background image

'19 • PAC-DB-333

2. REFRIGERANT PIPING WORK

1)

Restrictions

on

unit

installation

and

use

 

Check

the

following

points

in

light

of

the

indoor

unit

specifications

and

the

installation

site.

 

Obse

rve

the

following

restrictions

on

unit

installation

and

use.

  

Improper

installation

can

result

in

a

compressor

failure

or

pe

rformance

degradation

.

2)

Determination

of

pipe

size

 

Determine

refrigerant

pipe

size

pursuant

to

the

following

guidelines

based

on

the

  

indoor

unit

specifications.

Gas pipe

Liquid pipe

ø15.88

ø6.35

Flare

Flare

ø15.88

ø6.35

ø15.88

ø9.52

1. HAULAGE AND INSTALLATION

(T

ake particular care in car

rying in or moving the unit, and always pe

rform such an operation with two or more persons.)

Intake

The

height

of

a

wall

is

1200mm

or

less.

(

se

rvice

  space

)

Intake

Outlet

Fasten

with

bolts

(M10-12)

Use

a

thicker

block

to

 

anchor

deepe

r.

Use

a

long

block

to

extend

the

width.

CAUTION

When

a

unit

is

hoisted

with

slings

for

haulage,

take

into

consideration

the

offset

of

its

gravity

center

position.

  

If

not

properly

balanced,

the

unit

can

be

thrown

off-balance

and

fall.

1)

Delivery

Deliver

the

unit

as

close

as

possible

to

the

installation

site

before

removing

it

from

the

packaging.

When

you

have

to

unpack

the

unit

for

a

compelling

reason

before

you

haul

it

to

the

installation

point,

hoist

the

unit

with

nylon

slings

or

ropes

and

protection

pads

so

that

you

may

not

damage

the

unit.

2)

Portage

The

right

hand

side

of

the

unit

as

viewed

from

the

front

(diffuser

side)

is

heavie

r.

A

person

car

rying

the

right

hand

side

must

take

heed

of

this

fact.

A

person

car

rying

the

left

hand

side

must

hold

with

his

right

hand

the

handle

provided

on

the

front

panel

of

the

unit

and

with

his

left

hand

the

corner

column

section

.

5)

Installation

space

W

alls surrounding the unit in the four sides are not acceptable.

There must be a 1-meter or larger space in the above.

When more than one unit are installed side by side, provide a 250mm or wider interval between them as a service  space.  In order to facilitate servicing of controllers, please provide a sufficient space between units so that their  top plates can be removed easily.

Where a danger of short-ci

rcuiting exists, install guide louvers.

When more than one unit are installed, provide sufficient intake space consciously so that short-ci

rcuiting may not occur

.

Where

piling

snow

can

bu

ry

the

outdoor

unit,

provide

proper

snow

guards.

L

3

L

2

L

4

L

1

Example installation

Size

In installing the unit, fix the unit

’s legs with bolts specified on the above.

The protrusion of an anchor bolt on the front side must be kept within 15 mm.

Securely install the unit so that it does not fall over during earthquakes or strong winds, etc.

Refer to the above illustrations for information regarding concrete foundations.

Install the unit in a level area. (With a gradient of 5 mm or less.) Im

pr

op

er

 in

st

al

la

tio

ca

re

su

lt 

in

a

co

m

pr

es

so

rf

ai

lu

re

, b

ro

ke

n

pi

pi

ng

w

ith

in

th

e

un

it

an

ab

no

rm

al

 n

oi

se

 g

en

er

at

io

n.

6)

Installation

L

H

Outdoor unit

Indoor unit

CAUTION

Th

e

us

e

re

st

ric

tio

ns

ap

pe

ar

in

g

in

th

e

ta

bl

e

ab

ov

e

ar

e

ap

pl

ica

bl

e

to

th

e

st

an

da

rd

pi

pe

siz

e

co

m

bi

na

tio

ns

sh

ow

n

in

th

e

ta

bl

e

be

lo

w.

W

he

re

an

ex

ist

in

g

pi

pe

 s

ys

te

m

 is

 u

til

ize

d,

di

ffe

re

nt

 o

ne

-w

ay

pi

pe

 le

ng

th

 re

st

ric

tio

ns

sh

ou

ld

 a

pp

ly 

de

pe

nd

in

on

 it

pi

pe

siz

e.

Fo

r m

or

e

in

fo

rm

at

io

n,

 p

lea

se

se

e

“5

. U

TI

LI

ZA

TI

ON

OF

 E

XI

ST

IN

G

PI

PI

NG

.”

Outdoor unit connected

Refrigerant piping (branch pipe

L)

Indoor unit connected

About brazing

When pipe is brazing.

(2)

If

the

unit

can

be

affected

by

strong

wind,

following

measures

are

required.

Strong

wind

can

cause

damage

of

fan

(fan

motor),

or

can

cause

pe

rformance

degradation,

or

can

trigger

anomalous

stop

of

the

unit

due

to

rising

of

high

pressure.

3)

 Refrigerant

 pipe

 wall

 thickness

 and

 material

Select

 refrigerant

 pipes

 of

 the

 table

 shown

 on

 the

 right

 wall

 thickness

 and

 material

 as

 specified

 for

 each

 pipe

 size.

Pipe diameter [mm]

Minimum pipe wall thickness [mm]

Pipe material*

ø6.35

0.8

O-type pipe

ø15.88

1.0

O-type pipe

*Phosphorus deoxidized seamless copper pipe  ICS 23.040.15, ICS 77.150.30

NOTE

Select

 pipes

 having

 a

 wall

 thickness

 larger

 than

 the

 specified

 minimum

 pipe

 thickness.

He

avy

Pad

L1

L2

L3

L4

Open

300

100

250

Open

250

150

250

500

Open

100

250

(mm)

I

II

III

60

580

340

19

380

418

19

880

87.9

15

150

150

Intake

Outlet

① 

Anchor bol tfixed position

② 

Notabilia for installation

Plug the end of the pipe with tape, or other  material, and fill the pipe with nitrogen gas.

Only use nitrogen gas (N

2

)

Taping

N

2

Nitrogen

Brazing

Station valve

Prima

ry side

Seconda

ry side

0.5MPa

Hand

Relief valve

Nitrogen

gas

Brazing

must

be

performed

under

a

nitrogen

gas

flo

w

.

Without

nitrogen

gas,

a

large

quantity

of

foreign

matters

(oxidized

film)

are

created,

causing

a

critical

failure

from

capilla

ry

tube

or

expansion

valve

clogging.

If the refrigerant is existing in the pipe at brazing, poisonous gas is produced.

Wind

 direction

Wind

 direction

Over

 500

 mm

2.Install the outlet air blow side of 

the unit in a position perpendicular  to the direction of wind.

3.

The

 unit

 should

 be

 installed

 on 

the

 stable

 and

 level

 foundation.

If 

the

 foundation

 is

 not

 level, 

the

 down

 the

 unit

 with

 wires.

1.

Install the outlet air blow side of the  unit to face a wall of building, or  provide a fence or a windbreak screen.

7)  To run the unit for a cooling operation, 

when the outdoor temperature is –5°C or lower. 

 

When the outdoor air temperature is –5°C or lower, provide a snow hood to the outdoor unit on site. So that strong wind will not blow against the outdoor heat exchanger directly.

4)

Caution

about

selection

of

installation

location

(1)

If

the

unit

is

installed

in

the

area

where

the

snow

will

accumulate,

following

measures

are

required.

The

bottom

plate

of

unit

and

intake,

outlet

may

be

blocked

by

sno

w

.

1

2

Provide

a

snow

hood

to

the

outdoor

unit

on

site.

3

Install

the

unit

under

eaves

or

provide

the

roof

on

site.

Since

drain

water

generated

by

defrost

control

may

freeze,

following

measures

are

required.

Don’t execute drain piping work 

by using a drain elbow and drain grommets (accessories).

 [Refer to Drain piping work.]

Install the unit on the base so  that the bottom is higher than  snow cover surface, and  draining water is secured.

● 

Attached heater on a base plate on site, if there is possibility to freeze drain water. In case that the product has a corrective drainage system, the drainage paths should have suitable  threatment against freezing but be sure not to melt the material of drainage paths with heat.

30m

or less

20m

or less

20m

or less

L

H

H

Restrictions

Dimensional restrictions

Marks appearing in the drawing on the right

Main pipe length

Elevation difference between 

Indoor unit

indoor and outdoor units

When the outdoor unit is positioned higher

FDT, FDE, FDU, FDUM, SRK

When the outdoor unit is positioned lower

3)

  S

el

ec

tio

of

 in

stalla

tio

lo

ca

tio

fo

th

ou

td

oo

un

it

Be

 s

ur

to

 sele

ct

 a

 s

ui

ta

ble

 in

st

alla

tio

pla

ce

 in

 c

on

si

de

ra

tio

of

 fo

llo

w

in

co

nd

iti

on

s.

 

pla

ce

 w

he

re

 it

 is

 h

or

iz

on

ta

l, 

st

ab

le

 a

nd

 c

an

 e

nd

ur

th

un

it 

w

ei

gh

t a

nd

 wi

ll 

no

t a

llo

w

 v

ib

ra

tio

tr

an

sm

itt

an

ce

 

of

 th

un

it.

 

pla

ce

 w

he

re

 it

 c

an

 b

fr

ee

 fr

om

 p

os

si

bi

lit

of

 b

ot

he

rin

ne

ig

hb

or

du

to

 n

oi

se

 o

ex

ha

us

t a

ir 

fr

om

 th

un

it.

 

pla

ce

 w

he

re

 th

un

it 

is

 n

ot

 e

xp

os

ed

 to

 o

il 

sp

la

sh

es

.

 

pla

ce

 w

he

re

 it

 c

an

 b

fr

ee

 fr

om

 d

an

ge

of

 fl

am

m

ab

le

 g

as

 lea

ka

ge

.

 

pla

ce

 w

he

re

 d

ra

in

 w

at

er

 c

an

 b

di

sp

os

ed

 w

ith

ou

t a

ny

 tr

ou

bl

e.

 

pla

ce

 w

he

re

 th

un

it 

wil

l n

ot

 b

af

fe

ct

ed

 b

he

at

 r

ad

ia

tio

fr

om

 o

th

er

 h

ea

t s

ou

rc

e.

 

pla

ce

 w

he

re

 s

no

w

 wil

l n

ot

 a

cc

um

ul

at

e.

 

pla

ce

 w

he

re

 th

un

it 

ca

be

 k

ep

t aw

ay

 5

m

 o

m

or

fr

om

 T

se

t a

nd

/o

ra

di

recei

ve

in

 o

rd

er

 to

 a

vo

id

 a

ny

 

ra

di

or

 T

in

te

rf

er

en

ce

.

 

pla

ce

 w

he

re

 g

oo

ai

ci

rc

ula

tio

ca

be

 s

ec

ur

ed

, a

nd

 e

no

ug

 h

se

rvi

ce

 s

pa

ce

 c

an

 b

se

cu

re

fo

ma

in

te

na

nc

an

se

rvic

of

 th

un

it 

sa

fe

ly

.

 

pla

ce

 w

he

re

 th

un

it 

wi

ll 

no

t b

af

fec

te

by

 el

ec

tr

om

ag

ne

tic

 wav

es

 a

nd

/o

r h

ig

h-

ha

rm

on

ic

 wav

es

 g

en

er

at

ed

 b

ot

he

eq

ui

pm

en

t.

 

pla

ce

 w

he

re

 c

hemic

al

 s

ub

st

an

ce

lik

su

lfu

ric

 g

as

, c

hl

or

ic

 g

as

, a

ci

an

alka

li 

(in

cl

ud

in

ga

m

m

on

ia

), 

w

hi

ch

 c

an

 

ha

rm

 th

un

it,

 wil

l n

ot

 b

ge

ne

ra

te

an

no

t r

em

ai

n.

 

If 

op

er

at

io

is

 c

on

du

ct

ed

 w

he

th

ou

td

oo

ai

te

m

pera

tu

re

 is

 -

lo

w

er

, t

he

 o

ut

do

or

 u

ni

t s

ho

ul

be

 in

stall

ed

 

at

 a

 p

lace

 w

he

re i

t i

no

t i

nfl

ue

nc

ed

 b

na

tu

ral w

in

d.

 

pla

ce

 w

he

re

 s

tr

on

w

in

d wi

ll 

no

t b

lo

w

 a

ga

in

st

 th

ou

tle

t a

ir 

bl

ow

 o

f t

he

 u

ni

t.

D

no

in

st

al

l t

he

 u

ni

in

 p

lac

es

 w

hi

ch

 e

xp

os

ed

 t

se

br

ee

ze

 (

e.

g.

 c

oa

st

al

 a

re

a)

 o

cal

ci

um

 c

hl

or

id

(e

.g

. s

no

w

 

mel

tin

ag

en

t)

, e

xp

os

ed

 to

 a

m

m

on

ia

 s

ub

st

an

ce

 (

e.

g.

 o

rg

an

ic

 fe

rt

ili

ze

r)

.

PSC012D137

Notabilia as a unit designed for R32

• 

Read the “SAFETY PRECAUTIONS” ca

refully first of all and strictly follow it during the installation work in o

rder 

to p

rotect yourself.

• 

The p

recautionary items mentioned below a

re distinguished into two levels,                          and                       .

                              : 

W

rong installation would cause serious consequences such as injuries or death.

                              : 

W

rong installation might cause serious consequences depending on ci

rcumstances.

Both mentions the important items to p

rotect your health and safety so strictly follow them by any means.

• 

Be su

re to confirm no anomaly on the equipment by commissioning after completed installation and explain the 

operating methods as well as the maintenance methods of this eq

uipment to the user accor

ding to the owner

’s 

manual.

• 

Keep the installation manual together with owner

’s manual at a place whe

re any user can 

read at any time. 

Mo

reover if necessar

y, ask to hand them to a new use

r.

• 

For installing qualified personnel, take p

recautions in 

respect to themselves by using suitable p

rotective 

clothing, g

roves, etc., and then perform the installation works.

• 

Please pay attention not to fall down the tools, etc. when installing the unit at the high position.

• 

If unusual noise can be hea

rd during operation, consult the deale

r.

• 

The meanings of “Marks” used he

re a

re shown as follows:

• 

This installation manual deals with outdoor units and general installation specifications onl

y.  For indoor units, 

refer to the 

respective installation manuals supplied with the units.

• 

When install the unit, be su

re to check whether the selection of installation place, power source specifications, usage limitation (piping length, height di

ffe

rences between indoor and outdoor units, power 

source voltage and etc.) and installation spaces. 

SAFETY PRECAUTION

S

Never do it under any ci

rcumstances.

Always do it acco

rding to the instruction.

CAUTION

W

ARNING

CAUTION

W

ARNING

W

ARNIN

G

CAUTION

• 

Car

ry out the electrical work for ground lead with care.

 

Do not connect the ground lead to the gas line

, water line

, lightning conductor or telephone line

’s ground lead

. Incorrect grounding can cause unit faults such as electric shocks due to short-circuiting.

• 

Ensure that no air enters in the refrigerant circuit when the unit is  installed and rem

oved.

 

If 

ai

r e

nt

ers in

 th

re

fri

ge

ra

nt

 c

irc

ui

t, t

he

 p

re

ss

ur

e in t

he

 re

fri

ge

ra

nt c

ircu

it 

be

co

m

es

 to

o hi

gh

, w

hi

ch

 c

an

 c

au

se

 b

ur

st

 a

nd

 p

er

so

na

l in

ju

ry

.

• 

Do

 n

ot

 p

ro

ce

ss

in

g,

 s

pl

ic

th

po

w

er

 c

or

d,

 o

r s

ha

re

 a

 s

oc

ke

t wit

ot

he

r p

ow

er

 p

lu

gs

.

 

This may cause fire or electric shock due to defecting contact

, defecting insulation 

and ove

r-current etc.

• 

Use the circuit breaker for all pole correct  capacit

y.

 Circuit breaker 

should be the one that disconnect all poles under 

over current.

 

Using the incorrect circuit breake

r, it can cause the unit malfunction and fire.

• 

Install isolator or disconnect switch on the power source wiring in  accordance with the local codes and regulations.

 

The isolator should be locked in OFF state in accordance with EN60204-1.

• 

Af

te

r m

ai

nt

en

an

ce

, al

l w

iri

ng

, w

iri

ng

 ti

es 

an

th

e li

ke

, s

ho

ul

be r

et

ur

ne

to

 th

ei

r o

rig

in

al sta

te

 a

nd

 wi

rin

ro

ut

e,

 a

nd

 th

ne

ce

ss

ar

cl

ea

ra

nc

fr

om

 

all

 m

eta

l p

ar

ts

 s

ho

ul

be

 s

ec

ur

ed

.

• 

Se

cu

re

 a 

sp

ac

e f

or

 in

stallat

io

n,

 in

sp

ec

tio

an

m

ain

te

na

nc

sp

ec

ifi

ed

 in

 

th

m

an

ua

l.

 

Insufficient space can result in accident such as personal inju

ry due to falling 

from the installation place.

• 

Earth 

lea

ka

ge

 b

re

ak

er

 m

ust

 b

e instal

le

d

If 

th

ea

rth 

le

ak

ag

br

ea

ke

r is 

no

t in

st

al

le

d,

 it

 c

an

 c

au

se

 fir

or

 e

le

ct

ric 

sh

oc

ks

.

• 

Do

 no

t i

nstall 

th

un

it i

th

lo

cati

on

s lis

ted

 be

lo

w

.

• 

Lo

ca

tio

ns

 w

he

re 

ca

rb

on

 fi

be

r, 

m

et

al p

ow

de

r or

 a

ny

 p

ow

de

r is 

flo

ati

ng

.

• 

Lo

ca

tio

ns

 w

he

re

 a

ny

 subs

ta

nc

es

 th

at

 c

an 

af

fe

ct

 th

e un

it such

 a

s sulphid

gas

ch

lo

rid

e g

as

, aci

an

al

ka

lin

ca

oc

cu

r. 

• 

Veh

ic

le

and shi

ps

.

• 

Lo

ca

tio

ns

 w

he

re 

co

sm

et

ic o

r spe

ci

al sp

ra

ys

 a

re

 ofte

n u

sed

.

• 

Lo

ca

tions

 w

ith di

re

ct

 ex

posu

re

 o

f o

il mi

st

 a

nd 

st

ea

m su

ch

 a

s k

itch

en a

nd

 

m

ach

in

e pl

an

t.

• 

Lo

ca

tions

 w

he

re

 a

ny

 m

achines

 w

hich ge

ne

ra

te

 high

 fr

eq

ue

ncy

 h

ar

m

on

ic

s a

re

 

us

ed

.

• 

Lo

ca

tio

ns

 w

ith sa

lty a

tmosphe

re

s such 

as 

coa

st

lin

es

• 

Lo

ca

tio

ns

 w

ith 

he

av

y sn

ow

 (I

f in

st

all

ed

, b

e s

ure

 to

 p

ro

vide 

ba

se

 fr

am

and sn

ow

 

ho

od

 m

en

tio

ne

d i

th

m

an

ua

l).

• 

Lo

ca

tions

 w

he

re

 th

e uni

t is

 e

xp

os

ed 

to

 chimn

ey

 smo

ke

.

• 

Lo

ca

tio

ns 

at

 high a

lti

tud

e (m

or

than

 1

000

m hig

h)

.

• 

Lo

ca

tio

ns

 w

ith

 a

m

m

onic

 a

tm

osp

he

res

. (e

.g

. o

rg

anic

 fe

rtiliz

er

)

• 

Lo

ca

tio

ns

 w

ith

 c

alcium chl

or

id

e (e

.g

. s

no

w

 m

el

ting

 a

ge

nt)

.

• 

Lo

ca

tio

ns

 w

he

re h

eat

 ra

di

at

io

fro

m

 o

ther h

eat

 s

ou

rce

 c

an 

affe

ct

 th

e un

it.

• 

Lo

ca

tions

 w

ith

ou

t g

oo

ai

r circu

la

tio

n.

• 

Lo

ca

tio

ns

 w

ith

 a

ny

 ob

st

acl

es 

w

hich 

ca

n pr

ev

en

t in

let

 a

nd

 o

ut

let

 a

ir 

of

 th

e un

it.

• 

Lo

ca

tio

ns

 w

he

re s

ho

rt 

circuit 

of

 a

ir 

ca

occ

ur

 (in

 c

as

of

 mu

ltip

le

 uni

ts

 

in

st

al

la

tio

n)

.

• 

Lo

ca

tio

ns

 w

he

re 

st

ro

ng air b

low

ag

ains

t t

he 

ai

r o

ut

let

 of

 o

ut

door

 un

it.

• 

Lo

ca

tions

 w

he

re

 s

om

et

hing 

lo

ca

te

ab

ov

the un

it 

co

uld

 fal

l.

 

It 

ca

ca

us

re

m

ar

kab

le

 d

ec

re

ase in

 p

er

fo

rm

an

ce

, c

or

ro

si

on

 a

nd

 d

am

ag

of 

co

mpo

ne

nts

, ma

lfu

nc

tio

an

fir

e.

• 

Installation must be carried out by the qualified installe

r.

 

If 

you i

ns

tal

l t

he

 s

ys

te

by

 y

ou

rse

lf,

 it

 m

ay

 c

au

se

 s

er

io

us

 tr

ou

bl

e su

ch

 a

w

at

er

 le

ak

s,

 

el

ec

tri

sh

oc

ks

, fi

re

 a

nd p

er

so

na

l in

ju

ry

, a

res

ul

t o

f a

 s

ys

tem

 m

al

fu

nc

tio

n.

 D

no

ca

rry

 o

ut

 th

e ins

tall

at

io

and 

m

ai

nt

ena

nc

e w

or

ex

ce

pt

 b

the qualifi

ed in

st

al

le

r.

• 

Install the system in full accordance with the installation manual.

 

In

co

rre

ct ins

ta

lla

tio

m

ay

 c

au

se

 b

ur

st

s,

 p

er

so

na

l in

ju

ry

, w

at

er

 le

ak

s,

 e

le

ctr

ic

 

sh

oc

ks

 a

nd

 fi

re

.

• 

Be sure to use only for household and residence.

 

If 

thi

appl

ia

nc

e is ins

ta

lle

d in 

in

fe

rio

r e

nv

iro

nm

en

t s

uc

as

 m

ac

hi

ne

 s

ho

an

et

c.

it 

ca

ca

use 

m

al

fu

nc

tio

n.

• 

When installing in small rooms

, take prevention measures not to 

exceed the density limit of refrigerant in the event of leakage

, referred 

by the formula (accordance with ISO5149)

 

If the density of refrigerant exceeds the limit

, please consult the dealer and install the 

ventilation system

, otherwise lack of oxygen can occu

r, which can cause serious accident.

• 

Use the original accessories and the specified components for  installation.

 

If parts other than those prescribed by us are used

, It may cause water leaks

electric shocks

, fire and personal inju

ry

.

• 

Install the unit in a location with good support.

 

Unsuitable installation locations can cause the unit to fall and cause material 

damage and personal inju

ry

.

• 

Ensure the unit is stable when installed

, so that it can withstand 

earthquakes and strong winds.

 

Unsuitable installation locations can cause the unit to fall and cause material 

damage and personal inju

ry

.

• 

Ve

ntila

te

 th

w

or

ki

ng

 a

re

w

ell in 

th

ev

ent

 o

f r

ef

rig

er

an

t l

ea

ka

ge 

du

rin

in

stalla

tio

n.

 

If the refrigerant comes into contact with naked flames

, poisonous gas is produced.

• 

Use the prescribed pipes

, fl

are nuts and tools for R32.

 

Using existing parts (for R22 or R407C) can cause the unit failure and serious 

accidents due to burst of the refrigerant circuit.

• 

Tighten the 

flare nut by to

rque wrench with specified method.

 

If the flare nut were tightened with excess torque

, this may cause burst and 

refrigerant leakage after a long period.

• 

Do not open the se

rvice 

valves for liquid line and gas line until completed 

refrigerant piping work

, air tightness test and e

vacuation.

 

If the compressor is operated in state of opening se

rvice valves before completed 

connection of refrigerant piping work

, you may incur frost bite or inju

ry from an 

abrupt refrigerant outflow and air can be sucked into refrigeran

t circuit

, which can 

cause burst or personal inju

ry due to anomalously high pressure in the refrigerant.

• 

Th

el

ec

tr

ic

al

 in

stalla

tio

m

us

t b

ca

rr

ie

ou

t b

th

qu

al

ifi

ed

 e

le

ct

ric

ia

in

 a

cc

or

da

nc

e wi

th

 “

th

no

rm 

fo

r e

le

ct

ric

al

 w

or

k”

 a

nd

 “

nat

io

na

l w

iri

ng

 

re

gu

lat

io

n”

, a

nd

 th

e sy

st

em 

m

ust

 b

co

nn

ec

te

to

 th

de

di

ca

te

ci

rcu

it.

 

Power source with insufficient capacity and incorrect function done by improper  work can cause electric shocks and fire.

• 

Be sure to shut off the power before starting electrical work.

 

Failure to shut off the power can cause electric shocks

, unit failure or incorrect 

function of equipment.

• 

Be sure to use the cables conformed to safety standard and cable  ampacity for power distribution work

 

Unconformable cables can cause electric leak

, anomalous heat production or fire

.  

• 

This appliance must be connected to main power source by means of a circuit breaker or switch (fuse:20A) with a contact separation of at least 3mm

• 

Arrange the wiring in the control box so that it cannot be pushed up  further into the box

. Install the se

rvice panel correctl

y.

 

Incorrect installation may result in overheating and fire.

• 

Use the prescribed cables for electrical connection

, tighten the cables 

securely in terminal block and relieve the cables correctly to prevent  overloading the terminal blocks.

 

Lo

os

co

nn

ec

tio

ns

 o

r c

ab

le

 m

ou

nt

ings

 c

an

 c

au

se

 a

no

m

al

ous 

he

at

 p

ro

du

ct

io

or

 fi

re

.

• 

Be sure to fix up the se

rvice panels.

 

Incorrect fixing can cause electric shocks or fire due to intrusion of dust or wate

r.

• 

Be sure to switch off the power source in the event of installation

inspection or se

rvicing.

 

If the power source is not shut off

, there is a risk of electric shocks

, unit failure or 

personal inju

ry due to the unexpected start of fan.

• 

Stop the compressor before rem

oving the pipe after shutting the 

se

rvice 

valve on pump down work.

 

If the pipe is removed when the compressor is in operation with the se

rvice valve 

open

, air would be mixed in the refrigeration circuit and it could cause explosion 

and injuries due to abnormal high pressure in the cooling cycle.

• 

Only use prescribed option parts

. The installation must be carried out 

by the qualified installe

r.

