more is
available.
Dimensions (Viewed from front)
37
23
23
固定穴
18.3
83.5 120
19
120
37
23
23
19
120
Fixing holes
83.5
120
18.3
≦
200 m
0.5 mm
2
x 2 cores
≦
300m
0.75 mm
2
x 2 cores
≦
400m
1.25 mm
2
x 2 cores
≦
600m
2.0 mm
2
x 2 cores
● Do not install the remote control at following places.
1) It could cause break-down or deformation of remote control.
・
Where it is exposed to direct sunlight
・
Where the ambient temperature becomes 0 °C or below, or 40 °C or above
・
Where the surface is not flat
・
Where the strength of installation area is insufficient
2) Moisture may be attached to internal parts of the remote control, resulting in a display failure.
・
Place with high humidity where condensation occurs on the remote control
・
Where the remote control gets wet
3) Accurate room temperature may not be detected using the temperature sensor of the remote control.
・
Where the average room temperature cannot be detected
・
Place near the equipment to generate heat
・
Place affected by outside air in opening/closing the door
・
Place exposed to direct sunlight or wind from air-conditioner
・
Where the difference between wall and room temperature is large
4) When you are using the automatic grille up and down panel in the IU, you may not be able
to confirm the up and down motion.
・
Where the IU cannot be visually confirmed
● When installing the unit at a hospital, telecommunication facility, etc., take measures to
suppress electric noises.
It could cause malfunction or break-down due to hazardous effects on the inverter, private power generator,
high frequency medical equipment, radio communication equipment, etc.
The influences transmitted from the remote control to medical or communication equipment could disrupt medical
activities, video broadcasting or cause noise interference.
R/C cable:0.3mm
2
x2 cores
When the cable length is longer than 100 m,
the max size for wires used in the R/C case
is 0.5 mm
2
. Connect them to wires of larger
size near the outside of R/C. When wires are
connected, take measures to prevent water,
etc. from entering inside.
Adapted RoHS directive
(3) Remote control (Option parts)
(a) Wired remote control
Model RC-EX3A
PJZ000Z333