'19 • PAC-DB-333
5
10
15
20
25
30
-20
-15
-10
-5
0
5
10
15
20
25
-20
-10
0
10
20
30
40
50
10
12
14
16
18
20
22
24
26
Operating temperature range
■
Cooling
■
Heating
Decline in cooling and heating capacity or operation stop may occur when the outdoor unit is installed in
places where natural wind can increase or decrease its design air flow rate.
46
℃
DB
-15
℃
DB
Usage range in cooling
Indoor air temperature (
℃
WB)
Outdoor air temperature (
℃
WB)
Outdoor air temperature (
℃
DB)
Indoor air temperature (
℃
DB)
PJF000Z
871
“CAUTION”
Cooling operation under low outdoor air temperature conditions
PAC models can be operated in cooling mode at low outdoor air temperature condition within above temperature range. However in
case of severely low temperature conditions if the following precaution is not observed, it may not be operated in spite of operable
temperature range mentioned above and cooling capacity may not be established under certain conditions.
[Precaution]
In case of severely low temperature condition
1) Install the outdoor unit at the place where strong wind cannot blow directly into the outdoor unit.
2) If there is no installation place where can prevent strong wind from directly blowing into the outdoor unit, mount the flex flow
adapter (prepared as optional part) or like such devices onto the outdoor unit in order to divert the strong wind.
[Reason]
Under the low outdoor air temperature conditions of -5
℃
or lower, the outdoor fan is controlled at lower or lowest speed by outdoor
fan control, but if strong wind directly blow into the outdoor unit, the outdoor heat exchanger temperature will drop more.
This makes high and low pressures to drop as well. This low pressure drop makes the indoor heat exchanger temperature to drop and
will activate anti-frost control at indoor heat exchanger at frequent intervals, that cooling operation may not be established for any
given time.
-
3
2
-
Usage range in heating
'19 • PAC-DB-311D
5
10
15
20
25
30
-20
-15
-10
-5
0
5
10
15
20
25
-20
-10
0
10
20
30
40
50
10
12
14
16
18
20
22
24
26
Operating temperature range
■
Cooling
■
Heating
Decline in cooling and heating capacity or operation stop may occur when the outdoor unit is installed in
places where natural wind can increase or decrease its design air flow rate.
46
℃
DB
-15
℃
DB
Usage range in cooling
Indoor air temperature (
℃
WB)
Outdoor air temperature (
℃
WB)
Outdoor air temperature (
℃
DB)
Indoor air temperature (
℃
DB)
PJF000Z
871
“CAUTION”
Cooling operation under low outdoor air temperature conditions
PAC models can be operated in cooling mode at low outdoor air temperature condition within above temperature range. However in
case of severely low temperature conditions if the following precaution is not observed, it may not be operated in spite of operable
temperature range mentioned above and cooling capacity may not be established under certain conditions.
[Precaution]
In case of severely low temperature condition
1) Install the outdoor unit at the place where strong wind cannot blow directly into the outdoor unit.
2) If there is no installation place where can prevent strong wind from directly blowing into the outdoor unit, mount the flex flow
adapter (prepared as optional part) or like such devices onto the outdoor unit in order to divert the strong wind.
[Reason]
Under the low outdoor air temperature conditions of -5
℃
or lower, the outdoor fan is controlled at lower or lowest speed by outdoor
fan control, but if strong wind directly blow into the outdoor unit, the outdoor heat exchanger temperature will drop more.
This makes high and low pressures to drop as well. This low pressure drop makes the indoor heat exchanger temperature to drop and
will activate anti-frost control at indoor heat exchanger at frequent intervals, that cooling operation may not be established for any
given time.
-
3
2
-
Usage range in heating
'19 • PAC-DB-311D
PCA001Z871
- 37 -