 

If you install the system by yourself

, it can cause serious trouble such as water 

leaks

, electric shocks

, fire.

• 

Be sure to wear protective goggles and gl

oves while at work.

• 

Earth leakage breaker must be installed.

 

If the earth leakage breaker is not installed

, it can cause electric shocks.

• 

After completed installation

, check that no refrigerant leaks from the 

system.

 

If refrigerant leaks into the room and comes into contact with an oven or other hot 

surface

, poisonous gas is produced.

• 

Hang up the unit at the specified points with ropes which can su

pport the 

weight in lifting for portage

. And to avoid jolting out of alignment

, be sure 

to hang up the unit at 4-point support.

 

An improper manner of portage such as 3-point support can cause death or 

serious personal inju

ry due to falling of the unit.

• 

Consult the dealer or an 

expert regarding rem

ov

al of the unit.

 

Incorrect installation can cause water leaks

, electric shocks or fire.

• 

Do not perform brazing work in the airtight room.

 

It can cause lack of oxygen.

• 

This unit is designed specifically for R32.

 

Using any other refrigerant can cause u

nit failure and personal inju

ry

.

• 

Do not bundling

, winding or processing for the power cord

. O

r, do not 

deforming the power plug due to tread it.

 

This may cause fire or heating.

• 

Do not run the unit with rem

oved panels or protections.

 

Touching rotating equipments

, hot surfaces or high voltage parts can cause 

personal inju

ry due to entrapment

, burn or electric shocks.

• 

Do not perform a

ny change of protective device itself or its setup condition.

 

The forced operation by short-circuiting protective device of pressure switch and 

temperature control or the use of non specified component can cause fire or burst.

• 

Do not perform a

ny repairs or modifications by yourself

. Consult the dealer 

if the unit requires repai

r.

 

If you repair or modify the unit

, it can cause water leaks

, electric shocks or fire.

• 

Take care when car

rying the unit by hand.

 

If the unit weights more than 20kg

, it must be carried by two or more persons

. Do 

not car

ry by the plastic straps

, always use the car

ry handle when car

rying the unit 

by hand

. Use gloves to minimize the risk of cuts by the aluminum fins.

• 

Dispose of a

ny packing materials correctl

y.

 

Any remaining packing materials can cause personal inju

ry

. T

o avoid danger of 

suffocation

, be sure to keep the plastic wrapper away from children and to 

dispose after tear it up.

 

• 

Be sure to insulate the refrigerant pipes so as not to condense the  ambient air moisture on them.

 

Ins

uf

fic

ie

nt insu

la

tio

ca

ca

us

cond

ens

at

io

n,

 which

 c

an 

le

ad

 to

 mo

is

tu

re

 

da

m

ag

on the 

ce

ili

ng

, fl

oo

r, fu

rniture 

and a

ny

 o

th

er

 v

al

ua

bl

es

.

• 

Be s

ur

to

 p

er

fo

rm air t

ig

ht

ness test 

by 

press

ur

iz

in

w

ith

 n

itr

og

en

 g

as

 

after

 c

om

plet

ed

 refr

ig

eran

t p

ip

in

w

or

k.

 

If the density of refrigerant exceeds the limit in the event of refrigerant leakage in 

the small room

, lack of oxygen can occu

r, which can cause serious accidents.

• 

Do

 no

t i

nstall 

the

 o

ut

do

or

 u

nit 

in

 th

lo

cati

on

s list

ed

 be

lo

w

.

 L

oc

at

io

ns

 w

he

re discha

rged ho

t a

ir or o

pe

ra

ting 

so

und

 of

 th

ou

td

oo

r un

it 

ca

bot

he

r n

eigh

bo

rh

oo

d.

 L

oc

at

io

ns

 w

he

re

 ou

tle

t air

 of

 th

ou

td

oor un

it bl

ow

s dir

ect

ly 

to

 a

ani

m

al 

or

 

pl

an

ts

. T

he

 o

ut

le

t air

 c

an

 a

ffe

ct

 a

dve

rsel

to

 th

pl

an

t et

c.

 L

oc

at

io

ns

 w

he

re 

vib

rat

ion 

can b

amplified 

and

 tr

ansm

itt

ed due

 to

 insu

ffi

ci

en

st

re

ng

th

 o

f s

tru

ct

ur

e.

 L

oc

at

io

ns wh

er

vib

ra

tio

and op

er

at

io

n sound g

en

er

at

ed b

th

e ou

tdo

or

 un

it 

can 

af

fe

ct

 s

er

io

us

ly (

on

 th

e w

all

 o

r a

t t

he

 pl

ace 

ne

ar

 bed

 ro

om

).

 L

oc

at

io

ns

 w

he

re

 an

 e

quipme

nt

 af

fe

ct

ed by high h

ar

m

onics is p

la

ce

d (TV s

et

 o

ra

dio

 re

ce

ive

r is p

la

ce

w

ithin

 5

m

).

 L

oc

at

io

ns

 w

he

re

 d

ra

in

ag

ca

nn

ot

 run 

of

f s

af

el

y.

 

It ca

af

fe

ct

 sur

ro

undin

en

vir

on

m

en

t a

nd

 c

aus

cl

ai

m

.

• 

Do

 no

t i

nstall 

the

 u

nit 

ne

ar

 th

e l

oc

ati

on

 w

he

re

 le

ak

ag

of

 co

mb

ust

ib

le

 

gase

ca

oc

cu

r.

 

If 

le

aked

 g

ases accumu

la

te a

ro

und 

the un

it,

 it

 c

an

 c

aus

fir

e.

• 

Do

 n

ot install th

uni

t w

her

co

rr

osiv

gas (

su

ch as s

ulf

ur

ous 

ac

id gas etc

.) 

or

 c

om

bu

stibl

gas (

su

ch as t

hi

nn

er a

nd

 p

et

ro

le

um

 g

ases) 

ca

n accum

ula

te

 

or

 c

olle

ct

, o

r w

here

 v

olatile 

co

m

bus

tib

le 

su

bst

an

ces are h

an

dl

ed

.

 

Co

rr

os

ive

 g

as

 c

an

 c

au

se

 c

or

ro

si

on

 o

f h

ea

t e

xc

ha

ng

er

, b

re

ak

ag

of

 pl

as

tic

 p

ar

ts

 

an

et

c.

 A

nd

 c

ombustible 

ga

can ca

us

fir

e.

• 

Do

 no

t i

nstall

 no

r u

se

 the

 syst

em 

clo

se

 to 

the

 equ

ipm

en

t t

hat

 g

en

erat

es

 

el

ec

tr

oma

gn

et

ic

 fi

el

ds

 o

r h

ig

h f

req

uen

cy

 h

arm

on

ic

s.

 

Equipme

nt

 such

 a

s i

nv

er

te

rs

, s

tand

by

 ge

ne

ra

to

rs

, medical high

 freque

ncy

 

equipme

nt

s and

 te

le

communic

at

io

equip

m

en

ts can 

aff

ec

t t

he

 s

ys

te

m

, a

nd

 c

au

se

 

m

al

fun

ct

io

ns 

and b

re

akdo

wn

s.

 The sy

ste

m can 

also 

af

fe

ct

 m

edi

cal equipment a

nd

 

te

le

communic

at

io

n equipme

nt

, and

 o

bs

tru

ct

 it

fun

ct

io

or caus

e jammi

ng

.

• 

Se

cur

e a 

sp

ac

e f

or

 in

stallat

ion

, i

ns

pec

tion

 a

nd

 m

ai

nt

en

an

ce

 s

pe

cifi

ed

 in

 

the

 m

anu

al

.

 

In

su

ffi

ci

en

t sp

ac

can 

re

su

lt in accide

nt

 suc

as 

pe

rsonal in

ju

ry

 du

to

 fallin

fro

m

 

th

e i

ns

ta

llat

io

n pl

ac

e.

 Do

 n

ot install 

th

ou

td

oo

r u

nit in a

 lo

ca

tio

w

he

re in

se

cts 

an

sm

al

animals 

ca

in

ha

bi

t.

 

Ins

ec

ts and small animal

can 

en

te

r t

he

 el

ec

tric

 p

ar

ts

 a

nd

 c

ause

 d

amag

or

 fi

re

In

st

ru

ct

 th

e us

er

 to

 k

ee

th

su

rrounding

cl

ea

n.

 D

no

t u

se

 th

ba

se

 fr

am

fo

r o

ut

do

or

 u

ni

t w

hi

ch

 is

 c

or

ro

de

or

 d

am

ag

ed

 

du

to

 lo

ng

 p

er

io

ds

 o

f o

pe

ra

tio

n.

 

Using a

old and da

m

age 

ba

se

 fr

ame ca

caus

the un

it 

falling d

ow

an

cau

se

 

pe

rs

onal in

ju

ry

 Do

 n

ot

 u

se

 a

ny

 m

aterial

ot

he

r t

ha

n a fus

w

ith

 th

co

rr

ec

t r

at

in

in

 th

lo

cat

io

w

he

re

 fu

ses a

re

 to

 b

e u

se

d.

 

Con

ne

ct

ing

 th

ci

rc

ui

t w

ith 

co

pp

er

 w

ire

 o

r o

th

er

 m

et

al 

th

re

ad

 c

an

 c

ause un

it 

fai

lu

re an

fir

e.

 Do

 n

ot 

to

uc

an

bu

tt

ons

 w

ith

 w

et h

an

ds

.

 

It 

ca

cau

se 

el

ec

tric s

ho

cks

.

 D

no

t t

ou

ch

 a

ny

 re

fr

ig

er

an

t p

ip

es

 w

ith

 y

ou

r h

an

ds 

w

he

th

e system is 

in

 

op

era

tio

n.

 

Du

ring op

er

at

ion

 the 

re

frige

rant pipes b

ec

ome

 e

xtr

emely h

ot 

or

 e

xt

reme

ly 

co

ld

 

de

pe

ndin

th

op

er

at

in

cond

iti

on

, a

nd

 it

 c

an

 c

ause 

bu

rn in

ju

ry

 o

r fr

os

t in

ju

ry

.

 Do 

no

t t

ou

ch

 th

e su

ct

io

or al

um

in

um fi

on

 th

ou

td

oo

r u

ni

t.

 

This 

m

ay

 c

ause in

ju

ry

.

 Do

 n

ot

 p

ut

 a

nyth

in

on

 th

ou

tdo

or

 u

nit

 a

nd

 o

pe

ra

tin

un

it.

 

This 

m

ay

 c

ause

 d

amage

 the o

bj

ec

ts 

or

 in

ju

ry

 du

to 

falling to the o

bj

ect

.

 Do

 n

ot

 u

se

 th

unit

 fo

r s

pe

cia

l p

ur

po

se

suc

h as 

st

or

in

fo

od

s,

 c

oo

lin

pr

ec

is

io

in

st

ru

m

en

ts 

an

pr

es

er

vat

io

of

 a

ni

m

al

s,

 p

la

nt

or

 a

rt

.

 Do

 n

ot

 c

le

an

 u

th

un

it 

w

ith

 w

at

er

.

 Do

 n

ot s

te

ont

o the

 o

ut

do

or

 u

ni

t.

 W

he

th

ou

tdo

or

 u

nit is 

in

stal

le

on a

 roo

f o

r a

 h

ig

pla

ce

, p

ro

vi

de

 

pe

rma

ne

nt l

ad

de

rs 

an

ha

nd

rails 

al

on

th

ac

cess

 rou

te and 

fe

nc

es

 

ha

nd

rails 

ar

ou

nd

 th

ou

td

oo

r un

it.

Inverter

 driven

 split

 P

AC

90,

 100VNP

Designed

 for

 R32

 refrigerant

a

b

c

d

e

f

g

h

Gauge manifold

Charge hose

Electronic scale for refrigerant charging

Torque wrench

Flare tool

Protrusion control copper pipe gauge

Vacuum pump adapter

Gas leak detector

Dedicated R32 tools

● 

Do not use any refrigerant other than R32.

 R32 will rise to pressure about 1.6 times higher than that of a conventional refrigerant (R22 or 

R407C). A cylinder containing R32 has a lightblue indication mark on the top.

● 

A unit designed for R32 has adopted a different size indoor unit operation valve charge port and a different size check joint p

rovided in the 

unit to prevent the charging of a wrong refrigerant by mistake. The processed dimension of the flared part of a refrigerant pipe and a flare nut's parallel side measurement have also been alter

ed to raise 

strength against pressure. Accordingly, you are required to arrange dedicated R32 tools listed in the table on the next page before installing or servicin

g this unit.

● 

All indoor units must be models designed exclusively for R32. Check connectable indoor unit models in a catalog, etc. (A wrong 

in door unit, 

if connected into the system, will impair proper system operation)

Accessories for outdoor unit

• Model name and power source • Refrigerant piping length • Piping, wiring and miscellaneous small parts • Indoor unit installation manual

Grommet (Heat pump type only)

Drain elbow (Heat pump type only)

Reducer set ø9.52    ø6.35

2

1

1

1

2

3

Check before installation work

Q’ty

INS

TALL

ATION MAN

UAL FOR OUTDOOR UNIT

2. REFRIGERANT PIPING WORK

1)

Restrictions

on

unit

installation

and

use

 

Check

the

following

points

in

light

of

the

indoor

unit

specifications

and

the

installation

site.

 

Obse

rve

the

following

restrictions

on

unit

installation

and

use.

  

Improper

installation

can

result

in

a

compressor

failure

or

pe

rformance

degradation

.

2)

Determination

of

pipe

size

 

Determine

refrigerant

pipe

size

pursuant

to

the

following

guidelines

based

on

the

  

indoor

unit

specifications.

Gas pipe

Liquid pipe

ø15.88

ø6.35

Flare

Flare

ø15.88

ø6.35

ø15.88

ø9.52

1. HAULAGE AND INSTALLATION

(T

ake particular care in car

rying in or moving the unit, and always pe

rform such an operation with two or more persons.)

Intake

The

height

of

a

wall

is

1200mm

or

less.

(

se

rvice

  space

)

Intake

Outlet

Fasten

with

bolts

(M10-12)

Use

a

thicker

block

to

 

anchor

deepe

r.

Use

a

long

block

to

extend

the

width.

CAUTION

When

a

unit

is

hoisted

with

slings

for

haulage,

take

into

consideration

the

offset

of

its

gravity

center

position.

  

If

not

properly

balanced,

the

unit

can

be

thrown

off-balance

and

fall.

1)

Delivery

Deliver

the

unit

as

close

as

possible

to

the

installation

site

before

removing

it

from

the

packaging.

When

you

have

to

unpack

the

unit

for

a

compelling

reason

before

you

haul

it

to

the

installation

point,

hoist

the

unit

with

nylon

slings

or

ropes

and

protection

pads

so

that

you

may

not

damage

the

unit.

2)

Portage

The

right

hand

side

of

the

unit

as

viewed

from

the

front

(diffuser

side)

is

heavie

r.

A

person

car

rying

the

right

hand

side

must

take

heed

of

this

fact.

A

person

car

rying

the

left

hand

side

must

hold

with

his

right

hand

the

handle

provided

on

the

front

panel

of

the

unit

and

with

his

left

hand

the

corner

column

section

.

5)

Installation

space

W

alls surrounding the unit in the four sides are not acceptable.

There must be a 1-meter or larger space in the above.

When more than one unit are installed side by side, provide a 250mm or wider interval between them as a service  space.  In order to facilitate servicing of controls, please provide a sufficient space between units so that their top  plates can be removed easily.

Where a danger of short-ci

rcuiting exists, install guide louvers.

When more than one unit are installed, provide sufficient intake space consciously so that short-ci

rcuiting may not occur

.

Where

piling

snow

can

bu

ry

the

outdoor

unit,

provide

proper

snow

guards.

L

3

L

2

L

4

L

1

Example installation

Size

In installing the unit, fix the unit

’s legs with bolts specified on the above.

The protrusion of an anchor bolt on the front side must be kept within 15 mm.

Securely install the unit so that it does not fall over during earthquakes or strong winds, etc.

Refer to the above illustrations for information regarding concrete foundations.

Install the unit in a level area. (With a gradient of 5 mm or less.) Im

pr

op

er

 in

st

al

la

tio

ca

re

su

lt 

in

a

co

m

pr

es

so

rf

ai

lu

re

, b

ro

ke

n

pi

pi

ng

w

ith

in

th

e

un

it

an

ab

no

rm

al

 n

oi

se

 g

en

er

at

io

n.

6)

Installation

L

H

Outdoor unit

Indoor unit

CAUTION

Th

e

us

e

re

st

ric

tio

ns

ap

pe

ar

in

g

in

th

e

ta

bl

e

ab

ov

e

ar

e

ap

pl

ica

bl

e

to

th

e

st

an

da

rd

pi

pe

siz

e

co

m

bi

na

tio

ns

sh

ow

n

in

th

e

ta

bl

e

be

lo

w.

W

he

re

an

ex

ist

in

g

pi

pe

 s

ys

te

m

 is

 u

til

ize

d,

di

ffe

re

nt

 o

ne

-w

ay

pi

pe

 le

ng

th

 re

st

ric

tio

ns

sh

ou

ld

 a

pp

ly 

de

pe

nd

in

on

 it

pi

pe

siz

e.

Fo

r m

or

e

in

fo

rm

at

io

n,

 p

lea

se

se

e

“5

. U

TI

LI

ZA

TI

ON

OF

 E

XI

ST

IN

G

PI

PI

NG

.”

Outdoor unit connected

Refrigerant piping (branch pipe

L)

Indoor unit connected

About brazing

When pipe is brazing.

(2)

If

the

unit

can

be

affected

by

strong

wind,

following

measures

are

required.

Strong

wind

can

cause

damage

of

fan

(fan

motor),

or

can

cause

pe

rformance

degradation,

or

can

trigger

anomalous

stop

of

the

unit

due

to

rising

of

high

pressure.

3)

 Refrigerant

 pipe

 wall

 thickness

 and

 material

Select

 refrigerant

 pipes

 of

 the

 table

 shown

 on

 the

 right

 wall

 thickness

 and

 material

 as

 specified

 for

 each

 pipe

 size.

Pipe diameter [mm]

Minimum pipe wall thickness [mm]

Pipe material*

ø6.35

0.8

O-type pipe

ø15.88

1.0

O-type pipe

*Phosphorus deoxidized seamless copper pipe  ICS 23.040.15, ICS 77.150.30

NOTE

Select

 pipes

 having

 a

 wall

 thickness

 larger

 than

 the

 specified

 minimum

 pipe

 thickness.

He

avy

Pad

L1

L2

L3

L4

Open

300

100

250

Open

250

150

250

500

Open

100

250

(mm)

I

II

III

60

580

340

19

380

418

19

880

87.9

15

150

150

Intake

Outlet

① 

Anchor bol tfixed position

② 

Notabilia for installation

Plug the end of the pipe with tape, or other  material, and fill the pipe with nitrogen gas.

Only use nitrogen gas (N

2

)

Taping

N

2

Nitrogen

Brazing

Station valve

Prima

ry side

Seconda

ry side

0.5MPa

Hand

Relief valve

Nitrogen

gas

Brazing

must

be

performed

under

a

nitrogen

gas

flo

w

.

Without

nitrogen

gas,

a

large

quantity

of

foreign

matters

(oxidized

film)

are

created,

causing

a

critical

failure

from

capilla

ry

tube

or

expansion

valve

clogging.

If the refrigerant is existing in the pipe at brazing, poisonous gas is produced.

Wind

 direction

Wind

 direction

Over

 500

 mm

2.Install the outlet air blow side of 

the unit in a position perpendicular  to the direction of wind.

3.

The

 unit

 should

 be

 installed

 on 

the

 stable

 and

 level

 foundation.

If 

the

 foundation

 is

 not

 level, 

the

 down

 the

 unit

 with

 wires.

1.

Install the outlet air blow side of the  unit to face a wall of building, or  provide a fence or a windbreak screen.

7)  To run the unit for a cooling operation, 

when the outdoor temperature is –5°C or lower. 

 

When the outdoor air temperature is –5°C or lower, provide a snow hood to the outdoor unit on site. So that strong wind will not blow against the outdoor heat exchanger directly.

4)

Caution

about

selection

of

installation

location

(1)

If

the

unit

is

installed

in

the

area

where

the

snow

will

accumulate,

following

measures

are

required.

The

bottom

plate

of

unit

and

intake,

outlet

may

be

blocked

by

sno

w

.

1

2

Provide

a

snow

hood

to

the

outdoor

unit

on

site.

3

Install

the

unit

under

eaves

or

provide

the

roof

on

site.

Since

drain

water

generated

by

defrost

control

may

freeze,

following

measures

are

required.

Don’t execute drain piping work 

by using a drain elbow and drain grommets (accessories).

 [Refer to DRAIN PIPING WORK.]

Install the unit on the base so  that the bottom is higher than  snow cover surface, and  draining water is secured.

● 

Attached heater on a base plate on site, if there is possibility to freeze drain water. In case that the product has a corrective drainage system, the drainage paths should have suitable  threatment against freezing but be sure not to melt the material of drainage paths with heat.

30m

or less

20m

or less

20m

or less

L

H

H

Restrictions

Dimensional restrictions

Marks appearing in the drawing on the right

Main pipe length

Elevation difference between 

Indoor unit

indoor and outdoor units

When the outdoor unit is positioned higher

FDT, FDE, FDU, FDUM, SRK

When the outdoor unit is positioned lower

3)

  S

el

ec

tio

of

 in

stalla

tio

lo

ca

tio

fo

th

ou

td

oo

un

it

Be

 s

ur

to

 sele

ct

 a

 s

ui

ta

ble

 in

st

alla

tio

pla

ce

 in

 c

on

si

de

ra

tio

of

 fo

llo

w

in

co

nd

iti

on

s.

 

pla

ce

 w

he

re

 it

 is

 h

or

iz

on

ta

l, 

st

ab

le

 a

nd

 c

an

 e

nd

ur

th

un

it 

w

ei

gh

t a

nd

 wi

ll 

no

t a

llo

w

 v

ib

ra

tio

tr

an

sm

itt

an

ce

 

of

 th

un

it.

 

pla

ce

 w

he

re

 it

 c

an

 b

fr

ee

 fr

om

 p

os

si

bi

lit

of

 b

ot

he

rin

ne

ig

hb

or

du

to

 n

oi

se

 o

ex

ha

us

t a

ir 

fr

om

 th

un

it.

 

pla

ce

 w

he

re

 th

un

it 

is

 n

ot

 e

xp

os

ed

 to

 o

il 

sp

la

sh

es

.

 

pla

ce

 w

he

re

 it

 c

an

 b

fr

ee

 fr

om

 d

an

ge

of

 fl

am

m

ab

le

 g

as

 lea

ka

ge

.

 

pla

ce

 w

he

re

 d

ra

in

 w

at

er

 c

an

 b

di

sp

os

ed

 w

ith

ou

t a

ny

 tr

ou

bl

e.

 

pla

ce

 w

he

re

 th

un

it 

wil

l n

ot

 b

af

fe

ct

ed

 b

he

at

 r

ad

ia

tio

fr

om

 o

th

er

 h

ea

t s

ou

rc

e.

 

pla

ce

 w

he

re

 s

no

w

 wil

l n

ot

 a

cc

um

ul

at

e.

 

pla

ce

 w

he

re

 th

un

it 

ca

be

 k

ep

t aw

ay

 5

m

 o

m

or

fr

om

 T

se

t a

nd

/o

ra

di

recei

ve

in

 o

rd

er

 to

 a

vo

id

 a

ny

 

ra

di

or

 T

in

te

rf

er

en

ce

.

 

pla

ce

 w

he

re

 g

oo

ai

ci

rc

ula

tio

ca

be

 s

ec

ur

ed

, a

nd

 e

no

ug

 h

se

rvi

ce

 s

pa

ce

 c

an

 b

se

cu

re

fo

m

ai

nt

en

an

ce

 

an

se

rvic

of

 th

un

it 

sa

fe

ly

.

 

pla

ce

 w

he

re

 th

un

it 

wi

ll 

no

t b

af

fect

ed

 b

el

ec

tr

om

ag

net

ic

 wav

es

 a

nd

/o

r h

ig

h-

ha

rm

on

ic

 wav

es

 g

en

er

at

ed

 b

ot

he

eq

ui

pm

en

t.

 

pla

ce

 w

he

re

 c

hemic

al

 s

ub

st

an

ce

lik

su

lfu

ric

 g

as

, c

hl

or

ic

 g

as

, a

ci

an

alka

li 

(in

cl

ud

in

ga

m

m

on

ia

), 

w

hi

ch

 c

an

 

ha

rm

 th

un

it,

 wil

l n

ot

 b

ge

ne

ra

te

an

no

t r

ema

in

.

 

If 

op

er

at

io

is

 c

on

du

ct

ed

 w

he

th

ou

td

oo

ai

te

m

pera

tu

re

 is

 -

lo

w

er

, t

he

 o

ut

do

or

 u

ni

t s

ho

ul

be

 in

st

al

le

at

 a

 p

lace

 w

he

re i

t i

no

t i

nfl

ue

nc

ed

 b

na

tu

ral wi

nd

.

 

pla

ce

 w

he

re

 s

tr

on

w

in

d wi

ll 

no

t b

lo

w

 a

ga

in

st

 th

ou

tle

t a

ir 

bl

ow

 o

f t

he

 u

ni

t.

D

no

in

st

al

l t

he

 u

ni

in

 p

lac

es

 w

hi

ch

 e

xp

os

ed

 to

 s

ea

 b

ree

ze

 (

e.

g.

 c

oa

st

al

 a

re

a)

 o

cal

ci

um

 c

hl

or

id

(e

.g

. s

no

w

 

mel

tin

ag

en

t)

, e

xp

os

ed

 to

 a

m

m

on

ia 

su

bs

ta

nc

(e

.g

. o

rg

an

ic

 fe

rt

ili

ze

r)

.

PSC012D137

Notabilia as a unit designed for R32

• 

Read the “SAFETY PRECAUTIONS” ca

refully first of all and strictly follow it during the installation work in o

rder 

to p

rotect yourself.

• 

The p

recautionary items mentioned below a

re distinguished into two levels,                          and                       .

                              : 

W

rong installation would cause serious consequences such as injuries or death.

                              : 

W

rong installation might cause serious consequences depending on ci

rcumstances.

Both mentions the important items to p

rotect your health and safety so strictly follow them by any means.

• 

Be su

re to confirm no anomaly on the equipment by commissioning after completed installation and explain the 

operating methods as well as the maintenance methods of this eq

uipment to the user accor

ding to the owner

’s 

manual.

• 

Keep the installation manual together with owner

’s manual at a place whe

re any user can 

read at any time. 

Mo

reover if necessar

y, ask to hand them to a new use

r.

• 

For installing qualified personnel, take p

recautions in 

respect to themselves by using suitable p

rotective 

clothing, g

roves, etc., and then perform the installation works.

• 

Please pay attention not to fall down the tools, etc. when installing the unit at the high position.

• 

If unusual noise can be hea

rd during operation, consult the deale

r.

• 

The meanings of “Marks” used he

re a

re shown as follows:

• 

This installation manual deals with outdoor units and general installation specifications onl

y.  For indoor units, 

refer to the 

respective installation manuals supplied with the units.

• 

When install the unit, be su

re to check whether the selection of installation place, power supply specifications, usage limitation (piping length, height di

ffe

rences between indoor and outdoor units, power 

supply voltage and etc.) and installation spaces. 

SAFETY PRECAUTION

S

Never do it under any ci

rcumstances.

Always do it acco

rding to the instruction.

CAUTION

W

ARNING

CAUTION

W

ARNING

W

ARNIN

G

CAUTION

• 

Car

ry out the electrical work for ground lead with care.

 

Do not connect the ground lead to the gas line

, water line

, lightning conductor or telephone line

’s ground lead

. Incorrect grounding can cause unit faults such as electric shocks due to short-circuiting.

• 

Ensure that no air enters in the refrigerant circuit when the unit is  installed and rem

oved.

 

If 

ai

r e

nt

ers i

th

re

fri

ge

ra

nt 

ci

rc

ui

t, 

th

pr

es

su

re

 in 

th

re

fri

ge

ra

nt

 c

irc

ui

be

co

m

es

 to

o hi

gh

, w

hi

ch

 c

an

 c

au

se

 b

ur

st

 a

nd

 p

er

so

na

l in

ju

ry

.

• 

Do

 n

ot 

pr

oc

es

si

ng

, s

pl

ic

th

po

w

er

 c

or

d,

 o

r s

ha

re

 a

 s

oc

ke

t w

ith

 o

th

er

 p

ow

er

 p

lu

gs

.

 

This may cause fire or electric shock due to defecting contact

, defecting insulation 

and ove

r-current etc.

• 

Use the circuit breaker for all pole correct  capacit

y.

 Circuit breaker 

should be the one that disconnect all poles under 

over current.

 

Using the incorrect circuit breake

r, it can cause the unit malfunction and fire.

• 

Install isolator or disconnect switch on the power supply wiring in  accordance with the local codes and regulations.

 

The isolator should be locked in OFF state in accordance with EN60204-1.

• 

Af

te

r m

ai

nt

en

an

ce

, all 

w

iri

ng

, wi

rin

tie

an

th

lik

e,

 s

ho

ul

be

 re

tu

rn

ed

 

to

 th

ei

r o

rig

in

al sta

te

 a

nd

 wi

rin

ro

ut

e,

 a

nd

 th

ne

ce

ss

ar

cl

ea

ra

nc

e f

ro

m

 

all

 m

eta

l p

ar

ts

 s

ho

ul

be

 s

ec

ur

ed

.

• 

Se

cu

re

 a 

sp

ac

e f

or

 in

stallat

io

n,

 in

sp

ec

tio

an

m

ain

te

na

nc

sp

ec

ifi

ed

 in

 

th

m

an

ua

l.

 

Insufficient space can result in accident such as personal inju

ry due to falling 

from the installation place.

• 

Earth

 le

ak

ag

bre

ak

er

 m

ust

 b

in

stal

le

d

If 

th

ea

rth

 le

ak

ag

br

eak

er is 

no

t in

st

all

ed

, i

t c

an

 c

au

se

 fi

re

 o

r e

le

ctr

ic 

sh

oc

ks

.

• 

Do

 no

t i

nstall 

th

un

it i

th

lo

cati

on

s lis

ted

 be

lo

w

.

• 

Lo

ca

tio

ns

 w

he

re 

ca

rb

on

 fi

be

r, 

m

et

al 

pow

de

r o

r a

ny

 p

ow

de

r is 

flo

at

in

g.

• 

Lo

ca

tio

ns

 w

he

re

 a

ny

 subs

ta

nc

es

 th

at

 c

an 

af

fe

ct

 th

e un

it such

 a

s sulphi

de

 g

as

ch

lo

rid

e g

as

, a

cid an

al

ka

lin

ca

oc

cu

r. 

• 

Veh

ic

le

and shi

ps

.

• 

Lo

ca

tio

ns

 w

he

re 

co

sm

et

ic o

r spe

ci

al sp

ra

ys

 a

re

 ofte

n u

sed

.

• 

Lo

ca

tions

 w

ith di

re

ct

 ex

posu

re

 o

f o

il mi

st

 a

nd 

st

ea

m su

ch

 a

s k

itch

en a

nd

 

m

ach

in

pl

an

t.

• 

Lo

ca

tions

 w

he

re

 a

ny

 m

achines

 w

hich ge

ne

ra

te

 high

 fr

eq

ue

ncy

 h

ar

m

on

ic

s a

re

 

us

ed

.

• 

Lo

ca

tio

ns

 w

ith 

sa

lty

 a

tm

osph

er

es such 

as 

coa

st

lin

es

• 

Lo

ca

tio

ns

 w

ith 

he

av

y sn

ow

 (I

f in

st

all

ed

, b

e s

ure

 to

 p

ro

vide 

ba

se

 fr

am

and s

now

 

ho

od m

en

tio

ne

d i

th

m

an

ua

l).

• 

Lo

ca

tio

ns

 w

he

re

 th

e uni

t is

 e

xp

osed 

to

 chim

ney

 s

m

ok

e.

• 

Lo

ca

tions 

at

 high

 a

lti

tud

e (m

or

th

an 

100

0m hig

h)

.

• 

Lo

ca

tio

ns

 w

ith

 a

m

m

oni

at

m

osp

he

re

s.

 (e

.g

. o

rg

anic

 fe

rtiliz

er

)

• 

Lo

ca

tio

ns

 w

ith

 c

alcium chl

or

id

e (e

.g

. s

no

w

 m

el

ting

 a

ge

nt)

.

• 

Lo

ca

tio

ns

 w

he

re h

eat

 ra

di

at

io

fro

m

 o

ther h

eat

 s

ou

rce

 c

an 

affe

ct

 th

e un

it.

• 

Lo

ca

tions

 w

ith

ou

t g

oo

ai

r circu

la

tio

n.

• 

Lo

ca

tio

ns

 w

ith

 a

ny

 ob

st

acl

es 

w

hich 

ca

n pr

ev

en

t in

let

 a

nd

 o

ut

let

 a

ir 

of

 th

e un

it.

• 

Lo

ca

tio

ns

 w

he

re s

ho

rt 

circuit 

of

 a

ir 

ca

occ

ur

 (in

 c

as

of

 mu

ltip

le

 un

its

 

instal

la

tio

n)

.

• 

Lo

ca

tio

ns

 w

he

re 

st

ro

ng air b

low

ag

ains

t t

he 

ai

r o

ut

let

 of

 o

ut

door

 un

it.

• 

Lo

ca

tions

 w

he

re

 s

om

et

hing 

lo

ca

te

ab

ov

the un

it 

co

uld

 fal

l.

 

It 

ca

ca

us

re

m

ar

ka

bl

de

cr

ea

se

 in p

er

fo

rm

an

ce

, c

or

ro

si

on

 a

nd

 d

am

ag

of 

co

m

po

nen

ts

, m

al

fu

nct

io

an

fir

e.

• 

Installation must be carried out by the qualified installe

r.

 

If 

you in

st

al

l t

he

 s

ys

tem 

by

 y

ou

rs

el

f, 

it 

m

ay

 c

au

se

 s

er

io

us

 tr

ou

bl

e su

ch

 a

w

at

er

 le

ak

s,

 

el

ec

tri

c s

ho

ck

s,

 fi

re

 a

nd 

pe

rsonal in

ju

ry

, a

res

ul

t o

f a

 s

ys

tem 

m

al

fu

nc

tio

n.

 D

no

ca

rry

 o

ut

 th

e ins

tall

at

io

and 

m

ai

nt

ena

nc

e w

or

ex

cep

t b

th

e qu

ali

fie

d in

sta

lle

r.

• 

Install the system in full accordance with the installation manual.

 

In

co

rre

ct in

st

al

la

tio

m

ay

 c

aus

bu

rs

ts

, p

er

so

na

l in

ju

ry

, w

at

er

 le

ak

s,

 e

le

ct

ric

 

sh

oc

ks and fi

re

.

• 

Be sure to use only for household and residence.

 

If 

this app

lia

nc

e is ins

ta

lle

d in i

nf

er

io

r e

nv

iro

nm

en

t s

uc

as

 m

ac

hi

ne

 s

ho

an

et

c.

it 

ca

ca

us

m

al

fu

nc

tio

n.

• 

When installing in small rooms

, take prevention measures not to 

exceed the density limit of refrigerant in the event of leakage

, referred 

by the formula (accordance with ISO5149)

 

If the density of refrigerant exceeds the limit

, please consult the dealer and install the 

ventilation system

, otherwise lack of oxygen can occu

r, which can cause serious accident.

• 

Use the original accessories and the specified components for  installation.

 

If parts other than those prescribed by us are used

, It may cause water leaks

electric shocks

, fire and personal inju

ry

.

• 

Install the unit in a location with good support.

 

Unsuitable installation locations can cause the unit to fall and cause material 

damage and personal inju

ry

.

• 

Ensure the unit is stable when installed

, so that it can withstand 

earthquakes and strong winds.

 

Unsuitable installation locations can cause the unit to fall and cause material 

damage and personal inju

ry

.

• 

Ve

ntila

te

 th

w

or

ki

ng

 a

re

w

ell in

 th

ev

ent

 o

f r

ef

rig

er

an

t l

ea

ka

ge

 d

ur

in

in

stallati

on

.

 

If the refrigerant comes into contact with naked flames

, poisonous gas is produced.

• 

Use the prescribed pipes

, fl

are nuts and tools for R32.

 

Using existing parts (for R22 or R407C) can cause the unit failure and serious 

accidents due to burst of the refrigerant circuit.

• 

Tighten the 

flare nut by to

rque wrench with specified method.

 

If the flare nut were tightened with excess torque

, this may cause burst and 

refrigerant leakage after a long period.

• 

Do not open the se

rvice 

valves for liquid line and gas line until completed 

refrigerant piping work

, air tightness test and e

vacuation.

 

If the compressor is operated in state of opening se

rvice valves before completed 

connection of refrigerant piping work

, you may incur frost bite or inju

ry from an 

abrupt refrigerant outflow and air can be sucked into refrigeran

t circuit

, which can 

cause burst or personal inju

ry due to anomalously high pressure in the refrigerant.

• 

Th

el

ec

tr

ic

al

 in

stalla

tio

m

us

t b

ca

rr

ie

ou

t b

th

qu

al

ifi

ed

 e

le

ct

ric

ia

in

 a

cc

or

da

nc

e wi

th

 “

th

no

rm 

fo

r e

le

ct

ric

al

 w

or

k”

 a

nd

 “

nat

io

na

l w

iri

ng

 

re

gu

lat

io

n”

, a

nd

 th

e sy

st

em 

m

ust

 b

co

nn

ec

te

to

 th

de

di

ca

te

ci

rcu

it.

 

Power supply with insufficient capacity and incorrect function done by improper  work can cause electric shocks and fire.

• 

Be sure to shut off the power before starting electrical work.

 

Failure to shut off the power can cause electric shocks

, unit failure or incorrect 

function of equipment.

• 

Be sure to use the cables conformed to safety standard and cable  ampacity for power distribution work

 

Unconformable cables can cause electric leak

, anomalous heat production or fire

.  

• 

This appliance must be connected to main power supply by means of a circuit breaker or switch (fuse:20A) with a contact separation of at least 3mm

• 

Arrange the wiring in the control box so that it cannot be pushed up  further into the box

. Install the se

rvice panel correctl

y.

 

Incorrect installation may result in overheating and fire.

• 

Use the prescribed cables for electrical connection

, tighten the cables 

securely in terminal block and relieve the cables correctly to prevent  overloading the terminal blocks.

 

Lo

os

co

nn

ec

tio

ns

 o

r c

ab

le

 m

ou

nt

ings

 c

an

 c

au

se

 a

no

m

al

ous 

he

at

 p

ro

du

ct

io

or

 fi

re

.

• 

Be sure to fix up the se

rvice panels.

 

Incorrect fixing can cause electric shocks or fire due to intrusion of dust or wate

r.

• 

Be sure to switch off the power supply in the event of installation

inspection or se

rvicing.

 

If the power supply is not shut off

, there is a risk of electric shocks

, unit failure or 

personal inju

ry due to the unexpected start of fan.

• 

Stop the compressor before rem

oving the pipe after shutting the 

se

rvice 

valve on pump down work.

 

If the pipe is removed when the compressor is in operation with the se

rvice valve 

open

, air would be mixed in the refrigeration circuit and it could cause explosion 

and injuries due to abnormal high pressure in the cooling cycle.

• 

Only use prescribed optional parts

. The installation must be carried out 

by the qualified installe

r.

 

If you install the system by yourself

, it can cause serious trouble such as water 

leaks

, electric shocks

, fire.

• 

Be sure to wear protective goggles and gl

oves while at work.

• 

Earth leakage breaker must be installed.

 

If the earth leakage breaker is not installed

, it can cause electric shocks.

• 

After completed installation

, check that no refrigerant leaks from the 

system.

 

If refrigerant leaks into the room and comes into contact with an oven or other hot 

surface

, poisonous gas is produced.

• 

Hang up the unit at the specified points with ropes which can su

pport the 

weight in lifting for portage

. And to avoid jolting out of alignment

, be sure 

to hang up the unit at 4-point support.

 

An improper manner of portage such as 3-point support can cause death or 

serious personal inju

ry due to falling of the unit.

• 

Consult the dealer or an 

expert regarding rem

ov

al of the unit.

 

Incorrect installation can cause water leaks

, electric shocks or fire.

• 

Do not perform brazing work in the airtight room.

 

It can cause lack of oxygen.

• 

This unit is designed specifically for R32.

 

Using any other refrigerant can cause u

nit failure and personal inju

ry

.

• 

Do not bundling

, winding or processing for the power cord

. O

r, do not 

deforming the power plug due to tread it.

 

This may cause fire or heating.

• 

Do not run the unit with rem

oved panels or protections.

 

Touching rotating equipments

, hot surfaces or high voltage parts can cause 

personal inju

ry due to entrapment

, burn or electric shocks.

• 

Do not perform a

ny change of protective device itself or its setup condition.

 

The forced operation by short-circuiting protective device of pressure switch and 

temperature controller or the use of non specified component can cause fire or burst.

• 

Do not perform a

ny repairs or modifications by yourself

. Consult the dealer 

if the unit requires repai

r.

 

If you repair or modify the unit

, it can cause water leaks

, electric shocks or fire.

• 

Take care when car

rying the unit by hand.

 

If the unit weights more than 20kg

, it must be carried by two or more persons

. Do 

not car

ry by the plastic straps

, always use the car

ry handle when car

rying the unit 

by hand

. Use gloves to minimize the risk of cuts by the aluminum fins.

• 

Dispose of a

ny packing materials correctl

y.

 

Any remaining packing materials can cause personal inju

ry

. T

o avoid danger of 

suffocation

, be sure to keep the plastic wrapper away from children and to 

dispose after tear it up.

 

• 

Be sure to insulate the refrigerant pipes so as not to condense the  ambient air moisture on them.

 

Ins

uf

fic

ie

nt insu

la

tio

ca

ca

us

cond

ens

at

io

n,

 which

 c

an 

le

ad

 to

 mo

is

tu

re

 

da

m

ag

on the 

ce

ili

ng

, fl

oo

r, fu

rniture 

and a

ny

 o

th

er

 v

al

ua

bl

es

.

• 

Be s

ur

to

 p

er

fo

rm air t

ig

ht

ness test 

by 

press

ur

iz

in

w

ith

 n

itr

og

en

 g

as

 

after

 c

om

plet

ed

 refr

ig

eran

t p

ip

in

w

or

k.

 

If the density of refrigerant exceeds the limit in the event of refrigerant leakage in 

the small room

, lack of oxygen can occu

r, which can cause serious accidents.

• 

Do

 no

t i

nstall t

he

 o

ut

do

or 

un

it i

th

e lo

cat

io

ns lis

ted

 b

el

ow

.

 L

oc

at

io

ns

 w

he

re

 discha

rg

ed 

hot

 air o

r o

pe

ra

ting sound 

of

 th

e ou

td

oo

r unit c

an

 

bot

he

r n

eigh

bo

rh

oo

d.

 L

oc

at

io

ns

 w

he

re

 ou

tle

t air

 of

 th

ou

td

oor un

it bl

ow

s dir

ect

ly 

to

 a

ani

m

al 

or

 

pl

an

ts

. Th

ou

tle

t a

ir 

can

 af

fe

ct

 a

dv

er

sel

to

 th

e pl

an

t e

tc

.

 L

oc

at

io

ns

 w

he

re 

vib

rat

ion 

can b

amplified 

and

 tr

ansm

itt

ed due

 to

 insu

ffi

ci

en

st

re

ng

th

 o

f s

tru

ct

ur

e.

 L

oc

at

io

ns wh

er

vib

ra

tio

and op

er

at

io

n sound g

en

er

at

ed b

th

e ou

tdo

or

 un

it 

can 

af

fe

ct

 s

er

io

us

ly (

on

 th

e w

all

 o

r a

t t

he

 pl

ace 

ne

ar

 bed

 ro

om

).

 L

oc

at

io

ns

 w

he

re

 an

 e

quipme

nt

 af

fe

ct

ed by high h

ar

m

onics is p

la

ce

d (TV s

et

 o

ra

dio

 re

ce

ive

r is p

la

ce

w

ithin

 5

m

).

 L

oc

at

io

ns

 w

he

re

 d

ra

in

ag

ca

nn

ot

 run 

of

f s

af

el

y.

 

It ca

af

fe

ct

 sur

ro

undin

en

vir

on

m

en

t a

nd

 c

aus

cl

ai

m

.

• 

Do

 no

t i

nstall 

the

 u

nit 

ne

ar

 th

e l

oc

ati

on

 w

he

re

 le

ak

ag

of

 co

mb

ust

ib

le

 

gase

ca

oc

cu

r.

 

If 

le

aked

 g

ases accumu

la

te a

ro

und 

the un

it,

 it

 c

an

 c

aus

fir

e.

• 

Do

 n

ot install th

uni

t w

her

co

rr

osiv

gas (

su

ch as s

ulf

ur

ous 

ac

id gas 

etc

.) 

or

 c

om

bu

stibl

gas (

su

ch as t

hi

nn

er a

nd

 p

et

ro

le

um

 g

ases) 

ca

n accum

ula

te

 

or

 c

olle

ct

, o

r w

here

 v

olatile 

co

m

bus

tib

le 

su

bst

an

ces are h

an

dl

ed

.

 

Co

rr

os

ive

 g

as

 c

an

 c

au

se

 c

or

ro

si

on

 o

f h

ea

t e

xc

ha

ng

er

, b

re

ak

ag

of

 p

la

st

ic

 p

ar

ts

 

an

et

c.

 A

nd

 c

ombustib

le

 g

as

 c

an ca

us

fir

e.

• 

Do

 no

t i

nstall

 no

r u

se

 th

e syst

em 

clo

se

 to 

the

 equ

ipme

nt 

th

at g

en

er

at

es

 

el

ec

tr

oma

gn

et

ic

 fi

el

ds 

or

 h

ig

h f

re

quen

cy

 h

arm

on

ic

s.

 

Equipme

nt

 such

 a

s i

nv

er

te

rs

, s

tand

by

 ge

ne

ra

to

rs

, medical high

 freque

ncy

 

equipme

nt

s and

 te

le

communic

at

io

equip

m

en

ts can 

aff

ec

t t

he

 s

ys

te

m

, a

nd

 c

au

se

 

m

al

fun

ct

io

ns 

and b

re

akdo

wn

s.

 The sy

ste

m can 

also 

af

fe

ct

 m

edi

cal equipment 

an

te

le

communic

at

io

n equipme

nt

, and

 o

bs

tru

ct

 it

fun

ct

io

or caus

e jammi

ng

.

• 

Se

cur

e a 

sp

ac

e f

or

 in

stallat

ion

, i

ns

pec

tion

 a

nd

 m

ai

nt

en

an

ce

 s

pe

cifi

ed

 in

 

the

 m

anu

al

.

 

In

su

ffi

ci

en

t sp

ac

can 

re

su

lt in accide

nt

 suc

as 

pe

rsonal in

ju

ry

 du

e to

 fa

lling

 fr

om

 

th

e i

ns

ta

llat

io

n pl

ac

e.

 D

no

t install 

th

ou

td

oo

r u

nit in a 

lo

ca

tio

w

he

re i

ns

ects

 a

nd 

sm

al

animals c

an

 in

ha

bi

t.

 

Ins

ec

ts and small an

im

al

can en

te

r the e

le

ct

ric

 p

art

s an

cause damage or

 fi

re

In

st

ru

ct

 th

e us

er

 to

 ke

ep

 the 

su

rro

unding

cl

ea

n.

 D

no

t u

se the base fra

m

fo

r o

ut

do

or

 u

nit

 w

hi

ch

 is

 c

or

ro

de

or

 d

am

ag

ed

 

du

to

 lo

ng

 p

er

io

ds

 o

f o

pe

ra

tio

n.

 

Using an old and da

m

age bas

frame

 c

an

 c

aus

th

e u

ni

t f

alling d

ow

n and c

au

se 

pe

rs

onal in

ju

ry

 D

no

t u

se

 a

ny ma

te

rial

ot

he

r t

ha

n a

 fu

se

 w

ith

 th

co

rr

ect rat

in

g in t

he

 

lo

cat

io

w

he

re

 fu

se

s a

re

 to

 b

us

ed.

 

Conn

ec

ting 

th

ci

rc

ui

t w

ith

 c

op

pe

r wi

re

 o

r o

th

er

 m

et

al

 th

re

ad

 c

an

 c

ause un

it 

fai

lu

re and

 fi

re

.

 D

no

t t

ou

ch

 a

ny

 b

ut

to

ns

 w

ith

 w

et h

an

ds

.

 

It 

ca

cau

se

 el

ec

tric s

ho

cks

.

 D

no

t t

ou

ch

 a

ny

 re

fr

ig

er

an

t p

ip

es

 w

ith

 y

ou

r h

an

ds

 w

he

th

e sys

te

m

 is

 in

 

op

era

tio

n.

 

Du

ring op

er

at

ion

 the 

re

frige

rant pi

pe

s b

ec

ome e

xt

re

mely 

ho

t o

r e

xt

re

m

el

co

ld

 

de

pe

ndin

th

op

er

atin

cond

iti

on

, a

nd i

t c

an

 c

au

se

 burn in

ju

ry

 o

r f

ro

st

 in

ju

ry

.

 Do 

no

t t

ou

ch

 th

e su

ct

io

or al

um

in

um fi

on

 th

ou

td

oo

r u

ni

t.

 

This 

m

ay

 c

ause in

ju

ry

.

 D

no

t p

ut

 a

ny

th

in

on t

he 

ou

td

oo

r u

nit

 a

nd

 o

pe

ra

tin

un

it.

 

This 

m

ay

 c

ause

 d

am

ag

th

ob

je

cts 

or

 in

ju

ry due

 to

 fa

llin

to

 th

ob

je

ct.

 D

no

t u

se

 th

unit

 fo

r s

pe

cial

 p

ur

po

ses 

su

ch as s

to

rin

food

s,

 co

ol

in

pr

ec

is

io

n inst

ru

m

en

ts 

an

pr

es

er

va

tio

of

 a

ni

m

al

s,

 p

la

nt

or 

art

.

 D

no

t c

le

an

 u

th

un

it 

w

ith

 w

at

er

.

 D

no

t s

te

on

to

 th

ou

td

oo

r u

ni

t.

 W

he

th

ou

tdo

or

 u

nit is 

in

stal

le

on 

ro

of

 o

r a 

hi

gh

 p

la

ce

, p

ro

vi

de

 

pe

rma

ne

nt l

ad

de

rs 

an

ha

nd

rails 

al

on

th

ac

ce

ss

 ro

ute

 a

nd

 fe

nc

es

 

ha

nd

rails 

ar

ou

nd

 th

ou

td

oo

r un

it.

Inverter

 driven

 split

 P

AC

90,

 100VNP

Designed

 for

 R32

 refrigerant

a

b

c

d

e

f

g

h

Gauge manifold

Charge hose

Electronic scale for refrigerant charging

Torque wrench

Flare tool

Protrusion control copper pipe gauge

Vacuum pump adapter

Gas leak detector

Dedicated R32 tools

● 

Do not use any refrigerant other than R32.

 R32 will rise to pressure about 1.6 times higher than that of a conventional refrigerant (R22 or 

R407C). A cylinder containing R32 has a lightblue indication mark on the top.

● 

A unit designed for R32 has adopted a different size indoor unit service valve charge port and a different size check joint p

rovided in the unit 

to prevent the charging of a wrong refrigerant by mistake. The processed dimension of the flared part of a refrigerant pipe and a flare nut's parallel side measurement have also been alter

ed to raise 

strength against pressure. Accordingly, you are required to arrange dedicated R32 tools listed in the table on the next page before installing or servicin

g this unit.

● 

All indoor units must be models designed exclusively for R32. Check connectable indoor unit models in a catalog, etc. (A wrong 

in door unit, 

if connected into the system, will impair proper system operation)

Accessories for outdoor unit

• Model name and power source • Refrigerant piping length • Piping, wiring and miscellaneous small parts • Indoor unit installation manual

Grommet (Heat pump type only)

Drain elbow (Heat pump type only)

Reducer set ø9.52    ø6.35

2

1

1

Check before installation work

Q’ty

201907

2. REFRIGERANT PIPING WORK

1)

Restrictions

on

unit

installation

and

use

 

Check

the

following

points

in

light

of

the

indoor

unit

specifications

and

the

installation

site.

 

Obse

rve

the

following

restrictions

on

unit

installation

and

use.

  

Improper

installation

can

result

in

a

compressor

failure

or

pe

rformance

degradation

.

2)

Determination

of

pipe

size

 

Determine

refrigerant

pipe

size

pursuant

to

the

following

guidelines

based

on

the

  

indoor

unit

specifications.

Gas pipe

Liquid pipe

ø15.88

ø6.35

Flare

Flare

ø15.88

ø6.35

ø15.88

ø9.52

1. HAULAGE AND INSTALLATION

(T

ake particular care in car

rying in or moving the unit, and always pe

rform such an operation with two or more persons.)

Intake

The

height

of

a

wall

is

1200mm

or

less.

(

se

rvice

  space

)

Intake

Outlet

Fasten

with

bolts

(M10-12)

Use

a

thicker

block

to

 

anchor

deepe

r.

Use

a

long

block

to

extend

the

width.

CAUTION

When

a

unit

is

hoisted

with

slings

for

haulage,

take

into

consideration

the

offset

of

its

gravity

center

position.

  

If

not

properly

balanced,

the

unit

can

be

thrown

off-balance

and

fall.

1)

Delivery

Deliver

the

unit

as

close

as

possible

to

the

installation

site

before

removing

it

from

the

packaging.

When

you

have

to

unpack

the

unit

for

a

compelling

reason

before

you

haul

it

to

the

installation

point,

hoist

the

unit

with

nylon

slings

or

ropes

and

protection

pads

so

that

you

may

not

damage

the

unit.

2)

Portage

The

right

hand

side

of

the

unit

as

viewed

from

the

front

(diffuser

side)

is

heavie

r.

A

person

car

rying

the

right

hand

side

must

take

heed

of

this

fact.

A

person

car

rying

the

left

hand

side

must

hold

with

his

right

hand

the

handle

provided

on

the

front

panel

of

the

unit

and

with

his

left

hand

the

corner

column

section

.

5)

Installation

space

W

alls surrounding the unit in the four sides are not acceptable.

There must be a 1-meter or larger space in the above.

When more than one unit are installed side by side, provide a 250mm or wider interval between them as a service  space.  In order to facilitate servicing of controllers, please provide a sufficient space between units so that their  top plates can be removed easily.

Where a danger of short-ci

rcuiting exists, install guide louvers.

When more than one unit are installed, provide sufficient intake space consciously so that short-ci

rcuiting may not occur

.

Where

piling

snow

can

bu

ry

the

outdoor

unit,

provide

proper

snow

guards.

L

3

L

2

L

4

L

1

Example installation

Size

In installing the unit, fix the unit

’s legs with bolts specified on the above.

The protrusion of an anchor bolt on the front side must be kept within 15 mm.

Securely install the unit so that it does not fall over during earthquakes or strong winds, etc.

Refer to the above illustrations for information regarding concrete foundations.

Install the unit in a level area. (With a gradient of 5 mm or less.) Im

pr

op

er

 in

st

al

la

tio

ca

re

su

lt 

in

a

co

m

pr

es

so

rf

ai

lu

re

, b

ro

ke

n

pi

pi

ng

w

ith

in

th

e

un

it

an

ab

no

rm

al

 n

oi

se

 g

en

er

at

io

n.

6)

Installation

L

H

Outdoor unit

Indoor unit

CAUTION

Th

e

us

e

re

st

ric

tio

ns

ap

pe

ar

in

g

in

th

e

ta

bl

e

ab

ov

e

ar

e

ap

pl

ica

bl

e

to

th

e

st

an

da

rd

pi

pe

siz

e

co

m

bi

na

tio

ns

sh

ow

n

in

th

e

ta

bl

e

be

lo

w.

W

he

re

an

ex

ist

in

g

pi

pe

 s

ys

te

m

 is

 u

til

ize

d,

di

ffe

re

nt

 o

ne

-w

ay

pi

pe

 le

ng

th

 re

st

ric

tio

ns

sh

ou

ld

 a

pp

ly 

de

pe

nd

in

on

 it

pi

pe

siz

e.

Fo

r m

or

e

in

fo

rm

at

io

n,

 p

lea

se

se

e

“5

. U

TI

LI

ZA

TI

ON

OF

 E

XI

ST

IN

G

PI

PI

NG

.”

Outdoor unit connected

Refrigerant piping (branch pipe

L)

Indoor unit connected

About brazing

When pipe is brazing.

(2)

If

the

unit

can

be

affected

by

strong

wind,

following

measures

are

required.

Strong

wind

can

cause

damage

of

fan

(fan

motor),

or

can

cause

pe

rformance

degradation,

or

can

trigger

anomalous

stop

of

the

unit

due

to

rising

of

high

pressure.

3)

 Refrigerant

 pipe

 wall

 thickness

 and

 material

Select

 refrigerant

 pipes

 of

 the

 table

 shown

 on

 the

 right

 wall

 thickness

 and

 material

 as

 specified

 for

 each

 pipe

 size.

Pipe diameter [mm]

Minimum pipe wall thickness [mm]

Pipe material*

ø6.35

0.8

O-type pipe

ø15.88

1.0

O-type pipe

*Phosphorus deoxidized seamless copper pipe  ICS 23.040.15, ICS 77.150.30

NOTE

Select

 pipes

 having

 a

 wall

 thickness

 larger

 than

 the

 specified

 minimum

 pipe

 thickness.

He

avy

Pad

L1

L2

L3

L4

Open

300

100

250

Open

250

150

250

500

Open

100

250

(mm)

I

II

III

60

580

340

19

380

418

19

880

87.9

15

150

150

Intake

Outlet

① 

Anchor bol tfixed position

② 

Notabilia for installation

Plug the end of the pipe with tape, or other  material, and fill the pipe with nitrogen gas.

Only use nitrogen gas (N

2

)

Taping

N

2

Nitrogen

Brazing

Station valve

Prima

ry side

Seconda

ry side

0.5MPa

Hand

Relief valve

Nitrogen

gas

Brazing

must

be

performed

under

a

nitrogen

gas

flo

w

.

Without

nitrogen

gas,

a

large

quantity

of

foreign

matters

(oxidized

film)

are

created,

causing

a

critical

failure

from

capilla

ry

tube

or

expansion

valve

clogging.

If the refrigerant is existing in the pipe at brazing, poisonous gas is produced.

Wind

 direction

Wind

 direction

Over

 500

 mm

2.Install the outlet air blow side of 

the unit in a position perpendicular  to the direction of wind.

3.

The

 unit

 should

 be

 installed

 on 

the

 stable

 and

 level

 foundation.

If 

the

 foundation

 is

 not

 level, 

the

 down

 the

 unit

 with

 wires.

1.

Install the outlet air blow side of the  unit to face a wall of building, or  provide a fence or a windbreak screen.

7)  To run the unit for a cooling operation, 

when the outdoor temperature is –5°C or lower. 

 

When the outdoor air temperature is –5°C or lower, provide a snow hood to the outdoor unit on site. So that strong wind will not blow against the outdoor heat exchanger directly.

4)

Caution

about

selection

of

installation

location

(1)

If

the

unit

is

installed

in

the

area

where

the

snow

will

accumulate,

following

measures

are

required.

The

bottom

plate

of

unit

and

intake,

outlet

may

be

blocked

by

sno

w

.

1

2

Provide

a

snow

hood

to

the

outdoor

unit

on

site.

3

Install

the

unit

under

eaves

or

provide

the

roof

on

site.

Since

drain

water

generated

by

defrost

control

may

freeze,

following

measures

are

required.

Don’t execute drain piping work 

by using a drain elbow and drain grommets (accessories).

 [Refer to Drain piping work.]

Install the unit on the base so  that the bottom is higher than  snow cover surface, and  draining water is secured.

● 

Attached heater on a base plate on site, if there is possibility to freeze drain water. In case that the product has a corrective drainage system, the drainage paths should have suitable  threatment against freezing but be sure not to melt the material of drainage paths with heat.

30m

or less

20m

or less

20m

or less

L

H

H

Restrictions

Dimensional restrictions

Marks appearing in the drawing on the right

Main pipe length

Elevation difference between 

Indoor unit

indoor and outdoor units

When the outdoor unit is positioned higher

FDT, FDE, FDU, FDUM, SRK

When the outdoor unit is positioned lower

3)

  S

el

ec

tio

of

 in

stalla

tio

lo

ca

tio

fo

th

ou

td

oo

un

it

Be

 s

ur

to

 sele

ct

 a

 s

ui

ta

ble

 in

st

alla

tio

pla

ce

 in

 c

on

si

de

ra

tio

of

 fo

llo

w

in

co

nd

iti

on

s.

 

pla

ce

 w

he

re

 it

 is

 h

or

iz

on

ta

l, 

st

ab

le

 a

nd

 c

an

 e

nd

ur

th

un

it 

w

ei

gh

t a

nd

 wi

ll 

no

t a

llo

w

 v

ib

ra

tio

tr

an

sm

itt

an

ce

 

of

 th

un

it.

 

pla

ce

 w

he

re

 it

 c

an

 b

fr

ee

 fr

om

 p

os

si

bi

lit

of

 b

ot

he

rin

ne

ig

hb

or

du

to

 n

oi

se

 o

ex

ha

us

t a

ir 

fr

om

 th

un

it.

 

pla

ce

 w

he

re

 th

un

it 

is

 n

ot

 e

xp

os

ed

 to

 o

il 

sp

la

sh

es

.

 

pla

ce

 w

he

re

 it

 c

an

 b

fr

ee

 fr

om

 d

an

ge

of

 fl

am

m

ab

le

 g

as

 lea

ka

ge

.

 

pla

ce

 w

he

re

 d

ra

in

 w

at

er

 c

an

 b

di

sp

os

ed

 w

ith

ou

t a

ny

 tr

ou

bl

e.

 

pla

ce

 w

he

re

 th

un

it 

wil

l n

ot

 b

af

fe

ct

ed

 b

he

at

 r

ad

ia

tio

fr

om

 o

th

er

 h

ea

t s

ou

rc

e.

 

pla

ce

 w

he

re

 s

no

w

 wil

l n

ot

 a

cc

um

ul

at

e.

 

pla

ce

 w

he

re

 th

un

it 

ca

be

 k

ep

t aw

ay

 5

m

 o

m

or

fr

om

 T

se

t a

nd

/o

ra

di

recei

ve

in

 o

rd

er

 to

 a

vo

id

 a

ny

 

ra

di

or

 T

in

te

rf

er

en

ce

.

 

pla

ce

 w

he

re

 g

oo

ai

ci

rc

ula

tio

ca

be

 s

ec

ur

ed

, a

nd

 e

no

ug

 h

se

rvi

ce

 s

pa

ce

 c

an

 b

se

cu

re

fo

ma

in

te

na

nc

an

se

rvic

of

 th

un

it 

sa

fe

ly

.

 

pla

ce

 w

he

re

 th

un

it 

wi

ll 

no

t b

af

fec

te

by

 el

ec

tr

om

ag

ne

tic

 wav

es

 a

nd

/o

r h

ig

h-

ha

rm

on

ic

 wav

es

 g

en

er

at

ed

 b

ot

he

eq

ui

pm

en

t.

 

pla

ce

 w

he

re

 c

hemic

al

 s

ub

st

an

ce

lik

su

lfu

ric

 g

as

, c

hl

or

ic

 g

as

, a

ci

an

alka

li 

(in

cl

ud

in

ga

m

m

on

ia

), 

w

hi

ch

 c

an

 

ha

rm

 th

un

it,

 wil

l n

ot

 b

ge

ne

ra

te

an

no

t r

em

ai

n.

 

If 

op

er

at

io

is

 c

on

du

ct

ed

 w

he

th

ou

td

oo

ai

te

m

pera

tu

re

 is

 -

lo

w

er

, t

he

 o

ut

do

or

 u

ni

t s

ho

ul

be

 in

stall

ed

 

at

 a

 p

lace

 w

he

re i

t i

no

t i

nfl

ue

nc

ed

 b

na

tu

ral w

in

d.

 

pla

ce

 w

he

re

 s

tr

on

w

in

d wi

ll 

no

t b

lo

w

 a

ga

in

st

 th

ou

tle

t a

ir 

bl

ow

 o

f t

he

 u

ni

t.

D

no

in

st

al

l t

he

 u

ni

in

 p

lac

es

 w

hi

ch

 e

xp

os

ed

 to

 s

ea

 b

ree

ze

 (

e.

g.

 c

oa

st

al

 a

re

a)

 o

cal

ci

um

 c

hl

or

id

(e

.g

. s

no

w

 

mel

tin

ag

en

t)

, e

xp

os

ed

 to

 a

m

m

on

ia

 s

ub

st

an

ce

 (

e.

g.

 o

rg

an

ic

 fe

rt

ili

ze

r)

.

PSC012D137

Notabilia as a unit designed for R32

• 

Read the “SAFETY PRECAUTIONS” ca

refully first of all and strictly follow it during the installation work in o

rder 

to p

rotect yourself.

• 

The p

recautionary items mentioned below a

re distinguished into two levels,                          and                       .

                              : 

W

rong installation would cause serious consequences such as injuries or death.

                              : 

W

rong installation might cause serious consequences depending on ci

rcumstances.

Both mentions the important items to p

rotect your health and safety so strictly follow them by any means.

• 

Be su

re to confirm no anomaly on the equipment by commissioning after completed installation and explain the 

operating methods as well as the maintenance methods of this eq

uipment to the user accor

ding to the owner

’s 

manual.

• 

Keep the installation manual together with owner

’s manual at a place whe

re any user can 

read at any time. 

Mo

reover if necessar

y, ask to hand them to a new use

r.

• 

For installing qualified personnel, take p

recautions in 

respect to themselves by using suitable p

rotective 

clothing, g

roves, etc., and then perform the installation works.

• 

Please pay attention not to fall down the tools, etc. when installing the unit at the high position.

• 

If unusual noise can be hea

rd during operation, consult the deale

r.

• 

The meanings of “Marks” used he

re a

re shown as follows:

• 

This installation manual deals with outdoor units and general installation specifications onl

y.  For indoor units, 

refer to the 

respective installation manuals supplied with the units.

• 

When install the unit, be su

re to check whether the selection of installation place, power source specifications, usage limitation (piping length, height di

ffe

rences between indoor and outdoor units, power 

source voltage and etc.) and installation spaces. 

SAFETY PRECAUTION

S

Never do it under any ci

rcumstances.

Always do it acco

rding to the instruction.

CAUTION

W

ARNING

CAUTION

W

ARNING

W

ARNIN

G

CAUTION

• 

Car

ry out the electrical work for ground lead with care.

 

Do not connect the ground lead to the gas line

, water line

, lightning conductor or telephone line

’s ground lead

. Incorrect grounding can cause unit faults such as electric shocks due to short-circuiting.

• 

Ensure that no air enters in the refrigerant circuit when the unit is  installed and rem

oved.

 

If 

ai

r e

nt

ers in

 th

re

fri

ge

ra

nt

 c

irc

ui

t, t

he

 p

re

ss

ur

e in t

he

 re

fri

ge

ra

nt c

ircu

it 

be

co

m

es

 to

o hi

gh

, w

hi

ch

 c

an

 c

au

se

 b

ur

st

 a

nd

 p

er

so

na

l in

ju

ry

.

• 

Do

 n

ot

 p

ro

ce

ss

in

g,

 s

pl

ic

th

po

w

er

 c

or

d,

 o

r s

ha

re

 a

 s

oc

ke

t wit

ot

he

r p

ow

er

 p

lu

gs

.

 

This may cause fire or electric shock due to defecting contact

, defecting insulation 

and ove

r-current etc.

• 

Use the circuit breaker for all pole correct  capacit

y.

 Circuit breaker 

should be the one that disconnect all poles under 

over current.

 

Using the incorrect circuit breake

r, it can cause the unit malfunction and fire.

• 

Install isolator or disconnect switch on the power source wiring in  accordance with the local codes and regulations.

 

The isolator should be locked in OFF state in accordance with EN60204-1.

• 

Af

te

r m

ai

nt

en

an

ce

, al

l w

iri

ng

, w

iri

ng

 ti

es 

an

th

e li

ke

, s

ho

ul

be r

et

ur

ne

to

 th

ei

r o

rig

in

al sta

te

 a

nd

 wi

rin

ro

ut

e,

 a

nd

 th

ne

ce

ss

ar

cl

ea

ra

nc

fr

om

 

all

 m

eta

l p

ar

ts

 s

ho

ul

be

 s

ec

ur

ed

.

• 

Se

cu

re

 a 

sp

ac

e f

or

 in

stallat

io

n,

 in

sp

ec

tio

an

m

ain

te

na

nc

sp

ec

ifi

ed

 in

 

th

m

an

ua

l.

 

Insufficient space can result in accident such as personal inju

ry due to falling 

from the installation place.

• 

Earth 

lea

ka

ge

 b

re

ak

er

 m

ust

 b

e instal

le

d

If 

th

ea

rth 

le

ak

ag

br

ea

ke

r is 

no

t in

st

al

le

d,

 it

 c

an

 c

au

se

 fir

or

 e

le

ct

ric 

sh

oc

ks

.

• 

Do

 no

t i

nstall 

th

un

it i

th

lo

cati

on

s lis

ted

 be

lo

w

.

• 

Lo

ca

tio

ns

 w

he

re 

ca

rb

on

 fi

be

r, 

m

et

al p

ow

de

r or

 a

ny

 p

ow

de

r is 

flo

ati

ng

.

• 

Lo

ca

tio

ns

 w

he

re

 a

ny

 subs

ta

nc

es

 th

at

 c

an 

af

fe

ct

 th

e un

it such

 a

s sulphid

gas

ch

lo

rid

e g

as

, aci

an

al

ka

lin

ca

oc

cu

r. 

• 

Veh

ic

le

and shi

ps

.

• 

Lo

ca

tio

ns

 w

he

re 

co

sm

et

ic o

r spe

ci

al sp

ra

ys

 a

re

 ofte

n u

sed

.

• 

Lo

ca

tions

 w

ith di

re

ct

 ex

posu

re

 o

f o

il mi

st

 a

nd 

st

ea

m su

ch

 a

s k

itch

en a

nd

 

m

ach

in

e pl

an

t.

• 

Lo

ca

tions

 w

he

re

 a

ny

 m

achines

 w

hich ge

ne

ra

te

 high

 fr

eq

ue

ncy

 h

ar

m

on

ic

s a

re

 

us

ed

.

• 

Lo

ca

tio

ns

 w

ith sa

lty a

tmosphe

re

s such 

as 

coa

st

lin

es

• 

Lo

ca

tio

ns

 w

ith 

he

av

y sn

ow

 (I

f in

st

all

ed

, b

e s

ure

 to

 p

ro

vide 

ba

se

 fr

am

and sn

ow

 

ho

od

 m

en

tio

ne

d i

th

m

an

ua

l).

• 

Lo

ca

tions

 w

he

re

 th

e uni

t is

 e

xp

os

ed 

to

 chimn

ey

 smo

ke

.

• 

Lo

ca

tio

ns 

at

 high a

lti

tud

e (m

or

than

 1

000

m hig

h)

.

• 

Lo

ca

tio

ns

 w

ith

 a

m

m

onic

 a

tm

osp

he

res

. (e

.g

. o

rg

anic

 fe

rtiliz

er

)

• 

Lo

ca

tio

ns

 w

ith

 c

alcium chl

or

id

e (e

.g

. s

no

w

 m

el

ting

 a

ge

nt)

.

• 

Lo

ca

tio

ns

 w

he

re h

eat

 ra

di

at

io

fro

m

 o

ther h

eat

 s

ou

rce

 c

an 

affe

ct

 th

e un

it.

• 

Lo

ca

tions

 w

ith

ou

t g

oo

ai

r circu

la

tio

n.

• 

Lo

ca

tio

ns

 w

ith

 a

ny

 ob

st

acl

es 

w

hich 

ca

n pr

ev

en

t in

let

 a

nd

 o

ut

let

 a

ir 

of

 th

e un

it.

• 

Lo

ca

tio

ns

 w

he

re s

ho

rt 

circuit 

of

 a

ir 

ca

occ

ur

 (in

 c

as

of

 mu

ltip

le

 uni

ts

 

in

st

al

la

tio

n)

.

• 

Lo

ca

tio

ns

 w

he

re 

st

ro

ng air b

low

ag

ains

t t

he 

ai

r o

ut

let

 of

 o

ut

door

 un

it.

• 

Lo

ca

tions

 w

he

re

 s

om

et

hing 

lo

ca

te

ab

ov

the un

it 

co

uld

 fal

l.

 

It 

ca

ca

us

re

m

ar

kab

le

 d

ec

re

ase in

 p

er

fo

rm

an

ce

, c

or

ro

si

on

 a

nd

 d

am

ag

of 

co

mpo

ne

nts

, ma

lfu

nc

tio

an

fir

e.

• 

Installation must be carried out by the qualified installe

r.

 

If 

you i

ns

tal

l t

he

 s

ys

te

by

 y

ou

rse

lf,

 it

 m

ay

 c

au

se

 s

er

io

us

 tr

ou

bl

e su

ch

 a

w

at

er

 le

ak

s,

 

el

ec

tri

sh

oc

ks

, fi

re

 a

nd p

er

so

na

l in

ju

ry

, a

res

ul

t o

f a

 s

ys

tem

 m

al

fu

nc

tio

n.

 D

no

ca

rry

 o

ut

 th

e ins

tall

at

io

and 

m

ai

nt

ena

nc

e w

or

ex

ce

pt

 b

the qualifi

ed in

st

al

le

r.

• 

Install the system in full accordance with the installation manual.

 

In

co

rre

ct ins

ta

lla

tio

m

ay

 c

au

se

 b

ur

st

s,

 p

er

so

na

l in

ju

ry

, w

at

er

 le

ak

s,

 e

le

ctr

ic

 

sh

oc

ks

 a

nd

 fi

re

.

• 

Be sure to use only for household and residence.

 

If 

thi

appl

ia

nc

e is ins

ta

lle

d in 

in

fe

rio

r e

nv

iro

nm

en

t s

uc

as

 m

ac

hi

ne

 s

ho

an

et

c.

it 

ca

ca

use 

m

al

fu

nc

tio

n.

• 

When installing in small rooms

, take prevention measures not to 

exceed the density limit of refrigerant in the event of leakage

, referred 

by the formula (accordance with ISO5149)

 

If the density of refrigerant exceeds the limit

, please consult the dealer and install the 

ventilation system

, otherwise lack of oxygen can occu

r, which can cause serious accident.

• 

Use the original accessories and the specified components for  installation.

 

If parts other than those prescribed by us are used

, It may cause water leaks

electric shocks

, fire and personal inju

ry

.

• 

Install the unit in a location with good support.

 

Unsuitable installation locations can cause the unit to fall and cause material 

damage and personal inju

ry

.

• 

Ensure the unit is stable when installed

, so that it can withstand 

earthquakes and strong winds.

 

Unsuitable installation locations can cause the unit to fall and cause material 

damage and personal inju

ry

.

• 

Ve

ntila

te

 th

w

or

ki

ng

 a

re

w

ell in 

th

ev

ent

 o

f r

ef

rig

er

an

t l

ea

ka

ge 

du

rin

in

stalla

tio

n.

 

If the refrigerant comes into contact with naked flames

, poisonous gas is produced.

• 

Use the prescribed pipes

, fl

are nuts and tools for R32.

 

Using existing parts (for R22 or R407C) can cause the unit failure and serious 

accidents due to burst of the refrigerant circuit.

• 

Tighten the 

flare nut by to

rque wrench with specified method.

 

If the flare nut were tightened with excess torque

, this may cause burst and 

refrigerant leakage after a long period.

• 

Do not open the se

rvice 

valves for liquid line and gas line until completed 

refrigerant piping work

, air tightness test and e

vacuation.

 

If the compressor is operated in state of opening se

rvice valves before completed 

connection of refrigerant piping work

, you may incur frost bite or inju

ry from an 

abrupt refrigerant outflow and air can be sucked into refrigeran

t circuit

, which can 

cause burst or personal inju

ry due to anomalously high pressure in the refrigerant.

• 

Th

el

ec

tr

ic

al

 in

stalla

tio

m

us

t b

ca

rr

ie

ou

t b

th

qu

al

ifi

ed

 e

le

ct

ric

ia

in

 a

cc

or

da

nc

e wi

th

 “

th

no

rm 

fo

r e

le

ct

ric

al

 w

or

k”

 a

nd

 “

nat

io

na

l w

iri

ng

 

re

gu

lat

io

n”

, a

nd

 th

e sy

st

em 

m

ust

 b

co

nn

ec

te

to

 th

de

di

ca

te

ci

rcu

it.

 

Power source with insufficient capacity and incorrect function done by improper  work can cause electric shocks and fire.

• 

Be sure to shut off the power before starting electrical work.

 

Failure to shut off the power can cause electric shocks

, unit failure or incorrect 

function of equipment.

• 

Be sure to use the cables conformed to safety standard and cable  ampacity for power distribution work

 

Unconformable cables can cause electric leak

, anomalous heat production or fire

.  

• 

This appliance must be connected to main power source by means of a circuit breaker or switch (fuse:20A) with a contact separation of at least 3mm

• 

Arrange the wiring in the control box so that it cannot be pushed up  further into the box

. Install the se

rvice panel correctl

y.

 

Incorrect installation may result in overheating and fire.

• 

Use the prescribed cables for electrical connection

, tighten the cables 

securely in terminal block and relieve the cables correctly to prevent  overloading the terminal blocks.

 

Lo

os

co

nn

ec

tio

ns

 o

r c

ab

le

 m

ou

nt

ings

 c

an

 c

au

se

 a

no

m

al

ous 

he

at

 p

ro

du

ct

io

or

 fi

re

.

• 

Be sure to fix up the se

rvice panels.

 

Incorrect fixing can cause electric shocks or fire due to intrusion of dust or wate

r.

• 

Be sure to switch off the power source in the event of installation

inspection or se

rvicing.

 

If the power source is not shut off

, there is a risk of electric shocks

, unit failure or 

personal inju

ry due to the unexpected start of fan.

• 

Stop the compressor before rem

oving the pipe after shutting the 

se

rvice 

valve on pump down work.

 

If the pipe is removed when the compressor is in operation with the se

rvice valve 

open

, air would be mixed in the refrigeration circuit and it could cause explosion 

and injuries due to abnormal high pressure in the cooling cycle.

• 

Only use prescribed option parts

. The installation must be carried out 

by the qualified installe

r.

 

If you install the system by yourself

, it can cause serious trouble such as water 

leaks

, electric shocks

, fire.

• 

Be sure to wear protective goggles and gl

oves while at work.

• 

Earth leakage breaker must be installed.

 

If the earth leakage breaker is not installed

, it can cause electric shocks.

• 

After completed installation

, check that no refrigerant leaks from the 

system.

 

If refrigerant leaks into the room and comes into contact with an oven or other hot 

surface

, poisonous gas is produced.

• 

Hang up the unit at the specified points with ropes which can su

pport the 

weight in lifting for portage

. And to avoid jolting out of alignment

, be sure 

to hang up the unit at 4-point support.

 

An improper manner of portage such as 3-point support can cause death or 

serious personal inju

ry due to falling of the unit.

• 

Consult the dealer or an 

expert regarding rem

ov

al of the unit.

 

Incorrect installation can cause water leaks

, electric shocks or fire.

• 

Do not perform brazing work in the airtight room.

 

It can cause lack of oxygen.

• 

This unit is designed specifically for R32.

 

Using any other refrigerant can cause u

nit failure and personal inju

ry

.

• 

Do not bundling

, winding or processing for the power cord

. O

r, do not 

deforming the power plug due to tread it.

 

This may cause fire or heating.

• 

Do not run the unit with rem

oved panels or protections.

 

Touching rotating equipments

, hot surfaces or high voltage parts can cause 

personal inju

ry due to entrapment

, burn or electric shocks.

• 

Do not perform a

ny change of protective device itself or its setup condition.

 

The forced operation by short-circuiting protective device of pressure switch and 

temperature control or the use of non specified component can cause fire or burst.

• 

Do not perform a

ny repairs or modifications by yourself

. Consult the dealer 

if the unit requires repai

r.

 

If you repair or modify the unit

, it can cause water leaks

, electric shocks or fire.

• 

Take care when car

rying the unit by hand.

 

If the unit weights more than 20kg

, it must be carried by two or more persons

. Do 

not car

ry by the plastic straps

, always use the car

ry handle when car

rying the unit 

by hand

. Use gloves to minimize the risk of cuts by the aluminum fins.

• 

Dispose of a

ny packing materials correctl

y.

 

Any remaining packing materials can cause personal inju

ry

. T

o avoid danger of 

suffocation

, be sure to keep the plastic wrapper away from children and to 

dispose after tear it up.

 

• 

Be sure to insulate the refrigerant pipes so as not to condense the  ambient air moisture on them.

 

Ins

uf

fic

ie

nt insu

la

tio

ca

ca

us

cond

ens

at

io

n,

 which

 c

an 

le

ad

 to

 mo

is

tu

re

 

da

m

ag

on the 

ce

ili

ng

, fl

oo

r, fu

rniture 

and a

ny

 o

th

er

 v

al

ua

bl

es

.

• 

Be s

ur

to

 p

er

fo

rm air t

ig

ht

ness test 

by 

press

ur

iz

in

w

ith

 n

itr

og

en

 g

as

 

after

 c

om

plet

ed

 refr

ig

eran

t p

ip

in

w

or

k.

 

If the density of refrigerant exceeds the limit in the event of refrigerant leakage in 

the small room

, lack of oxygen can occu

r, which can cause serious accidents.

• 

Do

 no

t i

nstall 

the

 o

ut

do

or

 u

nit 

in

 th

lo

cati

on

s list

ed

 be

lo

w

.

 L

oc

at

io

ns

 w

he

re discha

rged ho

t a

ir or o

pe

ra

ting 

so

und

 of

 th

ou

td

oo

r un

it 

ca

bot

he

r n

eigh

bo

rh

oo

d.

 L

oc

at

io

ns

 w

he

re

 ou

tle

t air

 of

 th

ou

td

oor un

it bl

ow

s dir

ect

ly 

to

 a

ani

m

al 

or

 

pl

an

ts

. T

he

 o

ut

le

t air

 c

an

 a

ffe

ct

 a

dve

rsel

to

 th

pl

an

t et

c.

 L

oc

at

io

ns

 w

he

re 

vib

rat

ion 

can b

amplified 

and

 tr

ansm

itt

ed due

 to

 insu

ffi

ci

en

st

re

ng

th

 o

f s

tru

ct

ur

e.

 L

oc

at

io

ns wh

er

vib

ra

tio

and op

er

at

io

n sound g

en

er

at

ed b

th

e ou

tdo

or

 un

it 

can 

af

fe

ct

 s

er

io

us

ly (

on

 th

e w

all

 o

r a

t t

he

 pl

ace 

ne

ar

 bed

 ro

om

).

 L

oc

at

io

ns

 w

he

re

 an

 e

quipme

nt

 af

fe

ct

ed by high h

ar

m

onics is p

la

ce

d (TV s

et

 o

ra

dio

 re

ce

ive

r is p

la

ce

w

ithin

 5

m

).

 L

oc

at

io

ns

 w

he

re

 d

ra

in

ag

ca

nn

ot

 run 

of

f s

af

el

y.

 

It ca

af

fe

ct

 sur

ro

undin

en

vir

on

m

en

t a

nd

 c

aus

cl

ai

m

.

• 

Do

 no

t i

nstall 

the

 u

nit 

ne

ar

 th

e l

oc

ati

on

 w

he

re

 le

ak

ag

of

 co

mb

ust

ib

le

 

gase

ca

oc

cu

r.

 

If 

le

aked

 g

ases accumu

la

te a

ro

und 

the un

it,

 it

 c

an

 c

aus

fir

e.

• 

Do

 n

ot install th

uni

t w

her

co

rr

osiv

gas (

su

ch as s

ulf

ur

ous 

ac

id gas etc

.) 

or

 c

om

bu

stibl

gas (

su

ch as t

hi

nn

er a

nd

 p

et

ro

le

um

 g

ases) 

ca

n accum

ula

te

 

or

 c

olle

ct

, o

r w

here

 v

olatile 

co

m

bus

tib

le 

su

bst

an

ces are h

an

dl

ed

.

 

Co

rr

os

ive

 g

as

 c

an

 c

au

se

 c

or

ro

si

on

 o

f h

ea

t e

xc

ha

ng

er

, b

re

ak

ag

of

 pl

as

tic

 p

ar

ts

 

an

et

c.

 A

nd

 c

ombustible 

ga

can ca

us

fir

e.

• 

Do

 no

t i

nstall

 no

r u

se

 the

 syst

em 

clo

se

 to 

the

 equ

ipm

en

t t

hat

 g

en

erat

es

 

el

ec

tr

oma

gn

et

ic

 fi

el

ds

 o

r h

ig

h f

req

uen

cy

 h

arm

on

ic

s.

 

Equipme

nt

 such

 a

s i

nv

er

te

rs

, s

tand

by

 ge

ne

ra

to

rs

, medical high

 freque

ncy

 

equipme

nt

s and

 te

le

communic

at

io

equip

m

en

ts can 

aff

ec

t t

he

 s

ys

te

m

, a

nd

 c

au

se

 

m

al

fun

ct

io

ns 

and b

re

akdo

wn

s.

 The sy

ste

m can 

also 

af

fe

ct

 m

edi

cal equipment a

nd

 

te

le

communic

at

io

n equipme

nt

, and

 o

bs

tru

ct

 it

fun

ct

io

or caus

e jammi

ng

.

• 

Se

cur

e a 

sp

ac

e f

or

 in

stallat

ion

, i

ns

pec

tion

 a

nd

 m

ai

nt

en

an

ce

 s

pe

cifi

ed

 in

 

the

 m

anu

al

.

 

In

su

ffi

ci

en

t sp

ac

can 

re

su

lt in accide

nt

 suc

as 

pe

rsonal in

ju

ry

 du

to

 fallin

fro

m

 

th

e i

ns

ta

llat

io

n pl

ac

e.

 Do

 n

ot install 

th

ou

td

oo

r u

nit in a

 lo

ca

tio

w

he

re in

se

cts 

an

sm

al

animals 

ca

in

ha

bi

t.

 

Ins

ec

ts and small animal

can 

en

te

r t

he

 el

ec

tric

 p

ar

ts

 a

nd

 c

ause

 d

amag

or

 fi

re

In

st

ru

ct

 th

e us

er

 to

 k

ee

th

su

rrounding

cl

ea

n.

 D

no

t u

se

 th

ba

se

 fr

am

fo

r o

ut

do

or

 u

ni

t w

hi

ch

 is

 c

or

ro

de

or

 d

am

ag

ed

 

du

to

 lo

ng

 p

er

io

ds

 o

f o

pe

ra

tio

n.

 

Using a

old and da

m

age 

ba

se

 fr

ame ca

caus

the un

it 

falling d

ow

an

cau

se

 

pe

rs

onal in

ju

ry

 Do

 n

ot

 u

se

 a

ny

 m

aterial

ot

he

r t

ha

n a fus

w

ith

 th

co

rr

ec

t r

at

in

in

 th

lo

cat

io

w

he

re

 fu

ses a

re

 to

 b

e u

se

d.

 

Con

ne

ct

ing

 th

ci

rc

ui

t w

ith 

co

pp

er

 w

ire

 o

r o

th

er

 m

et

al 

th

re

ad

 c

an

 c

ause un

it 

fai

lu

re an

fir

e.

 Do

 n

ot 

to

uc

an

bu

tt

ons

 w

ith

 w

et h

an

ds

.

 

It 

ca

cau

se 

el

ec

tric s

ho

cks

.

 D

no

t t

ou

ch

 a

ny

 re

fr

ig

er

an

t p

ip

es

 w

ith

 y

ou

r h

an

ds 

w

he

th

e system is 

in

 

op

era

tio

n.

 

Du

ring op

er

at

ion

 the 

re

frige

rant pipes b

ec

ome

 e

xtr

emely h

ot 

or

 e

xt

reme

ly 

co

ld

 

de

pe

ndin

th

op

er

at

in

cond

iti

on

, a

nd

 it

 c

an

 c

ause 

bu

rn in

ju

ry

 o

r fr

os

t in

ju

ry

.

 Do 

no

t t

ou

ch

 th

e su

ct

io

or al

um

in

um fi

on

 th

ou

td

oo

r u

ni

t.

 

This 

m

ay

 c

ause in

ju

ry

.

 Do

 n

ot

 p

ut

 a

nyth

in

on

 th

ou

tdo

or

 u

nit

 a

nd

 o

pe

ra

tin

un

it.

 

This 

m

ay

 c

ause

 d

amage

 the o

bj

ec

ts 

or

 in

ju

ry

 du

to 

falling to the o

bj

ect

.

 Do

 n

ot

 u

se

 th

unit

 fo

r s

pe

cia

l p

ur

po

se

suc

h as 

st

or

in

fo

od

s,

 c

oo

lin

pr

ec

is

io

in

st

ru

m

en

ts 

an

pr

es

er

vat

io

of

 a

ni

m

al

s,

 p

la

nt

or

 a

rt

.

 Do

 n

ot

 c

le

an

 u

th

un

it 

w

ith

 w

at

er

.

 Do

 n

ot s

te

ont

o the

 o

ut

do

or

 u

ni

t.

 W

he

th

ou

tdo

or

 u

nit is 

in

stal

le

on a

 roo

f o

r a

 h

ig

pla

ce

, p

ro

vi

de

 

pe

rma

ne

nt l

ad

de

rs 

an

ha

nd

rails 

al

on

th

ac

cess

 rou

te and 

fe

nc

es

 

ha

nd

rails 

ar

ou

nd

 th

ou

td

oo

r un

it.

Inverter

 driven

 split

 P

AC

90,

 100VNP

Designed

 for

 R32

 refrigerant

a

b

c

d

e

f

g

h

Gauge manifold

Charge hose

Electronic scale for refrigerant charging

Torque wrench

Flare tool

Protrusion control copper pipe gauge

Vacuum pump adapter

Gas leak detector

Dedicated R32 tools

● 

Do not use any refrigerant other than R32.

 R32 will rise to pressure about 1.6 times higher than that of a conventional refrigerant (R22 or 

R407C). A cylinder containing R32 has a lightblue indication mark on the top.

● 

A unit designed for R32 has adopted a different size indoor unit operation valve charge port and a different size check joint p

rovided in the 

unit to prevent the charging of a wrong refrigerant by mistake. The processed dimension of the flared part of a refrigerant pipe and a flare nut's parallel side measurement have also been alter

ed to raise 

strength against pressure. Accordingly, you are required to arrange dedicated R32 tools listed in the table on the next page before installing or servicin

g this unit.

● 

All indoor units must be models designed exclusively for R32. Check connectable indoor unit models in a catalog, etc. (A wrong 

in door unit, 

if connected into the system, will impair proper system operation)

Accessories for outdoor unit

• Model name and power source • Refrigerant piping length • Piping, wiring and miscellaneous small parts • Indoor unit installation manual

Grommet (Heat pump type only)

Drain elbow (Heat pump type only)

Reducer set ø9.52    ø6.35

2

1

1

1

2

3

Check before installation work

Q’ty

INS

TALL

ATION MAN

UAL FOR OUTDOOR UNIT

2. REFRIGERANT PIPING WORK

1)

Restrictions

on

unit

installation

and

use

 

Check

the

following

points

in

light

of

the

indoor

unit

specifications

and

the

installation

site.

 

Obse

rve

the

following

restrictions

on

unit

installation

and

use.

  

Improper

installation

can

result

in

a

compressor

failure

or

pe

rformance

degradation

.

2)

Determination

of

pipe

size

 

Determine

refrigerant

pipe

size

pursuant

to

the

following

guidelines

based

on

the

  

indoor

unit

specifications.

Gas pipe

Liquid pipe

ø15.88

ø6.35

Flare

Flare

ø15.88

ø6.35

ø15.88

ø9.52

1. HAULAGE AND INSTALLATION

(T

ake particular care in car

rying in or moving the unit, and always pe

rform such an operation with two or more persons.)

Intake

The

height

of

a

wall

is

1200mm

or

less.

(

se

rvice

  space

)

Intake

Outlet

Fasten

with

bolts

(M10-12)

Use

a

thicker

block

to

 

anchor

deepe

r.

Use

a

long

block

to

extend

the

width.

CAUTION

When

a

unit

is

hoisted

with

slings

for

haulage,

take

into

consideration

the

offset

of

its

gravity

center

position.

  

If

not

properly

balanced,

the

unit

can

be

thrown

off-balance

and

fall.

1)

Delivery

Deliver

the

unit

as

close

as

possible

to

the

installation

site

before

removing

it

from

the

packaging.

When

you

have

to

unpack

the

unit

for

a

compelling

reason

before

you

haul

it

to

the

installation

point,

hoist

the

unit

with

nylon

slings

or

ropes

and

protection

pads

so

that

you

may

not

damage

the

unit.

2)

Portage

The

right

hand

side

of

the

unit

as

viewed

from

the

front

(diffuser

side)

is

heavie

r.

A

person

car

rying

the

right

hand

side

must

take

heed

of

this

fact.

A

person

car

rying

the

left

hand

side

must

hold

with

his

right

hand

the

handle

provided

on

the

front

panel

of

the

unit

and

with

his

left

hand

the

corner

column

section

.

5)

Installation

space

W

alls surrounding the unit in the four sides are not acceptable.

There must be a 1-meter or larger space in the above.

When more than one unit are installed side by side, provide a 250mm or wider interval between them as a service  space.  In order to facilitate servicing of controls, please provide a sufficient space between units so that their top  plates can be removed easily.

Where a danger of short-ci

rcuiting exists, install guide louvers.

When more than one unit are installed, provide sufficient intake space consciously so that short-ci

rcuiting may not occur

.

Where

piling

snow

can

bu

ry

the

outdoor

unit,

provide

proper

snow

guards.

L

3

L

2

L

4

L

1

Example installation

Size

In installing the unit, fix the unit

’s legs with bolts specified on the above.

The protrusion of an anchor bolt on the front side must be kept within 15 mm.

Securely install the unit so that it does not fall over during earthquakes or strong winds, etc.

Refer to the above illustrations for information regarding concrete foundations.

Install the unit in a level area. (With a gradient of 5 mm or less.) Im

pr

op

er

 in

st

al

la

tio

ca

re

su

lt 

in

a

co

m

pr

es

so

rf

ai

lu

re

, b

ro

ke

n

pi

pi

ng

w

ith

in

th

e

un

it

an

ab

no

rm

al

 n

oi

se

 g

en

er

at

io

n.

6)

Installation

L

H

Outdoor unit

Indoor unit

CAUTION

Th

e

us

e

re

st

ric

tio

ns

ap

pe

ar

in

g

in

th

e

ta

bl

e

ab

ov

e

ar

e

ap

pl

ica

bl

e

to

th

e

st

an

da

rd

pi

pe

siz

e

co

m

bi

na

tio

ns

sh

ow

n

in

th

e

ta

bl

e

be

lo

w.

W

he

re

an

ex

ist

in

g

pi

pe

 s

ys

te

m

 is

 u

til

ize

d,

di

ffe

re

nt

 o

ne

-w

ay

pi

pe

 le

ng

th

 re

st

ric

tio

ns

sh

ou

ld

 a

pp

ly 

de

pe

nd

in

on

 it

pi

pe

siz

e.

Fo

r m

or

e

in

fo

rm

at

io

n,

 p

lea

se

se

e

“5

. U

TI

LI

ZA

TI

ON

OF

 E

XI

ST

IN

G

PI

PI

NG

.”

Outdoor unit connected

Refrigerant piping (branch pipe

L)

Indoor unit connected

About brazing

When pipe is brazing.

(2)

If

the

unit

can

be

affected

by

strong

wind,

following

measures

are

required.

Strong

wind

can

cause

damage

of

fan

(fan

motor),

or

can

cause

pe

rformance

degradation,

or

can

trigger

anomalous

stop

of

the

unit

due

to

rising

of

high

pressure.

3)

 Refrigerant

 pipe

 wall

 thickness

 and

 material

Select

 refrigerant

 pipes

 of

 the

 table

 shown

 on

 the

 right

 wall

 thickness

 and

 material

 as

 specified

 for

 each

 pipe

 size.

Pipe diameter [mm]

Minimum pipe wall thickness [mm]

Pipe material*

ø6.35

0.8

O-type pipe

ø15.88

1.0

O-type pipe

*Phosphorus deoxidized seamless copper pipe  ICS 23.040.15, ICS 77.150.30

NOTE

Select

 pipes

 having

 a

 wall

 thickness

 larger

 than

 the

 specified

 minimum

 pipe

 thickness.

He

avy

Pad

L1

L2

L3

L4

Open

300

100

250

Open

250

150

250

500

Open

100

250

(mm)

I

II

III

60

580

340

19

380

418

19

880

87.9

15

150

150

Intake

Outlet

① 

Anchor bol tfixed position

② 

Notabilia for installation

Plug the end of the pipe with tape, or other  material, and fill the pipe with nitrogen gas.

Only use nitrogen gas (N

2

)

Taping

N

2

Nitrogen

Brazing

Station valve

Prima

ry side

Seconda

ry side

0.5MPa

Hand

Relief valve

Nitrogen

gas

Brazing

must

be

performed

under

a

nitrogen

gas

flo

w

.

Without

nitrogen

gas,

a

large

quantity

of

foreign

matters

(oxidized

film)

are

created,

causing

a

critical

failure

from

capilla

ry

tube

or

expansion

valve

clogging.

If the refrigerant is existing in the pipe at brazing, poisonous gas is produced.

Wind

 direction

Wind

 direction

Over

 500

 mm

2.Install the outlet air blow side of 

the unit in a position perpendicular  to the direction of wind.

3.

The

 unit

 should

 be

 installed

 on 

the

 stable

 and

 level

 foundation.

If 

the

 foundation

 is

 not

 level, 

the

 down

 the

 unit

 with

 wires.

1.

Install the outlet air blow side of the  unit to face a wall of building, or  provide a fence or a windbreak screen.

7)  To run the unit for a cooling operation, 

when the outdoor temperature is –5°C or lower. 

 

When the outdoor air temperature is –5°C or lower, provide a snow hood to the outdoor unit on site. So that strong wind will not blow against the outdoor heat exchanger directly.

4)

Caution

about

selection

of

installation

location

(1)

If

the

unit

is

installed

in

the

area

where

the

snow

will

accumulate,

following

measures

are

required.

The

bottom

plate

of

unit

and

intake,

outlet

may

be

blocked

by

sno

w

.

1

2

Provide

a

snow

hood

to

the

outdoor

unit

on

site.

3

Install

the

unit

under

eaves

or

provide

the

roof

on

site.

Since

drain

water

generated

by

defrost

control

may

freeze,

following

measures

are

required.

Don’t execute drain piping work 

by using a drain elbow and drain grommets (accessories).

 [Refer to DRAIN PIPING WORK.]

Install the unit on the base so  that the bottom is higher than  snow cover surface, and  draining water is secured.

● 

Attached heater on a base plate on site, if there is possibility to freeze drain water. In case that the product has a corrective drainage system, the drainage paths should have suitable  threatment against freezing but be sure not to melt the material of drainage paths with heat.

30m

or less

20m

or less

20m

or less

L

H

H

Restrictions

Dimensional restrictions

Marks appearing in the drawing on the right

Main pipe length

Elevation difference between 

Indoor unit

indoor and outdoor units

When the outdoor unit is positioned higher

FDT, FDE, FDU, FDUM, SRK

When the outdoor unit is positioned lower

3)

  S

el

ec

tio

of

 in

stalla

tio

lo

ca

tio

fo

th

ou

td

oo

un

it

Be

 s

ur

to

 sele

ct

 a

 s

ui

ta

ble

 in

st

alla

tio

pla

ce

 in

 c

on

si

de

ra

tio

of

 fo

llo

w

in

co

nd

iti

on

s.

 

pla

ce

 w

he

re

 it

 is

 h

or

iz

on

ta

l, 

st

ab

le

 a

nd

 c

an

 e

nd

ur

th

un

it 

w

ei

gh

t a

nd

 wi

ll 

no

t a

llo

w

 v

ib

ra

tio

tr

an

sm

itt

an

ce

 

of

 th

un

it.

 

pla

ce

 w

he

re

 it

 c

an

 b

fr

ee

 fr

om

 p

os

si

bi

lit

of

 b

ot

he

rin

ne

ig

hb

or

du

to

 n

oi

se

 o

ex

ha

us

t a

ir 

fr

om

 th

un

it.

 

pla

ce

 w

he

re

 th

un

it 

is

 n

ot

 e

xp

os

ed

 to

 o

il 

sp

la

sh

es

.

 

pla

ce

 w

he

re

 it

 c

an

 b

fr

ee

 fr

om

 d

an

ge

of

 fl

am

m

ab

le

 g

as

 lea

ka

ge

.

 

pla

ce

 w

he

re

 d

ra

in

 w

at

er

 c

an

 b

di

sp

os

ed

 w

ith

ou

t a

ny

 tr

ou

bl

e.

 

pla

ce

 w

he

re

 th

un

it 

wil

l n

ot

 b

af

fe

ct

ed

 b

he

at

 r

ad

ia

tio

fr

om

 o

th

er

 h

ea

t s

ou

rc

e.

 

pla

ce

 w

he

re

 s

no

w

 wil

l n

ot

 a

cc

um

ul

at

e.

 

pla

ce

 w

he

re

 th

un

it 

ca

be

 k

ep

t aw

ay

 5

m

 o

m

or

fr

om

 T

se

t a

nd

/o

ra

di

recei

ve

in

 o

rd

er

 to

 a

vo

id

 a

ny

 

ra

di

or

 T

in

te

rf

er

en

ce

.

 

pla

ce

 w

he

re

 g

oo

ai

ci

rc

ula

tio

ca

be

 s

ec

ur

ed

, a

nd

 e

no

ug

 h

se

rvi

ce

 s

pa

ce

 c

an

 b

se

cu

re

fo

m

ai

nt

en

an

ce

 

an

se

rvic

of

 th

un

it 

sa

fe

ly

.

 

pla

ce

 w

he

re

 th

un

it 

wi

ll 

no

t b

af

fect

ed

 b

el

ec

tr

om

ag

net

ic

 wav

es

 a

nd

/o

r h

ig

h-

ha

rm

on

ic

 wav

es

 g

en

er

at

ed

 b

ot

he

eq

ui

pm

en

t.

 

pla

ce

 w

he

re

 c

hemic

al

 s

ub

st

an

ce

lik

su

lfu

ric

 g

as

, c

hl

or

ic

 g

as

, a

ci

an

alka

li 

(in

cl

ud

in

ga

m

m

on

ia

), 

w

hi

ch

 c

an

 

ha

rm

 th

un

it,

 wil

l n

ot

 b

ge

ne

ra

te

an

no

t r

ema

in

.

 

If 

op

er

at

io

is

 c

on

du

ct

ed

 w

he

th

ou

td

oo

ai

te

m

pera

tu

re

 is

 -

lo

w

er

, t

he

 o

ut

do

or

 u

ni

t s

ho

ul

be

 in

st

al

le

at

 a

 p

lace

 w

he

re i

t i

no

t i

nfl

ue

nc

ed

 b

na

tu

ral wi

nd

.

 

pla

ce

 w

he

re

 s

tr

on

w

in

d wi

ll 

no

t b

lo

w

 a

ga

in

st

 th

ou

tle

t a

ir 

bl

ow

 o

f t

he

 u

ni

t.

D

no

in

st

al

l t

he

 u

ni

in

 p

lac

es

 w

hi

ch

 e

xp

os

ed

 to

 s

ea

 b

ree

ze

 (

e.

g.

 c

oa

st

al

 a

re

a)

 o

cal

ci

um

 c

hl

or

id

(e

.g

. s

no

w

 

mel

tin

ag

en

t)

, e

xp

os

ed

 to

 a

m

m

on

ia 

su

bs

ta

nc

(e

.g

. o

rg

an

ic

 fe

rt

ili

ze

r)

.

PSC012D137

Notabilia as a unit designed for R32

• 

Read the “SAFETY PRECAUTIONS” ca

refully first of all and strictly follow it during the installation work in o

rder 

to p

rotect yourself.

• 

The p

recautionary items mentioned below a

re distinguished into two levels,                          and                       .

                              : 

W

rong installation would cause serious consequences such as injuries or death.

                              : 

W

rong installation might cause serious consequences depending on ci

rcumstances.

Both mentions the important items to p

rotect your health and safety so strictly follow them by any means.

• 

Be su

re to confirm no anomaly on the equipment by commissioning after completed installation and explain the 

operating methods as well as the maintenance methods of this eq

uipment to the user accor

ding to the owner

’s 

manual.

• 

Keep the installation manual together with owner

’s manual at a place whe

re any user can 

read at any time. 

Mo

reover if necessar

y, ask to hand them to a new use

r.

• 

For installing qualified personnel, take p

recautions in 

respect to themselves by using suitable p

rotective 

clothing, g

roves, etc., and then perform the installation works.

• 

Please pay attention not to fall down the tools, etc. when installing the unit at the high position.

• 

If unusual noise can be hea

rd during operation, consult the deale

r.

• 

The meanings of “Marks” used he

re a

re shown as follows:

• 

This installation manual deals with outdoor units and general installation specifications onl

y.  For indoor units, 

refer to the 

respective installation manuals supplied with the units.

• 

When install the unit, be su

re to check whether the selection of installation place, power supply specifications, usage limitation (piping length, height di

ffe

rences between indoor and outdoor units, power 

supply voltage and etc.) and installation spaces. 

SAFETY PRECAUTION

S

Never do it under any ci

rcumstances.

Always do it acco

rding to the instruction.

CAUTION

W

ARNING

CAUTION

W

ARNING

W

ARNIN

G

CAUTION

• 

Car

ry out the electrical work for ground lead with care.

 

Do not connect the ground lead to the gas line

, water line

, lightning conductor or telephone line

’s ground lead

. Incorrect grounding can cause unit faults such as electric shocks due to short-circuiting.

• 

Ensure that no air enters in the refrigerant circuit when the unit is  installed and rem

oved.

 

If 

ai

r e

nt

ers i

th

re

fri

ge

ra

nt 

ci

rc

ui

t, 

th

pr

es

su

re

 in 

th

re

fri

ge

ra

nt

 c

irc

ui

be

co

m

es

 to

o hi

gh

, w

hi

ch

 c

an

 c

au

se

 b

ur

st

 a

nd

 p

er

so

na

l in

ju

ry

.

• 

Do

 n

ot 

pr

oc

es

si

ng

, s

pl

ic

th

po

w

er

 c

or

d,

 o

r s

ha

re

 a

 s

oc

ke

t w

ith

 o

th

er

 p

ow

er

 p

lu

gs

.

 

This may cause fire or electric shock due to defecting contact

, defecting insulation 

and ove

r-current etc.

• 

Use the circuit breaker for all pole correct  capacit

y.

 Circuit breaker 

should be the one that disconnect all poles under 

over current.

 

Using the incorrect circuit breake

r, it can cause the unit malfunction and fire.

• 

Install isolator or disconnect switch on the power supply wiring in  accordance with the local codes and regulations.

 

The isolator should be locked in OFF state in accordance with EN60204-1.

• 

Af

te

r m

ai

nt

en

an

ce

, all 

w

iri

ng

, wi

rin

tie

an

th

lik

e,

 s

ho

ul

be

 re

tu

rn

ed

 

to

 th

ei

r o

rig

in

al sta

te

 a

nd

 wi

rin

ro

ut

e,

 a

nd

 th

ne

ce

ss

ar

cl

ea

ra

nc

e f

ro

m

 

all

 m

eta

l p

ar

ts

 s

ho

ul

be

 s

ec

ur

ed

.

• 

Se

cu

re

 a 

sp

ac

e f

or

 in

stallat

io

n,

 in

sp

ec

tio

an

m

ain

te

na

nc

sp

ec

ifi

ed

 in

 

th

m

an

ua

l.

 

Insufficient space can result in accident such as personal inju

ry due to falling 

from the installation place.

• 

Earth

 le

ak

ag

bre

ak

er

 m

ust

 b

in

stal

le

d

If 

th

ea

rth

 le

ak

ag

br

eak

er is 

no

t in

st

all

ed

, i

t c

an

 c

au

se

 fi

re

 o

r e

le

ctr

ic 

sh

oc

ks

.

• 

Do

 no

t i

nstall 

th

un

it i

th

lo

cati

on

s lis

ted

 be

lo

w

.

• 

Lo

ca

tio

ns

 w

he

re 

ca

rb

on

 fi

be

r, 

m

et

al 

pow

de

r o

r a

ny

 p

ow

de

r is 

flo

at

in

g.

• 

Lo

ca

tio

ns

 w

he

re

 a

ny

 subs

ta

nc

es

 th

at

 c

an 

af

fe

ct

 th

e un

it such

 a

s sulphi

de

 g

as

ch

lo

rid

e g

as

, a

cid an

al

ka

lin

ca

oc

cu

r. 

• 

Veh

ic

le

and shi

ps

.

• 

Lo

ca

tio

ns

 w

he

re 

co

sm

et

ic o

r spe

ci

al sp

ra

ys

 a

re

 ofte

n u

sed

.

• 

Lo

ca

tions

 w

ith di

re

ct

 ex

posu

re

 o

f o

il mi

st

 a

nd 

st

ea

m su

ch

 a

s k

itch

en a

nd

 

m

ach

in

pl

an

t.

• 

Lo

ca

tions

 w

he

re

 a

ny

 m

achines

 w

hich ge

ne

ra

te

 high

 fr

eq

ue

ncy

 h

ar

m

on

ic

s a

re

 

us

ed

.

• 

Lo

ca

tio

ns

 w

ith 

sa

lty

 a

tm

osph

er

es such 

as 

coa

st

lin

es

• 

Lo

ca

tio

ns

 w

ith 

he

av

y sn

ow

 (I

f in

st

all

ed

, b

e s

ure

 to

 p

ro

vide 

ba

se

 fr

am

and s

now

 

ho

od m

en

tio

ne

d i

th

m

an

ua

l).

• 

Lo

ca

tio

ns

 w

he

re

 th

e uni

t is

 e

xp

osed 

to

 chim

ney

 s

m

ok

e.

• 

Lo

ca

tions 

at

 high

 a

lti

tud

e (m

or

th

an 

100

0m hig

h)

.

• 

Lo

ca

tio

ns

 w

ith

 a

m

m

oni

at

m

osp

he

re

s.

 (e

.g

. o

rg

anic

 fe

rtiliz

er

)

• 

Lo

ca

tio

ns

 w

ith

 c

alcium chl

or

id

e (e

.g

. s

no

w

 m

el

ting

 a

ge

nt)

.

• 

Lo

ca

tio

ns

 w

he

re h

eat

 ra

di

at

io

fro

m

 o

ther h

eat

 s

ou

rce

 c

an 

affe

ct

 th

e un

it.

• 

Lo

ca

tions

 w

ith

ou

t g

oo

ai

r circu

la

tio

n.

• 

Lo

ca

tio

ns

 w

ith

 a

ny

 ob

st

acl

es 

w

hich 

ca

n pr

ev

en

t in

let

 a

nd

 o

ut

let

 a

ir 

of

 th

e un

it.

• 

Lo

ca

tio

ns

 w

he

re s

ho

rt 

circuit 

of

 a

ir 

ca

occ

ur

 (in

 c

as

of

 mu

ltip

le

 un

its

 

instal

la

tio

n)

.

• 

Lo

ca

tio

ns

 w

he

re 

st

ro

ng air b

low

ag

ains

t t

he 

ai

r o

ut

let

 of

 o

ut

door

 un

it.

• 

Lo

ca

tions

 w

he

re

 s

om

et

hing 

lo

ca

te

ab

ov

the un

it 

co

uld

 fal

l.

 

It 

ca

ca

us

re

m

ar

ka

bl

de

cr

ea

se

 in p

er

fo

rm

an

ce

, c

or

ro

si

on

 a

nd

 d

am

ag

of 

co

m

po

nen

ts

, m

al

fu

nct

io

an

fir

e.

• 

Installation must be carried out by the qualified installe

r.

 

If 

you in

st

al

l t

he

 s

ys

tem 

by

 y

ou

rs

el

f, 

it 

m

ay

 c

au

se

 s

er

io

us

 tr

ou

bl

e su

ch

 a

w

at

er

 le

ak

s,

 

el

ec

tri

c s

ho

ck

s,

 fi

re

 a

nd 

pe

rsonal in

ju

ry

, a

res

ul

t o

f a

 s

ys

tem 

m

al

fu

nc

tio

n.

 D

no

ca

rry

 o

ut

 th

e ins

tall

at

io

and 

m

ai

nt

ena

nc

e w

or

ex

cep

t b

th

e qu

ali

fie

d in

sta

lle

r.

• 

Install the system in full accordance with the installation manual.

 

In

co

rre

ct in

st

al

la

tio

m

ay

 c

aus

bu

rs

ts

, p

er

so

na

l in

ju

ry

, w

at

er

 le

ak

s,

 e

le

ct

ric

 

sh

oc

ks and fi

re

.

• 

Be sure to use only for household and residence.

 

If 

this app

lia

nc

e is ins

ta

lle

d in i

nf

er

io

r e

nv

iro

nm

en

t s

uc

as

 m

ac

hi

ne

 s

ho

an

et

c.

it 

ca

ca

us

m

al

fu

nc

tio

n.

• 

When installing in small rooms

, take prevention measures not to 

exceed the density limit of refrigerant in the event of leakage

, referred 

by the formula (accordance with ISO5149)

 

If the density of refrigerant exceeds the limit

, please consult the dealer and install the 

ventilation system

, otherwise lack of oxygen can occu

r, which can cause serious accident.

• 

Use the original accessories and the specified components for  installation.

 

If parts other than those prescribed by us are used

, It may cause water leaks

electric shocks

, fire and personal inju

ry

.

• 

Install the unit in a location with good support.

 

Unsuitable installation locations can cause the unit to fall and cause material 

damage and personal inju

ry

.

• 

Ensure the unit is stable when installed

, so that it can withstand 

earthquakes and strong winds.

 

Unsuitable installation locations can cause the unit to fall and cause material 

damage and personal inju

ry

.

• 

Ve

ntila

te

 th

w

or

ki

ng

 a

re

w

ell in

 th

ev

ent

 o

f r

ef

rig

er

an

t l

ea

ka

ge

 d

ur

in

in

stallati

on

.

 

If the refrigerant comes into contact with naked flames

, poisonous gas is produced.

• 

Use the prescribed pipes

, fl

are nuts and tools for R32.

 

Using existing parts (for R22 or R407C) can cause the unit failure and serious 

accidents due to burst of the refrigerant circuit.

• 

Tighten the 

flare nut by to

rque wrench with specified method.

 

If the flare nut were tightened with excess torque

, this may cause burst and 

refrigerant leakage after a long period.

• 

Do not open the se

rvice 

valves for liquid line and gas line until completed 

refrigerant piping work

, air tightness test and e

vacuation.

 

If the compressor is operated in state of opening se

rvice valves before completed 

connection of refrigerant piping work

, you may incur frost bite or inju

ry from an 

abrupt refrigerant outflow and air can be sucked into refrigeran

t circuit

, which can 

cause burst or personal inju

ry due to anomalously high pressure in the refrigerant.

• 

Th

el

ec

tr

ic

al

 in

stalla

tio

m

us

t b

ca

rr

ie

ou

t b

th

qu

al

ifi

ed

 e

le

ct

ric

ia

in

 a

cc

or

da

nc

e wi

th

 “

th

no

rm 

fo

r e

le

ct

ric

al

 w

or

k”

 a

nd

 “

nat

io

na

l w

iri

ng

 

re

gu

lat

io

n”

, a

nd

 th

e sy

st

em 

m

ust

 b

co

nn

ec

te

to

 th

de

di

ca

te

ci

rcu

it.

 

Power supply with insufficient capacity and incorrect function done by improper  work can cause electric shocks and fire.

• 

Be sure to shut off the power before starting electrical work.

 

Failure to shut off the power can cause electric shocks

, unit failure or incorrect 

function of equipment.

• 

Be sure to use the cables conformed to safety standard and cable  ampacity for power distribution work

 

Unconformable cables can cause electric leak

, anomalous heat production or fire

.  

• 

This appliance must be connected to main power supply by means of a circuit breaker or switch (fuse:20A) with a contact separation of at least 3mm

• 

Arrange the wiring in the control box so that it cannot be pushed up  further into the box

. Install the se

rvice panel correctl

y.

 

Incorrect installation may result in overheating and fire.

• 

Use the prescribed cables for electrical connection

, tighten the cables 

securely in terminal block and relieve the cables correctly to prevent  overloading the terminal blocks.

 

Lo

os

co

nn

ec

tio

ns

 o

r c

ab

le

 m

ou

nt

ings

 c

an

 c

au

se

 a

no

m

al

ous 

he

at

 p

ro

du

ct

io

or

 fi

re

.

• 

Be sure to fix up the se

rvice panels.

 

Incorrect fixing can cause electric shocks or fire due to intrusion of dust or wate

r.

• 

Be sure to switch off the power supply in the event of installation

inspection or se

rvicing.

 

If the power supply is not shut off

, there is a risk of electric shocks

, unit failure or 

personal inju

ry due to the unexpected start of fan.

• 

Stop the compressor before rem

oving the pipe after shutting the 

se

rvice 

valve on pump down work.

 

If the pipe is removed when the compressor is in operation with the se

rvice valve 

open

, air would be mixed in the refrigeration circuit and it could cause explosion 

and injuries due to abnormal high pressure in the cooling cycle.

• 

Only use prescribed optional parts

. The installation must be carried out 

by the qualified installe

r.

 

If you install the system by yourself

, it can cause serious trouble such as water 

leaks

, electric shocks

, fire.

• 

Be sure to wear protective goggles and gl

oves while at work.

• 

Earth leakage breaker must be installed.

 

If the earth leakage breaker is not installed

, it can cause electric shocks.

• 

After completed installation

, check that no refrigerant leaks from the 

system.

 

If refrigerant leaks into the room and comes into contact with an oven or other hot 

surface

, poisonous gas is produced.

• 

Hang up the unit at the specified points with ropes which can su

pport the 

weight in lifting for portage

. And to avoid jolting out of alignment

, be sure 

to hang up the unit at 4-point support.

 

An improper manner of portage such as 3-point support can cause death or 

serious personal inju

ry due to falling of the unit.

• 

Consult the dealer or an 

expert regarding rem

ov

al of the unit.

 

Incorrect installation can cause water leaks

, electric shocks or fire.

• 

Do not perform brazing work in the airtight room.

 

It can cause lack of oxygen.

• 

This unit is designed specifically for R32.

 

Using any other refrigerant can cause u

nit failure and personal inju

ry

.

• 

Do not bundling

, winding or processing for the power cord

. O

r, do not 

deforming the power plug due to tread it.

 

This may cause fire or heating.

• 

Do not run the unit with rem

oved panels or protections.

 

Touching rotating equipments

, hot surfaces or high voltage parts can cause 

personal inju

ry due to entrapment

, burn or electric shocks.

• 

Do not perform a

ny change of protective device itself or its setup condition.

 

The forced operation by short-circuiting protective device of pressure switch and 

temperature controller or the use of non specified component can cause fire or burst.

• 

Do not perform a

ny repairs or modifications by yourself

. Consult the dealer 

if the unit requires repai

r.

 

If you repair or modify the unit

, it can cause water leaks

, electric shocks or fire.

• 

Take care when car

rying the unit by hand.

 

If the unit weights more than 20kg

, it must be carried by two or more persons

. Do 

not car

ry by the plastic straps

, always use the car

ry handle when car

rying the unit 

by hand

. Use gloves to minimize the risk of cuts by the aluminum fins.

• 

Dispose of a

ny packing materials correctl

y.

 

Any remaining packing materials can cause personal inju

ry

. T

o avoid danger of 

suffocation

, be sure to keep the plastic wrapper away from children and to 

dispose after tear it up.

 

• 

Be sure to insulate the refrigerant pipes so as not to condense the  ambient air moisture on them.

 

Ins

uf

fic

ie

nt insu

la

tio

ca

ca

us

cond

ens

at

io

n,

 which

 c

an 

le

ad

 to

 mo

is

tu

re

 

da

m

ag

on the 

ce

ili

ng

, fl

oo

r, fu

rniture 

and a

ny

 o

th

er

 v

al

ua

bl

es

.

• 

Be s

ur

to

 p

er

fo

rm air t

ig

ht

ness test 

by 

press

ur

iz

in

w

ith

 n

itr

og

en

 g

as

 

after

 c

om

plet

ed

 refr

ig

eran

t p

ip

in

w

or

k.

 

If the density of refrigerant exceeds the limit in the event of refrigerant leakage in 

the small room

, lack of oxygen can occu

r, which can cause serious accidents.

• 

Do

 no

t i

nstall t

he

 o

ut

do

or 

un

it i

th

e lo

cat

io

ns lis

ted

 b

el

ow

.

 L

oc

at

io

ns

 w

he

re

 discha

rg

ed 

hot

 air o

r o

pe

ra

ting sound 

of

 th

e ou

td

oo

r unit c

an

 

bot

he

r n

eigh

bo

rh

oo

d.

 L

oc

at

io

ns

 w

he

re

 ou

tle

t air

 of

 th

ou

td

oor un

it bl

ow

s dir

ect

ly 

to

 a

ani

m

al 

or

 

pl

an

ts

. Th

ou

tle

t a

ir 

can

 af

fe

ct

 a

dv

er

sel

to

 th

e pl

an

t e

tc

.

 L

oc

at

io

ns

 w

he

re 

vib

rat

ion 

can b

amplified 

and

 tr

ansm

itt

ed due

 to

 insu

ffi

ci

en

st

re

ng

th

 o

f s

tru

ct

ur

e.

 L

oc

at

io

ns wh

er

vib

ra

tio

and op

er

at

io

n sound g

en

er

at

ed b

th

e ou

tdo

or

 un

it 

can 

af

fe

ct

 s

er

io

us

ly (

on

 th

e w

all

 o

r a

t t

he

 pl

ace 

ne

ar

 bed

 ro

om

).

 L

oc

at

io

ns

 w

he

re

 an

 e

quipme

nt

 af

fe

ct

ed by high h

ar

m

onics is p

la

ce

d (TV s

et

 o

ra

dio

 re

ce

ive

r is p

la

ce

w

ithin

 5

m

).

 L

oc

at

io

ns

 w

he

re

 d

ra

in

ag

ca

nn

ot

 run 

of

f s

af

el

y.

 

It ca

af

fe

ct

 sur

ro

undin

en

vir

on

m

en

t a

nd

 c

aus

cl

ai

m

.

• 

Do

 no

t i

nstall 

the

 u

nit 

ne

ar

 th

e l

oc

ati

on

 w

he

re

 le

ak

ag

of

 co

mb

ust

ib

le

 

gase

ca

oc

cu

r.

 

If 

le

aked

 g

ases accumu

la

te a

ro

und 

the un

it,

 it

 c

an

 c

aus

fir

e.

• 

Do

 n

ot install th

uni

t w

her

co

rr

osiv

gas (

su

ch as s

ulf

ur

ous 

ac

id gas 

etc

.) 

or

 c

om

bu

stibl

gas (

su

ch as t

hi

nn

er a

nd

 p

et

ro

le

um

 g

ases) 

ca

n accum

ula

te

 

or

 c

olle

ct

, o

r w

here

 v

olatile 

co

m

bus

tib

le 

su

bst

an

ces are h

an

dl

ed

.

 

Co

rr

os

ive

 g

as

 c

an

 c

au

se

 c

or

ro

si

on

 o

f h

ea

t e

xc

ha

ng

er

, b

re

ak

ag

of

 p

la

st

ic

 p

ar

ts

 

an

et

c.

 A

nd

 c

ombustib

le

 g

as

 c

an ca

us

fir

e.

• 

Do

 no

t i

nstall

 no

r u

se

 th

e syst

em 

clo

se

 to 

the

 equ

ipme

nt 

th

at g

en

er

at

es

 

el

ec

tr

oma

gn

et

ic

 fi

el

ds 

or

 h

ig

h f

re

quen

cy

 h

arm

on

ic

s.

 

Equipme

nt

 such

 a

s i

nv

er

te

rs

, s

tand

by

 ge

ne

ra

to

rs

, medical high

 freque

ncy

 

equipme

nt

s and

 te

le

communic

at

io

equip

m

en

ts can 

aff

ec

t t

he

 s

ys

te

m

, a

nd

 c

au

se

 

m

al

fun

ct

io

ns 

and b

re

akdo

wn

s.

 The sy

ste

m can 

also 

af

fe

ct

 m

edi

cal equipment 

an

te

le

communic

at

io

n equipme

nt

, and

 o

bs

tru

ct

 it

fun

ct

io

or caus

e jammi

ng

.

• 

Se

cur

e a 

sp

ac

e f

or

 in

stallat

ion

, i

ns

pec

tion

 a

nd

 m

ai

nt

en

an

ce

 s

pe

cifi

ed

 in

 

the

 m

anu

al

.

 

In

su

ffi

ci

en

t sp

ac

can 

re

su

lt in accide

nt

 suc

as 

pe

rsonal in

ju

ry

 du

e to

 fa

lling

 fr

om

 

th

e i

ns

ta

llat

io

n pl

ac

e.

 D

no

t install 

th

ou

td

oo

r u

nit in a 

lo

ca

tio

w

he

re i

ns

ects

 a

nd 

sm

al

animals c

an

 in

ha

bi

t.

 

Ins

ec

ts and small an

im

al

can en

te

r the e

le

ct

ric

 p

art

s an

cause damage or

 fi

re

In

st

ru

ct

 th

e us

er

 to

 ke

ep

 the 

su

rro

unding

cl

ea

n.

 D

no

t u

se the base fra

m

fo

r o

ut

do

or

 u

nit

 w

hi

ch

 is

 c

or

ro

de

or

 d

am

ag

ed

 

du

to

 lo

ng

 p

er

io

ds

 o

f o

pe

ra

tio

n.

 

Using an old and da

m

age bas

frame

 c

an

 c

aus

th

e u

ni

t f

alling d

ow

n and c

au

se 

pe

rs

onal in

ju

ry

 D

no

t u

se

 a

ny ma

te

rial

ot

he

r t

ha

n a

 fu

se

 w

ith

 th

co

rr

ect rat

in

g in t

he

 

lo

cat

io

w

he

re

 fu

se

s a

re

 to

 b

us

ed.

 

Conn

ec

ting 

th

ci

rc

ui

t w

ith

 c

op

pe

r wi

re

 o

r o

th

er

 m

et

al

 th

re

ad

 c

an

 c

ause un

it 

fai

lu

re and

 fi

re

.

 D

no

t t

ou

ch

 a

ny

 b

ut

to

ns

 w

ith

 w

et h

an

ds

.

 

It 

ca

cau

se

 el

ec

tric s

ho

cks

.

 D

no

t t

ou

ch

 a

ny

 re

fr

ig

er

an

t p

ip

es

 w

ith

 y

ou

r h

an

ds

 w

he

th

e sys

te

m

 is

 in

 

op

era

tio

n.

 

Du

ring op

er

at

ion

 the 

re

frige

rant pi

pe

s b

ec

ome e

xt

re

mely 

ho

t o

r e

xt

re

m

el

co

ld

 

de

pe

ndin

th

op

er

atin

cond

iti

on

, a

nd i

t c

an

 c

au

se

 burn in

ju

ry

 o

r f

ro

st

 in

ju

ry

.

 Do 

no

t t

ou

ch

 th

e su

ct

io

or al

um

in

um fi

on

 th

ou

td

oo

r u

ni

t.

 

This 

m

ay

 c

ause in

ju

ry

.

 D

no

t p

ut

 a

ny

th

in

on t

he 

ou

td

oo

r u

nit

 a

nd

 o

pe

ra

tin

un

it.

 

This 

m

ay

 c

ause

 d

am

ag

th

ob

je

cts 

or

 in

ju

ry due

 to

 fa

llin

to

 th

ob

je

ct.

 D

no

t u

se

 th

unit

 fo

r s

pe

cial

 p

ur

po

ses 

su

ch as s

to

rin

food

s,

 co

ol

in

pr

ec

is

io

n inst

ru

m

en

ts 

an

pr

es

er

va

tio

of

 a

ni

m

al

s,

 p

la

nt

or 

art

.

 D

no

t c

le

an

 u

th

un

it 

w

ith

 w

at

er

.

 D

no

t s

te

on

to

 th

ou

td

oo

r u

ni

t.

 W

he

th

ou

tdo

or

 u

nit is 

in

stal

le

on 

ro

of

 o

r a 

hi

gh

 p

la

ce

, p

ro

vi

de

 

pe

rma

ne

nt l

ad

de

rs 

an

ha

nd

rails 

al

on

th

ac

ce

ss

 ro

ute

 a

nd

 fe

nc

es

 

ha

nd

rails 

ar

ou

nd

 th

ou

td

oo

r un

it.

Inverter

 driven

 split

 P

AC

90,

 100VNP

Designed

 for

 R32

 refrigerant

a

b

c

d

e

f

g

h

Gauge manifold

Charge hose

Electronic scale for refrigerant charging

Torque wrench

Flare tool

Protrusion control copper pipe gauge

Vacuum pump adapter

Gas leak detector

Dedicated R32 tools

● 

Do not use any refrigerant other than R32.

 R32 will rise to pressure about 1.6 times higher than that of a conventional refrigerant (R22 or 

R407C). A cylinder containing R32 has a lightblue indication mark on the top.

● 

A unit designed for R32 has adopted a different size indoor unit service valve charge port and a different size check joint p

rovided in the unit 

to prevent the charging of a wrong refrigerant by mistake. The processed dimension of the flared part of a refrigerant pipe and a flare nut's parallel side measurement have also been alter

ed to raise 

strength against pressure. Accordingly, you are required to arrange dedicated R32 tools listed in the table on the next page before installing or servicin

g this unit.

● 

All indoor units must be models designed exclusively for R32. Check connectable indoor unit models in a catalog, etc. (A wrong 

in door unit, 

if connected into the system, will impair proper system operation)

Accessories for outdoor unit

• Model name and power source • Refrigerant piping length • Piping, wiring and miscellaneous small parts • Indoor unit installation manual

Grommet (Heat pump type only)

Drain elbow (Heat pump type only)

Reducer set ø9.52    ø6.35

2

1

1

Check before installation work

Q’ty

201907

- 91 -

Summary of Contents for FDE100VNPWVH

Page 1: ...ED AIR CONDITIONERS DATA BOOK CEILINING CASSETTE 4 WAY TYPE FDT90VNPWVH 100VNPWVH DUCT CONNECTED LOW MIDDLE STATIC PRESSURE TYPE FDUM90VNPWVH 100VNPWVH WALL MOUNTED TYPE SRK100VNPWZR DUCT CONNECTED HIGH STATIC PRESSURE TYPE FDU90VNPWVH 100VNPWVH CEILING SUSPENDED TYPE FDE90VNPWVH 100VNPWVH ...

Page 2: ... 147 148 149 150 151 12 7 9 32 1 0 7 0 2 34 26 7 9 21 3 3 3 3 33 12 21 12 17 18 CONTENTS 3 1 SPECIFICATIONS 525 3 2 EXTERIOR DIMENSIONS 537 1 Indoor units 537 2 Outdoor units 537 3 4 NOISE LEVEL 3 7 PIPING SYSTEM 3 6 TEMPERATURE AND VELOCITY DISTRIBUTION 3 3 ELECTRICAL WIRING 540 3 8 RANGE OF USAGE LIMITATIONS 1 Indoor units 540 2 Outdoor units 540 3 Remote control Option parts 539 3 9 SELECTION C...

Page 3: ...eiling cassette 4 way type FDT 2 Duct connected Low Middle static pressure type FDUM 7 1 Duct connected High static pressure type FDU 6 3 Remote control Option parts 3 ELECTRICAL WIRING 4 NOISE LEVEL 3 5 CHARACTERISTICS OF FAN 6 TEMPERATURE AND VELOCITY DISTRIBUTION 8 7 PIPING SYSTEM 30 8 RANGE OF USAGE LIMITATIONS 32 1 Indoor units 2 Outdoor units 2 1 Indoor units 3 2 Outdoor units 5 9 2 Correcti...

Page 4: ...er sleeve for fan motor compressor Electric heater W Operation control Remote control Option Wired RC EX3A RC E5 RCH E3 Wireless RCN T 5AW E2 Room temperature control Thermostat by electronics Operation display Safety equipments Compressor overheat protection Overcurrent protection Frost protection Serial signal error protection Indoor fan motor error protection Heating overload protection High pr...

Page 5: ...ber sleeve for fan motor Rubber sleeve for fan motor compressor Electric heater W Operation control Remote control Option Wired RC EX3A RC E5 RCH E3 Wireless RCN T 5AW E2 Room temperature control Thermostat by electronics Operation display Safety equipments Compressor overheat protection Overcurrent protection Frost protection Serial signal error protection Indoor fan motor error protection Heatin...

Page 6: ...y Safety equipments Compressor overheat protection Overcurrent protection Frost protection Serial signal error protection Indoor fan motor error protection Heating overload protection High pressure control Cooling overload protection Installation data Refrigerant piping size O D Liquid line mm I U φ9 52 3 8 Pipe φ6 35 1 4 x0 8 O U φ6 35 1 4 Gas line φ15 88 5 8 Pipe φ15 88 5 8 x1 0 φ15 88 5 8 Conne...

Page 7: ...lectronics Operation display Safety equipments Compressor overheat protection Overcurrent protection Frost protection Serial signal error protection Indoor fan motor error protection Heating overload protection High pressure control Cooling overload protection Installation data Refrigerant piping size O D Liquid line mm I U φ9 52 3 8 Pipe φ6 35 1 4 x0 8 O U φ6 35 1 4 Gas line φ15 88 5 8 Pipe φ15 8...

Page 8: ...electronics Operation display Safety equipments Compressor overheat protection Overcurrent protection Frost protection Serial signal error protection Indoor fan motor error protection Heating overload protection High pressure control Cooling overload protection Installation data Refrigerant piping size O D Liquid line mm I U φ9 52 3 8 Pipe φ6 35 1 4 x0 8 O U φ6 35 1 4 Gas line φ15 88 5 8 Pipe φ15 ...

Page 9: ...perature control Thermostat by electronics Operation display Safety equipments Compressor overheat protection Overcurrent protection Frost protection Serial signal error protection Indoor fan motor error protection Heating overload protection High pressure control Cooling overload protection Installation data Refrigerant piping size O D Liquid line mm I U φ9 52 3 8 Pipe φ6 35 1 4 x0 8 O U φ6 35 1 ...

Page 10: ... for fan motor Rubber sleeve for fan motor compressor Electric heater W Operation control Remote control Option Wired RC EX3A RC E5 RCH E3 Wireless RCN E E3 Room temperature control Thermostat by electronics Operation display Safety equipments Compressor overheat protection Overcurrent protection Frost protection Serial signal error protection Indoor fan motor error protection Heating overload pro...

Page 11: ...tor Rubber sleeve for fan motor compressor Electric heater W Operation control Remote control Option Wired RC EX3A RC E5 RCH E3 Wireless RCN E E3 Room temperature control Thermostat by electronics Operation display Safety equipments Compressor overheat protection Overcurrent protection Frost protection Serial signal error protection Indoor fan motor error protection Heating overload protection Hig...

Page 12: ...tion absorber Rubber sleeve for fan motor Rubber sleeve for fan motor compressor Electric heater W Operation control Remote control Option Wired RC EX3A RC E5 RCH E3 Interface kit SC BIKN2 E Room temperature control Thermostat by electronics Operation display RUN Green TIMER Yellow HI POWER Green 3D AUTO Orange Safety equipments Compressor overheat protection Overcurrent protection Frost protectio...

Page 13: ... 35 215ー245 850 or less 140 100 100 60 140 140 6 φ4 140 100 130 240 140 6 φ4 200 76 112 137 129 50 38 99 40 65 5 φ4 167 44 13 H1 2 G H1 2 H1 2 B A F C H1 H2 H1 2 D G Unit mm A Gas piping φ15 88 5 8 Flare B Liquid piping φ9 52 3 8 Flare C Drain piping VP25 O D 32 D Hole for wiring F Suspension bolts M10 or M8 G Space for installation and service Obstacle H1 2 G H1 2 H1 2 Drain hose piece B A F C Ma...

Page 14: ... more Case 2 From bottom of unit Notes a There must not be obstacle to draw out 2 fan units For fan units maintenance refer to page 54 b Install refrigerant pipes drain pipe and wiring so as not to cross marked area c The case that pipes are installed to upper bottom of fan unit keep space of 60mm or more to upper bottom of unit C1 Drain piping VP25 O D 32 VP20 Unit mm 4 φ4 Suspension bolts pitch ...

Page 15: ...he model name label ࠉࠉis attached on the lid ࠉࠉ of the control box Notes a There must not be obstacle to draw out 2 fan units For fan units maintenance refer to page 60 b Install refrigerant pipes drain pipe and wiring so as not to cross marked area c The case that pipes are installed to upper bottom of fan unit keep space of 60mm or more to upper bottom of unit C1 Drain piping VP25 O D 32 VP20 Un...

Page 16: ... 19 PAC DB 333 d Ceiling suspended type FDE Model FDE100VH PFA004Z086 15 C 1 C 2 C 1 C 2 C 2 C 1 A E G F A B B D ...

Page 17: ...ce when viewing from the front 768 157 48 240 6 7 322 4 214 5 214 5 883 157 10 3 262 19 64 55 47 53 77 47 1197 339 150 50 Space for service Space for service Space for service 15 100 780 715 759 55 Installation board Outlet for downward piping Refer to the top view Terminal block 60 240 43 470 363 5 363 5 568 5 568 5 11 60 Unit mm Notes 1 The model name label is attached on the underside of the in...

Page 18: ...hat the blower outlet faces perpendicularly to the dominant wind direction 4 Leave 1m or more space above the unit 5 A wall in front of the blower outlet must not exceed the unit s height 6 The model name label is attached on the lower right corner Minimum installation space D C E Symbol Content A Service valve connection gas side φ15 88 5 8 Flare B Service valve connection liquid side φ6 35 1 4 F...

Page 19: ...remote control Where the average room temperature cannot be detected Place near the equipment to generate heat Place affected by outside air in opening closing the door Place exposed to direct sunlight or wind from air conditioner Where the difference between wall and room temperature is large 4 When you are using the automatic grille up and down panel in the IU you may not be able to confirm the ...

Page 20: ...cores Under 300m Under 400m Under 600m Upper part Lower part Lower case Sheath Upper cace Board Wiring Upper Lower X Y Sheath Upper cace Board Wiring Upper Lower Y X Tighten the screws after cutting off the thin part of screw mounting part Embedded mounting The peeling off length of sheath The peeling off length of sheath In case of pulling out from upper left In case of pulling out from upper lef...

Page 21: ... 19 PAC DB 333 b Wireless remote control RCN E2 Option parts Except SRK series 60 24 167 3 Remote control Unit mm 60 24 167 SRK series only 20 Unit mm Unit mm ...

Page 22: ...5 1 2 3 4 5 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 BK BK BK BK BK BK BK BK BK BL RD BR OR WH YE GN RD 12 12 12 3 Power source line Signal line 1 2 3 CNW3 WH 1 3 WH BL 2 0A 3 15A WH YE GN PIS WHWHWHWHWHWHWHWHWHWHBL BL BL BL BL BL BL BL BL BL RD RD RD RD RD RD RD RD RD RD SW2 1 BK BK BK BK BK RD WH E1 Indoor unit PCB 1 2 Option Remote operation input volt free contact The line between in...

Page 23: ... FMi1 2 FS Float switch Indication lamp Red Inspection Indication lamp Green Normal operation LED 3 LED 2 Connector CNB Z Model capacity setting SW6 Operation check drain pump motor test run SW7 1 SW5 Temperature sensor Remote control Temperature sensor Heat exchanger Temperature sensor Return air Thc Thi R1 2 3 TB2 Terminal block Signal line mark TB1 Terminal block Power source mark Remote contro...

Page 24: ...Power source line Signal line indoor unit and outdoor unit M 1 4 5 6 7 F4 2A CNM2 BK RD BL or BK BR or WH WH or BL OR or YE BL 3 1 WH CNW3 WH 1 2 WH RD YE GN 3 5 CNW0 WH 1 3 TB1 F1 5A YE GN M 1 4 5 6 7 RD F3 2A CNM1 WH BL or BK BR or WH WH or BL OR or YE L CNWR WH 1 3 1 2 CNTA BL Remote operation input volt free contact 12 Prepare on site XR5 Remote operation input volt free contact Thi R1 2 3 FMi...

Page 25: ...4 15 16 17 18 19 20 CNJ WH BL PK BR OR RD 12 1 PIS CNG BL CNV2 BK 2 4 3 1 3 Option WH BK RD WH RD BK WH RD BK WH RD BK CNL1 WH CNL2 WH Prepare on site CNZ CNC For HA WH RD SW2 SW6 SW5 SW7 LED 2 LED 3 SW8 1 5 Section 1 1 shows electric circuit of motion sensor Option Notes 1 indicates wiring on site 2 See the wiring diagram of outdoor unit about the line between indoor unit and outdoor unit 3 Use t...

Page 26: ...CIRCUIT PRINTED SM 1 LM 1 CNX M M M 5 5 LM 2 RD WH RD WH BK BL Y Y G BK CNG CNE DISPLAY WIRELESS RECEIVER CNF BACK UP SW 2 8 Th2 1 Th2 2 Th1 Th3 CNY Y G CNM 5 Color Marks Blue Black BK Red BL RD White WH Yellow Green Y G Yellow Y Color Mark Heat exchanger temperature sensor Humidity sensor Fan motor Room temperature sensor Flap motor Th1 Th2 1 2 Th3 Diode stack DS Fuse F Connector CNE FMi Terminal...

Page 27: ...mm x 4 90 100 3 1 2 N 1 Phase 220 230 240V 50Hz 1 5 Color RD Mark Orange OR Yellow Green YG Black BK Brown BR Yellow YE White WH Red Description Item Connector CN20S Electric expansion valve coil EEV Fan motor FMo Reactor L Terminal block TB1 2 Compressor motor CM Solenoid coil for 4 way valve 20S Heat exchanger temperature sensor outdoor unit TH1 Outdoor air temperature sensor TH2 TH3 Discharge p...

Page 28: ...odel FDT50VH 63 125 250 500 1000 2000 4000 8000 30 40 50 60 70 80 30 40 50 60 70 80 Cooling Heating Mid Octave Band Frequency Hz Mid Octave Band Frequency Hz Mid Octave Band Frequency Hz Sound power level dB Sound power level dB Model FDT60VH 63 125 250 500 1000 2000 4000 8000 20 10 30 40 50 60 20 10 30 40 50 60 N30 N40 N20 N50 N60 Mid Octave Band Frequency Hz Sound pressure level dB Standard 2 10...

Page 29: ...Hi 37 dB A at Me 32 dB A at Lo 63 125 250 500 1000 2000 4000 8000 20 10 30 40 50 60 20 10 30 40 50 60 N30 N40 N20 N50 N60 Sound pressure level dB Standard 2 10 5 Pa Mid Octave Band Frequency Hz Model FDE100VH Noise level 48 dB A at P Hi 43 dB A at Hi 38 dB A at Me 34 dB A at Lo 63 125 250 500 1000 2000 4000 8000 20 10 30 40 50 60 20 10 30 40 50 60 N30 N40 N20 N50 N60 Sound pressure level dB Standa...

Page 30: ...ng Heating Mid Octave Band Frequency Hz Sound pressure level dB standard 2 10 5 Pa 63 125 250 500 1000 2000 4000 8000 20 10 30 40 50 60 20 10 30 40 50 60 N30 N40 N20 N50 N60 Cooling Heating Mid Octave Band Frequency Hz Sound pressure level dB standard 2 10 5 Pa Heating noise level Hi 46 dB A Heating noise level Hi 46 dB A Heating noise level Hi 48 dB A Cooling noise level Hi 48 dB A Model SRK100ZR...

Page 31: ... 35 36 36 40 45 Air flow m3 min External static pressure Pa 0 20 40 60 80 100 120 140 160 180 200 220 10 15 20 25 30 35 40 45 Air flow m3 min External static pressure Pa Range of approvable air flow In case actual E S P correspond setting of E S P 0 20 40 60 80 100 120 140 160 180 200 220 32 33 34 35 36 38 39 40 37 Air flow m3 min External static pressure Pa SW8 4 OFF Range of use limitation Setti...

Page 32: ...a Setting 10Pa 100Pa Max 90Pa 80Pa 70Pa 60Pa 50Pa 40Pa 30Pa 20Pa 10Pa Min Lo Me Setting 40Pa Setting 10Pa Characteristic FAN 2 Characteristic FAN 1 Model FDUM100VH Air flow m3 min External static p 0 10 20 30 40 50 10 14 18 22 26 0 10 20 30 40 50 21 22 23 24 25 26 27 External static pr Air flow m3 min 20Pa 10Pa Min 0 10 20 30 40 50 60 70 80 90 100 16 20 24 28 32 36 40 44 Air flow m3 min External s...

Page 33: ... and obstacles 1 Ceiling cassette 4 way type FDT Model FDT100VH Cooling Air flow P Hi Louver position Temperature distribution 24 21 18 15 24 21 18 15 5m 4m 3m 2m 1m 0m 5m 4m 3m 2m 1m 0m 5m 4m 3m 2m 1m 0m 1m 2m 3m 4m 5m 20 Velocity distribution 0 3 0 6 0 3 0 6 5m 4m 3m 2m 1m 0m 5m 4m 3m 2m 1m 0m 5m 4m 3m 2m 1m 0m 1m 2m 3m 4m 5m m sec Heating Air flow P Hi Louver position Temperature distribution 2...

Page 34: ... Velocity distribution Velocity distribution 4m 3m 2m 1m 0m 8m 7m 5m 6m 0m 1m 2m 3m 3m 2m 1m 0m 15 18 21 24 m sec m sec 4m 3m 2m 1m 0m 8m 7m 5m 6m 0m 1m 2m 3m 3m 2m 1m 0m 2 0 1 5 1 0 0 5 35 32 29 26 23 4m 3m 2m 1m 0m 8m 7m 5m 6m 0m 1m 2m 3m 3m 2m 1m 0m 2 0 1 5 1 0 0 5 4m 3m 2m 1m 0m 8m 7m 5m 6m 0m 1m 2m 3m 3m 2m 1m 0m 5 45 Louver position Louver position ...

Page 35: ...y 7 PIPING SYSTEM Preset point of the protective devices Parts name Mark Equipped unit FDT FDU FDUM FDE series Temperature sensor for protection overloading in heating Thi R1 or Thi R2 Indoor unit OFF 63 ON 56 Temperature sensor for frost prevention OFF 1 0 ON 10 Temperature sensor for protection high pressure in cooling TH1 Outdoor unit OFF 63 ON 50 Temperature sensor for detecting discharge pipe...

Page 36: ... sensor Preset point of the protective devices Parts name Mark Equipped unit SRK series Temperature sensor for protection overloading in heating Th21 or Th22 Indoor unit OFF 51 5 58 ON 48 5 Temperature sensor for frost prevention OFF 2 5 ON 8 Temperature sensor for protection high pressure in cooling TH1 Outdoor unit OFF 63 ON 50 Temperature sensor for detecting discharge pipe temperature TH3 OFF ...

Page 37: ...iquid pipes need to be coverd with 20mm or thicker heat insulation materials at the place where humidity exceeds 70 8 RANGE OF USAGE LIMITATIONS Operating temperature range See next page When used below 5 C install a snow hood prepared on site Recommendable area to install Considering to get sufficient heating capacity the area where the averaged lowest ambient air temperature in day time during w...

Page 38: ... cooling operation may not be established for any given time 32 Usage range in heating 19 PAC DB 311D 5 10 15 20 25 30 20 15 10 5 0 5 10 15 20 25 20 10 0 10 20 30 40 50 10 12 14 16 18 20 22 24 26 Operating temperature range Cooling Heating Decline in cooling and heating capacity or operation stop may occur when the outdoor unit is installed in places where natural wind can increase or decrease its...

Page 39: ... 19 PAC DB 333 Limitation on unit and piping installation PJF000Z317 PCA001Z871 FDC90 100VNP W PCA001Z871 38 ...

Page 40: ... 26 DB 27 DB 28 DB 31 DB 33 DB 12 WB 14 WB 16 WB 18 WB 19 WB 20 WB 22 WB 24 WB 16 18 20 22 24 14 5 15 5 46 5 40 5 33 5 26 5 18 11 13 5 14 5 68 5 61 5 54 5 47 5 39 13 11 5 12 6 10 6 03 5 96 5 88 5 81 15 9 5 10 6 52 6 45 6 38 6 30 6 22 17 7 5 8 6 95 6 87 6 79 6 71 6 63 19 5 5 6 7 39 7 32 7 25 7 16 7 07 21 3 0 4 7 84 7 77 7 70 7 61 7 51 23 1 0 2 8 29 8 22 8 15 8 05 7 95 25 1 0 0 8 74 8 67 8 60 8 50 8...

Page 41: ... 64 6 57 6 49 6 41 6 33 21 3 0 4 7 05 6 97 6 89 6 80 6 72 23 1 0 2 7 45 7 37 7 29 7 20 7 10 25 1 0 0 7 86 7 77 7 68 7 59 7 49 27 2 0 1 8 06 7 97 7 88 7 78 7 68 29 3 0 2 8 26 8 18 8 11 8 01 7 91 31 5 0 4 8 64 8 60 8 55 8 46 8 37 33 7 0 6 9 03 9 02 9 00 8 91 8 82 35 9 0 8 9 50 9 46 9 41 9 37 9 32 37 11 5 10 9 97 9 90 9 82 9 82 9 82 39 13 5 12 10 39 10 38 10 36 10 35 10 35 41 15 5 14 10 82 10 86 10 8...

Page 42: ...2 5 94 19 5 5 6 6 64 6 57 6 49 6 41 6 33 21 3 0 4 7 05 6 97 6 89 6 80 6 72 23 1 0 2 7 45 7 37 7 29 7 20 7 10 25 1 0 0 7 86 7 77 7 68 7 59 7 49 27 2 0 1 8 06 7 97 7 88 7 78 7 68 29 3 0 2 8 26 8 18 8 11 8 01 7 91 31 5 0 4 8 64 8 60 8 55 8 46 8 37 33 7 0 6 9 03 9 02 9 00 8 91 8 82 35 9 0 8 9 50 9 46 9 41 9 37 9 32 37 11 5 10 9 97 9 90 9 82 9 82 9 82 39 13 5 12 10 39 10 38 10 36 10 35 10 35 41 15 5 14...

Page 43: ...80 6 72 23 1 0 2 7 45 7 37 7 29 7 20 7 10 25 1 0 0 7 86 7 77 7 68 7 59 7 49 27 2 0 1 8 06 7 97 7 88 7 78 7 68 29 3 0 2 8 26 8 18 8 11 8 01 7 91 31 5 0 4 8 64 8 60 8 55 8 46 8 37 33 7 0 6 9 03 9 02 9 00 8 91 8 82 35 9 0 8 9 50 9 46 9 41 9 37 9 32 37 11 5 10 9 97 9 90 9 82 9 82 9 82 39 13 5 12 10 39 10 38 10 36 10 35 10 35 41 15 5 14 10 82 10 86 10 89 10 88 10 87 43 16 5 16 11 24 11 34 11 43 11 41 1...

Page 44: ...10 56 7 63 10 88 7 58 11 52 7 94 12 16 7 79 7 5 8 8 93 8 89 8 85 8 80 8 75 23 9 65 7 19 10 28 7 70 10 59 7 65 10 91 7 59 11 56 7 95 12 21 7 81 5 5 6 9 05 9 00 8 97 8 91 8 86 25 8 93 7 28 9 64 7 19 10 31 7 71 10 62 7 66 10 95 7 61 11 61 7 97 12 27 7 83 3 0 4 9 17 9 12 9 07 9 03 8 97 27 8 86 7 25 9 64 7 19 10 34 7 72 10 65 7 67 10 96 7 61 11 57 7 95 1 0 2 9 29 9 23 9 19 9 13 9 07 29 8 80 7 22 9 50 7...

Page 45: ...rature DB 20 10 0 10 20 30 40 50 Indoor air temperature DB 15 Capacity compensation coeffcient 0 0 5 1 0 1 5 5 10 20 25 30 35 Indoor air temperature 24 WB Indoor air temperature 19 WB Indoor air temperature 12 WB Indoor air temperature 15 WB Indoor air temperature 17 WB Outdoor air temperature 10 WB Outdoor air temperature 15 WB Outdoor air temperature 18 WB Outdoor air temperature 1 WB Outdoor ai...

Page 46: ...rature 1 WB Outdoor air temperature 15 WB Outdoor air temperature 10 WB 45 II Model FDC100VNP W Cooling Heating Capacity compensation coeffcient 0 0 5 1 0 1 5 Outdoor air temperature DB 20 10 0 10 20 30 40 50 Indoor air temperature DB 15 Capacity compensation coeffcient 0 0 5 1 0 1 5 5 10 20 25 30 35 Indoor air temperature 24 WB Indoor air temperature 19 WB Indoor air temperature 12 WB Indoor air ...

Page 47: ...the cooling and heating capacity Net cooling capacity 9 0 1 00 0 97 0 99 8 6 kW Example The net cooling capacity of the model FDT90VNPWVH with the air flow P Hi the piping length of 15m the outdoor unit located 5m lower than the indoor unit indoor wet bulb temperature at 19 0 and outdoor dry bulb temperature 35 is Net cooling total capacity of FDT90VNPWVH Outdoor temp 35 DB Indoor temp 19 WB shown...

Page 48: ...aker is not installed it can cause electric shocks Use the circuit breaker of correct capacity Circuit breaker should be the one that disconnect all poles under over current Using the incorrect one could cause the system failure and fire Do not use any materials other than a fuse of correct capacity where a fuse should be used Connecting the circuit by wire or copper wire could cause unit failure ...

Page 49: ...ause condensation and leakage of water It is possible to set the air flow direction port by port independently Refer to the user s manual for details Preparation before installation Ceiling opening Suspension bolts pitch Pipe position Installation of indoor unit Work procedure 1 Set the suspension bolt length to about 50 mm from the ceiling 2 Temporarily locate the lower nuts of the suspension bol...

Page 50: ...drain After checking the pipe must be perf If the pipe lid has The position for drain 850mm above the ce tion to avoid obstacles tal drain pipe is too backflow of water w stopped and it may c the drain pan on the overflow keep the ho of the pipe within th below Drain test Drain pump operation Drain up 1 Remove the flare nut and blind flanges on the pipe of the indoor unit Makesuretoloosentheflaren...

Page 51: ...n them to the terminal block 5 Fix the wiring using clamps 6 Install the wiring cover and the lid of the control box Main fuse specification Specification T3 15A L250V Part No SSA564A149AF Panel installation Install the panel on the indoor unit after electrical wiring work Refer to the attached manual for panel installation for details How to check the dirt of drain pan and cleanimg the inlet of t...

Page 52: ...otor cable 2 3 Pass the anti draft motor ca 4 Fix the control box lid of the Hook of the contr Hook of the contro Pass through hole of The wiring work varies depend The connection positions of th For the Standard pan 1 Loosen 2 screws on the 2 Pass the flap motor wiri 3 Fix the control box lid o Accessories holding position Removal Stopper Coner lid Pull up around this part as shown in the picture...

Page 53: ...el type For the Standard panel 1 Loosen 2 screws on the control box lid of the indoor unit and remove the lid by sliding it 2 Pass the flap motor wiring 20 wire through the hook of the control box and connect to CnJ1 20P white 3 Fix the control box lid of the indoor unit and tighten 2 screws Closing direction Position for hanging hinges A a Pin Screw Installing the inlet grille Panel setting Flap ...

Page 54: ...TION CAUTION This model is high static blow type air conditionin Before insta Install correctly acc Confirm the followi Unit type Power Accessory item Case 2 Case 1 In h Note a Inspectio hole 450x45 Space for installation For refrigera Pipe cover big Pipe cov small 1 1 For heat insulation of gas pipe For heat insu of liquid tube For hanging Flat washer M10 8 For unit hanging PJG012D022 Perform ear...

Page 55: ...urce specification Pipes Wires Small parts Accessory items Accessory item Single type Multi type FDU F A B Size of inspection hole 45 56 1100 71 71 90 650 1300 100 140 112 160 1100 1720 725 For natural drainage Drain pipe connection VP20 PVC pipe Drain pipe connection PVC pipe Drain hose VP25 510 635 468 405 467 187 145 95 29 471 413 203 174 104 29 467 Refrigerant liquid pipe Refrigerant gas pipe ...

Page 56: ... specific blowout duct in a location where the air will circulate to the entire room Conduct the installation of the specific blowout hole and the connection of the duct before attaching them to the ceiling Insulate the area where the duct is secured by a band for dew condensation prevention Make sure provide an inspection hole on the ceiling It is indispensable to service electric equipment motor...

Page 57: ...cause over pressure and resultant it may result in bursting etc Store the copper pipes indoors and seal the both end of them until they are brazed in order to avoid any dust dirt or water getting into pipe Otherwise it will cause degradation of refrigeration oil and compressor breakdown etc Use special tools for R32 or R410A refrigerant 1 Remove the flare nut and blind flanges on the pipe of the i...

Page 58: ...hould not be used when actual E S P cannot be confirmed because the risk above becomes higher If 20 is selected for the setting No on the remote control the setting No shows No 19 You can not set E S P by wireless remote control How to set E S P by wired remote control Push marked button E S P button Select indoor unit No by using button Select setting No by using button and set E S P by button Se...

Page 59: ...unit located at the far side Screw iv Take out the fan unit in the arrow direction b Replacement procedure of the fan unit Model FDU100VH c Replacement procedure of the fan unit Notes 1 The unit is a heavy item It must be supported securely and handled with care not to drop when it is necessary to replace 2 For the maintenance space refer to page 54 i Remove the control box and the side panel and ...

Page 60: ...anger breakage of plastic parts etc And inflammable gas could cause fire Secure a space for installation inspection and maintenance specified in the manual Insufficient space can result in accident such as personal injury due to falling from the installation place Do not use the indoor unit at the place where water splashes such as laundry Indoor unit is not waterproof It could cause electric shoc...

Page 61: ...out fan motor marked area b Install refrigerant pipe drain pipe and wiring so as not to cross marked area If suspension bolt becomes longer do reinforcement of earthquake resistant For grid ceiling When the suspension bolt length is over 500mm or the gap between the ceiling and roof is over 700mm apply earthquake resistant brace to the bolt In case the unit is hanged directly from the slab and is ...

Page 62: ...nt 4 Refrigerant is cha As for the additio manual attached Caution Refrigerating mach is because even if force on the thread by the stress corro Refrigerating mach Be sure to use new pipes for the refrigerant pipes Use the flare nut attached to the product Regarding whether existing pipes can be reused or not and the washing method refer to the instruction manual of the outdoor unit catalogue or t...

Page 63: ...rease in turn the axial component force so that it could crack the flare by the stress corrosion Refrigerating machine oil may be applied to the internal surface of flare only Descending slope greater than 1 100 As wide as possible about100mm Supporting metal Descending slope greater than 1 100 Please confirm that the pipe doesn t bend Air vent No bump No trap Not touching the water Trapped air wi...

Page 64: ...either method of MANUAL SETTING or AUTO MATIC SETTING by remote control Indoor unit will control fan speed to keep rated air flow volume at each fan speed setting Lo Uhi 1 MANUAL SETTING You can set required E S P by wired remote control that calculated with the set air flow rate and pressure loss of the duct connected Select No 1 10 10Pa 100Pa from following table according to calculation result ...

Page 65: ...les 2 places from the fan unit located at the far side iv Take out the fan unit in the arrow direction Screw 2 Take out the fan unit in the arrow direction Side panel Screw Control box Side panel Screw 2 Take out the fan unit in the arrow direction Side panel Screw Control box Side panel Screw Control box 2 Take out the fan unit located at the near side in the arrow Side panel Screw direction Scre...

Page 66: ...ral ind other more than CAUTION Perform earth wiring surely Do not connect the earth wiring to the gas pipe water pipe lightning rod and telephone earth wiring Improper earth could cause unit failure electric shock and fire due to a short circuit Earth leakage breaker must be installed If the earth leakage breaker is not installed it can cause fire and electric shocks Use the circuit breaker of co...

Page 67: ...on the left and right sides CAUTION Do not give the reversed slope which may cause water leaks WARNING CAUTION Completely seal the hole in the wall with putty If not sealed properly dust insects small animals and highly humid air may enter the room from outside which could result in fire or other hazards Completely seal the hole in the wall with putty If not sealed properly furniture and other fix...

Page 68: ...wisting of the copper pipe When fastening the flare nut align the refrigeration pipe with the center of flare nut screw the nut for 3 4 times by hand and then tighten it by spanner with the specified torque mentioned in the table above 3 Cover the flare connection part of the indoor unit with attached insulation material after a gas leakage inspection and tighten both ends with attached straps Mak...

Page 69: ... control box Screw Screw Screw Screw Bracket The control content of indoor units can be switched in following way is the default setting Check if Expected trouble Check Falling vibration noise Inspection for leakage is done Insulation work is properly done Water leakage Water is drained properly Water leakage Power source voltage is same as mentioned in the model name plate PCB burnt out not worki...

Page 70: ...onal flare tool Pipe cutter Designed specifically for R32 or R410A RLD012A018 indd 1 RLD012A018 A 2 SELEC After getting cust 1 Indoor uni Where there is distributed A solid place wh A place where t can be secured Where it is easy A place where u A place where i A place separat ages and sound A place where t Avoid installing A place where t Install the indoo 180 cm 2 Remote co A place where t A pla...

Page 71: ...parts 5 ø65 Indoor side Outdoor side a Sleeve Top Thickness of the wall 1 5cm Cut Indoor side Outdoor side Installed state Turn to tighten b Sealing plate a Sleeve c Inclination plate d Putty d Putty Outdoor side Indoor side 1 Drill a hole with hole core drill 5 ELECTRICAL WIRING WORK Before installation make sure that the power source complies with the air conditioner s power speci fication Carry...

Page 72: ...er diameter B Rigid clutch type R32 or R410A Conventional 5 3 6 ø 1 9 5 3 6 ø 0 0 5 1 0 1 5 2 5 9 ø 2 3 1 2 5 9 ø 7 2 1 ø 6 6 1 7 2 1 ø 8 8 5 1 ø 7 9 1 8 8 5 1 ø 2 2 Connecting pipes 1 Connect pipes on both liquid and gas sides 2 Tighten nuts to specified torque shown in the table below Do not turn Liquid side Gas side Operation valve size mm Tightening torque N m ø6 35 1 4 14 18 ø9 52 3 8 34 42 ø...

Page 73: ...se two air conditioners are installed in the same room apply this setting so that one unit can be operated with only one remote control For the environmental protection be sure to pump down when relocating or disposing of the unit Pump down is the method of recovering refrigerant from the indoor unit to the outdoor unit before the connect ing pipes are removed from the unit When pump down is carri...

Page 74: ...le shows reference values in case of four outlet If you shut some outlets they are different Fan speed setting can be changed by using a wired remote control b FDE series Model Effective range FDE100VH 9 0m Conditions 1 Height of unit 2 4 3 0 m above floor level 2 Fan speed Hi 3 Location Free space without obstacles 4 The effective range means the horizontal distance for wind to reach the floor 5 ...

Page 75: ...g in the re outside of the case wire connecting se 100 200m Under 300m Under 400m Under 600m Switch No SW2 SW5 1 SW5 2 SW6 1 4 SW7 1 Control Content Indoor unit address 0 Fh Master Slave Switching plural Slave unit Setting Model capacity setting ON Operation check Drain motor test run OFF Normal operation The control content of indoor units can be switched in following way is the default setting N...

Page 76: ...XR5 Common Output 1 Output 2 Output 3 Output 4 Remote ON OFF switch or timer contactor AC100V DC12V DC24V Input 1 XR6 AC100V 200V DC12V DC24V Input 2 Note 1 0 3 mm2 2 m Note 1 0 3 mm2 2 m Note 1 To be no longer than 2 m 0 75mm2 0 2 m Butt connecting contactor Red Black Yellow Blue Brown Orange Remote ON OFF monitor kit Applicable range 0 75 1 25 mm2 XR5 XR6 White Black Yellow Blue Brown Orange Ora...

Page 77: ...r in winter The judgment to switch the operation mode Cooring Heating is done by the both factors of the set temp and outdoor air temp The set temp and fan speed can be set A 7 External Ventilation When the ventilator is combined On Off operation of the external ventilator can be done It is necessary to set from Menu Service setting R C function settings Ventilation setting If the Independent is s...

Page 78: ...temp setting Enable or Disable of Auto temp setting can be selected B Auto fan speed Enable or Disable of Auto fan speed can be selected B 3 IU settings Fan speed setting The fan speed for indoor units can be set B Filter sign The setting of filter sign display timer can be done from following patterns B Service password External input 1 The connect of control by external input 1 can be changed B ...

Page 79: ...ng the unit Repairing inspecting the unit with the power circuit breaker turned ON could cause electric shocks or injury Please read this manual carefully before starting installation work to install the unit properly Every one of the followings is important information to be observed strictly WARNING Failure to follow these instructions properly may result in serious consequences such as death se...

Page 80: ... shocks Do not wash the unit with water Use the specified cables for wiring and connect them securely with care to protect electronic parts from external forces etc y t t u p h t i w e l b a c l o r t n o c e t o m e r r o f e l o h t e l n i e h t l a e S break down If dew or water enters the unit it may cause screen display anomalies When installing the unit at a hospital telecommunication facili...

Page 81: ...ote control gets wet e h t f o r o s n e s e r u t a r e p m e t e h t g n i s u d e t c e t e d e b t o n y a m e r u t a r e p m e t m o o r e t a r u c c A 3 remote control Where the average room temperature cannot be detected Place near the equipment to generate heat Place affected by outside air in opening closing the door Place exposed to direct sunlight or wind from air conditioner Where th...

Page 82: ... Quick reference When the cable length is longer than 100 m the max size for wires used in the R C case is 0 5 mm2 Connect them to wires of larger size near the outside of R C When wires are connected take measures to prevent water etc from entering inside 200 m 0 5 mm2 x 2 cores 300m 0 75 mm2 x 2 cores 400m 1 25 mm2 x 2 cores 600m 2 0 mm2 x 2 cores For the installation method embedding wiring or ...

Page 83: ...d from front 37 23 23 固定穴 18 3 83 5 120 19 120 37 23 23 19 120 Fixing holes 83 5 120 18 3 PCB side Viewed from rear 8 50 200 壁 電線管 ロ ッ クナッ ト スイ ッ チ ボ ッ クス パテで シール する こ と リ モコ ン配線 下ケース配線穴 ブッ シング センサー USB 端子 Wall Conduit Sensor USB port Terminal block Locknut Bushing Switch box Seal with putty R C cable se at 2 places on the switch box Switch box for 1 pcs Switch box for 2 pcs 配線取出口 下 上 下ケース 下 上 下ケー...

Page 84: ...ugh the remote control case Take care not to pinch the sheath T If the wire is connected using an electric driver it may cause failure or deformation In case of exposing wiring When the wiring is taken out from the upper center or upper left of R C Cut out the thin wall sections on the cases for the size of wire screws In case of the upper center pass the wiring behind the bottom case Hatched sect...

Page 85: ...ata Error display Error history Display erase anomaly data Reset periodical check Saving IU settings Special settings Erase IU address CPU reset Restore of default setting Touch panel calibration Indoor unit capacity display Indoor unit R C Main R C Sub R C cable No polarity Advice Connection to personal computer It can be set from a personal computer via the USB port mini B Connect after removing...

Page 86: ...r knife and grind burrs with a file etc Install the lower case to the flat wall with attached two wooden screws Connect the remote control cord to t terminal block Connect the terminal of remote cont with the terminal of indoor unit X Y X and Y are no polarity Wiring route is as shown in the right depending on the pulling out directio The wiring inside the remote control The sheath should be peele...

Page 87: ...crews Connect the remote control cord to the terminal block Connect the terminal of remote control X Y with the terminal of indoor unit X Y X and Y are no polarity Wiring route is as shown in the right diagram depending on the pulling out direction The wiring inside the remote control case should be within 0 3mm2 recommended to 0 5mm2 The sheath should be peeled off inside the remote control case ...

Page 88: ...ication changes to FUNCTION SET 2 Press button once and change to the TEMP RANGE indication 3 Press SET button and enter the temperature range setting mode 4 Select UPPER LIMIT or LOWER LIMIT by using button 5 Press SET button to fix 6 When UPPER LIMIT is selected valid during heating Press SET button to fix Indication example UPPER 26 C Displayed for two seconds After the fixed upper limit value ...

Page 89: ...o be reset producing 1 0 C increase in return air temperature of indoor unit To be reset producing 1 0 C increase in return air temperature of indoor unit To be reset producing 1 5 C increase in return air temperature of indoor unit To be reset producing 2 0 C increase in return air temperature of indoor unit When heating thermostat is OFF fan speed is low speed When heating thermostat is OFF fan ...

Page 90: ...Set as the same procedure if you want to set continuously and if to finish go to 7 Press ON OFF button Setting is finished Indication is changed to 02 FAN SPEED SET Go to Note If plural indoor units are connected to a remote control the indication is I U 000 blinking The lowest number of the indoor unit connected is indicated No and function are indicated by turns on the indoor unit function table...

Page 91: ...red to arrange dedic All indoor units must be models designed excl if connected into the system will impair prope INSTALLATION MANUAL FOR OUTDOOR UNIT 2 REFRIGERANT PIPIN 1 Restrictions on unit insta 1 HAULAGE AND INST CAUTION When a unit is hoisted wit center position If not pro 1 Delivery Deliver the unit as close as possible to t the packaging When you have to unpack the unit for a installation...

Page 92: ...s which can prevent inlet and outlet air of the unit Locations where short circuit of air can occur in case of multiple units installation Locations where strong air blows against the air outlet of outdoor unit Locations where something located above the unit could fall It can cause remarkable decrease in performance corrosion and damage of components malfunction and fire Use the prescribed pipes ...

Page 93: ...nly Drain elbow Heat pump type only Reducer set ø9 52 ø6 35 2 1 1 1 2 3 Check before installation work Q ty 2 REFRIGERANT PIPING WORK 1 Restrictions on unit installation and use Check the following points in light of the indoor unit specifications and the installation site Observe the following restrictions on unit installation and use Improper installation can result in a compressor failure or pe...

Page 94: ... the refrigerant pipes become extremely hot or extremely cold ing the operating condition and it can cause burn injury or frost injury t touch the suction or aluminum fin on the outdoor unit ay cause injury t put anything on the outdoor unit and operating unit ay cause damage the objects or injury due to falling to the object t use the unit for special purposes such as storing foods cooling ion in...

Page 95: ...efrigerant after servicing etc Do not hold the valve cap area with a spanner Use a torque wrench Wires for connecting indoor and outdoor units Exterior tape Gas piping Insulation Liquid piping Band accessory Pipe cover accessory Formula to calculate the volume of additional refrigerant required 7 Additional refrigerant charge Additional charge volume kg Main length m Factory charged volume x 0 020...

Page 96: ...ecifications shown in the above table are for units without heaters For units with heaters refer to the installation instructions or the construction instructions of the indoor unit Switchgear or Circuit breaker capacity which is calculated from MAX over current should be chosen along the regulations in each country The cable specifications are based on the assumption that a metal or plastic condu...

Page 97: ...arge volume per meter of pipe 0 025kg m ø9 52 ø12 7 12 6 ø9 52 ø15 88 12 6 0 06kg m FDT FDE FDU FDUM SRK Table of pipe size restrictions Please consult with our distributor in the area if you need to recover refrigerant and charge it again Any combinations of pipe sizes not listed in the table are not usable Wires for connecting indoor and outdoor units Exterior tape Gas piping Insulation Liquid p...

Page 98: ...nd maintenance to electrical components shall include initial safety checks and component inspection procedures If a fault exists that could compromise safety then no electrical supply shall be connected to the circuit until it is satisfactorily dealt with If the fault cannot be corrected immediately but it is necessary to continue operation an adequate temporary solution shall be used This shall ...

Page 99: ...an is completely familiar with the equipment and all its detail It is recommended good practice that all refrigerants are recovered safely Prior to the task being carried out an oil and refrigerant sample shall be taken in case analysis is required prior to re use of reclaimed refrigerant It is essential that electrical power is available before the task is commenced a Become familiar with the equ...

Page 100: ...3 2 4 0 4 8 5 7 6 7 7 8 9 0 10 2 11 5 12 9 14 4 Wall mounted type 1 6 2 1 2 9 3 8 4 8 6 0 7 2 8 6 10 1 11 7 13 4 15 3 17 2 19 3 21 5 Refrigerant charge amount kg 5 0 5 5 6 0 6 5 7 0 7 5 8 0 8 5 9 0 9 5 10 0 10 5 11 0 11 5 12 0 minimum installation area m2 Ceiling mounted type 16 19 23 27 31 36 41 46 52 58 64 70 77 84 92 Wall mounted type 24 29 34 40 47 54 61 69 77 86 95 105 115 126 137 0 20 40 60 ...

Page 101: ...ak down or malfunction Do not modify the unit Be sure to turn OFF the power circuit breaker before repairing inspecting the unit Repairing inspecting the unit with the power circuit breaker turned ON could cause electric shocks or injury Do not install the unit in appropriate environment or where gas could generate in accumulate or leak If the unit is used at places where air contains dense oil mi...

Page 102: ...t the wiring of the receiver through the opening Put the wiring on the notch on the control box so as not to be pinched by the control box and lid as shown below Connect the wiring to the terminal block provided in the control box No polarity Attach the receiver to the panel according to the panel installation manual 1 2 Installation of the receiver SW1 Prevents interference during plural setting ...

Page 103: ...i Attach the receiv Fix the wiring wi Reattach the co 1 3 Refrigerant pipes Drain pipe The receiver can be installed by replacing with a corner panel on the applicable decorative panel Installation of t SW2 R SW3 SW4 Master Slave setting when using plural remote controls Preparation before installation Attach the decorative panel onto the air conditioner according to the installation manual for th...

Page 104: ...iring to the terminal block provided in the control box No polarity Attach the receiver to the panel according to the panel installation manual Fix the wiring with the clamp so that the wiring do not contact the edge of control box s metal sheet Reattach the control box lid with 3 screws removed 1 3 4 2 Terminal block in the indoor unit control box Installation of the receiver SW2 slave setting ON...

Page 105: ...e battery compartment using nippers 3 Insert the batteries and attach the back lid Changing the remote control setting How to change the Auto Run setting The Auto Run mode is not available on the building air conditioning and gas heat pump series excluding the cooling heating free multi system When using the remote control to operate those models set the remote control to disable the Auto Run mode...

Page 106: ...ter sign display OFF 01 Filter sign display 180 hours 02 Filter sign display 600 hours 03 Filter sign display 1000 hours 04 Filter sign display Operation stop after 1000 hours have elapsed U P 00 Anti draft setting Disable 01 Anti draft setting Enable SILENT 00 Infrared sensor setting Motion sensor setting Disable 01 Infrared sensor setting Motion sensor setting Enable HI POWER 00 Infrared sensor ...

Page 107: ...receiver 300lux 2 Correlation betw and reachable a The drawing in between the re illuminance at control is ope condition of c the illuminance narrowed down 3 Installation tips Minimum distan of 300lux of illum Backup switch A Backup switch is when the operation control lost or con to operate as temp directly when oper 1 The air cond the condition point High fa position 2 The air cond the switch is...

Page 108: ...peration command with the wireless remote control unit while the backup switch on the receiver is depressed If the backup switch on the receiver is pressed during a test run it will end the test run If you cannot operate the unit properly during a test run please check wiring by consulting with inspection guides How to read the 2 digit display On the receiver of a wireless kit a two digit 7 segmen...

Page 109: ...ing or a wall Select a method according to the installation position Installation position A Direct installation onto the ceiling with wood screws Take out th Fit the upp Use this m 1 B Installat PJZ012D112 Master Slave setting when using plural remote controls Do It c 1 2 3 4 5 6 7 Switch A To change setting 1 Remove one screws located on the under of the receiver and detach the board 2 Change th...

Page 110: ...eceiver continued Take out the connector to the backside from the hole of the lower case putting through the wiring at Fit the upper case and the lower case and tighten the screws Use this method when installaing onto a gypsum board 7 to 18mm etc 1 2 B Installation with enclosed bracket 2D112 SW1 Prevents interference during plural setting ON Normal OFF Customized SW2 Receiver master slave setting...

Page 111: ...onnect the wiring to the power source of the terminal block If it is connected printed board will be damaged 1 3 Drill the receiver installation holes with the dimensions shown right at the ceiling position where wires can be connected A Direct installation onto the ceiling with wood screws 88mm H 101mm W B Installation with enclosed bracket 108mm H 108mm W 1 Drilling of the ceiling ceiling openin...

Page 112: ...rawing Insert the end of the installation fitting into the back of the ceiling from the opening and tighten the screws to fix the bracket onto the ceiling Pass the wiring from the rear side through the hole on the lower case Fit the lower case onto the bracket and fix the lower case to the bracket using the two installation holes shown above The other four holes are not used Follow step to for A to c...

Page 113: ...the indoor unit PCB from 000 to 127 so as not to duplicate Terminal block Receiver continued Receiv 5 Wood screw Cutting Holder for remote control Ensure the correct polarity when inserting Button Numb FAN SPEED MODE FILTER U P SILENT HI POWER Band enclosed Hole Lower case Cord clamp Wiring Fix with band Hole Upper case Lower case A p p r o x 1 0 0 m m o r m o r e C Exposed installation Use the fo...

Page 114: ... Standard ON TIMER 00 Cooling fan residual period running Disable 01 Fun speed setting Setting 1 01 Cooling fan residual period running 0 5 hours 02 Fun speed setting Setting 2 02 Cooling fan residual period running 2 hours MODE 00 Room heating temperature adjustment Disable 03 Cooling fan residual period running 6 hours 01 Room heating temperature adjustment 1 C OFF TIMER 00 Heating fan residual ...

Page 115: ...ed on ceiling 1 Standard reachable area of the signa Condition Illuminance at the receiver 300lux when no lighting is installed within 1m of the receiver in an ordinary office l Receiver Ceiling surface Ceiling surface Floor Floor Orientation of receiver Receivable area of the signal Receivable area of the signal Orientation of receiver 2 Correlation between illuminance at the receiver and reachabl...

Page 116: ...peration command with the wireless remote control unit while the backup switch on the receiver is depressed If the backup switch on the receiver is pressed during a test run it will end the test run If you cannot operate the unit properly during a test run please check wiring by consulting with inspection guides How to read the 6 digit display A 6 digit indicator 7 segment indicator is provided on...

Page 117: ... is not strong enough the unit may drop and cause injury Be sure to have the electrical wiring work done by qualified electrical installer and use exclusive circuit Power source with insufficient and improper work can cause electric shock and fire Shut OFF the main power source before starting electrical work Otherwise it could result in electric shocks break down or malfunction Do not modify the ...

Page 118: ... insect etc enters through the hole it could cause electric shocks fire or break down CAUTION Please make sure that you have all of the following accessories How to connect the wiring for control box Preparation before installation Setting on site PCB on the receiver has the following switches to set the function Default setting is shown with mark wo receiver 012D635 SW1 Prevents interference duri...

Page 119: ...ver or wired remote control can be installed in one indoor unit group When two receiver or wired remote control are used it is necessary to change switch on the PCB to set it as slave How to install the receiver Connect The receiver can be installed by replacing with a cover of the panel CAUTION When installing the receiver after unit has been fixed injury due to falling may result because of work...

Page 120: ...ion is unnecessary for indoor unit that have wiring is already connected from the signal terminal block to the receiver How to connect the wiring for control box o receiver remote can be in one nit group wo receiver remote are used it sary to switch on to set it as OFF Invalid er Slave ng when g plural e controls Wiring from receiver C L 3P Whire X White Y Black Attached wiring Signal terminal blo...

Page 121: ...e MODE button Note Once the batteries are removed the setting is reset to the factory default e v o b a d e b i r c s e d s p e t s e h t t a e p e r d e v o m e r e r a s e i r e t t a b e h t n e h W Indoor function settings 1 How to set indoor functions Press the ON OFF button to stop the unit Press the desired one of the buttons shown item 2 while holding down the FUNCTION SETTING switch Use t...

Page 122: ...Filter sign display Operation stop after 1000 hours have elapsed U P Up Down 00 Anti draft setting Disable 01 Anti draft setting Enable SILENT 00 Infrared sensor setting Motion sensor setting Disable 01 Infrared sensor setting Motion sensor setting Enable HI POWER 00 Infrared sensor control Motion sensor control Disable 01 Infrared sensor control Motion sensor control Power control only 02 Infrare...

Page 123: ...ol Up to two receivers can be installed in one indoor unit group Wireless rem Backup swi A backup switch section of the p When operation unit is not possi unit a unit failur means You sho If pressed w will cause t in the autom only in the Wind spee Louver ho If pressed Cooling test After safety Transmit a c on the receiv If the backup If you canno inspection g How to read A two digit indi An indic...

Page 124: ...n guides How to read the two digit display A two digit indicator 7 segment indicator is provided on the receiver section An indication will be displayed for one hour after power on An indication appears for 3 5 seconds when a Stop command is sent from the wireless remote control unit while the air conditioner is not running An indication appearing in 1 or 2 above will go off as soon as the unit st...

Page 125: ...case the cover needs to be detached protect the motion sensor with a packaging or bag In order to keep it away from water and dust 1 Places exposed to direct sunlight 2 Places near heat devices 3 High humidity places 4 Hot surface or cold surface enough to generate condensation 5 Places exposed to oil mist or steam directly 6 Places affected by the direct air flow of the Indoor unit 7 Places where...

Page 126: ... to the installation manual for the panel 2 Remove the inlet grille 3 Remove the corner lid A located on the panel 4 Loosen 2 screws for the control lid It is unnecessury to remove the screws 5 Slide the control lid and open and remove it Preparation before installation Hight of the ceiling 2 7 about 4 5 about 6 4 3 5 about 6 4 about 8 3 4 0 about 7 6 about 9 5 Detectable scope Detectable scope Re...

Page 127: ... through the opening of the panel Hang the wiring on the hook which is on the panel s inside Pass the wiring through the opening of the control box Connect the connecter to CNL 3P Black on PWB in the contorl box Tighten the bolts which fix the panel Install the motion sensor on the panel Fix the motion sensor by the screw Reinstall the control lid and tighten 2 screws 6 126 ...

Page 128: ...nstalled Set the function of the motion sensor by the wired or wireless remote control Refer to the manual instruction of each remote control for the setting procedure Note It is not possible to set by the following remote control models or older Wired RC EX1A RC E5 RCH E3 Wireless RCN E1R 127 ...

Page 129: ... as not to apply unexpected stress on the PCB Loose connection or hold will cause abnormal heat generation or fire Make sure the power source is turned off when electric wiring work Otherwise electric shock malfunction and improper running may occur WARNING CAUTION Attention Accessories Installing the motion sensor Please make sure that all components are in the package ø Please prepare a relay wi...

Page 130: ...the angle of about 100 degrees Height of the ceiling h m 2 7 3 5 4 0 Detectable area φ A m 4 5 6 4 7 6 Detectable area φ B m 6 4 8 3 9 5 The detectable area 0 8 h φA φB Ceiling plane Floor face Side of screws for fixing the case Installing the motion sensor There are the following 3 methods to install the motion sensor on the ceiling plane or wall surface hereinafter called ceiling plane Select th...

Page 131: ...hole Screws Installing hole Using a crimping terminal etc connect the same color to the relay wiring prepare on site and the wiring of motion sensor Relay wiring Wiring from the motion sensor Connect wirings with the same colors White Red Black White Sensor board Red Black Place the connecting part inside of the ceiling space Seal the wiring hole on the lower case with putty Taking care not to pin...

Page 132: ...o the relay wiring prepare on site and the wiring of motion sensor The same as of Option A Taking care not to pinch the wirings slip the upper case into the lower case and tighten the screws The same as of Option A Seal the cut part at Step with putty Option C Set up the switch box and relay wiring prepare on site in advance Seal the relay wiring inlet with putty Lower case Upper case Thinner part...

Page 133: ...site and the attached wiring 2 Remove the control box cover from the indoor unit Connect CnG connector 4P blue to the PCB Connect CnV2 connector 4P black to the PCB Relay wiring Connect wirings with the same colors White Red Black White Red Black Attached wiring to CnG connector 4P blue Connect the same color to the relay wiring prepare on site and the wiring of motion sensor The same as of Option...

Page 134: ...lled Set the function of the motion sensor by the wired or wireless remote control Refer to the manual instruction of each remote control for the setting procedure Note It is not possible to set by the following remote control models or older Wired RC EX1A RC E5 RCH E3 Wireless RCN E1R Setting the motion sensor Relay wiring prepare on site Connect wirings with the same colors White Red Black White...

Page 135: ... or bag In order to keep it away from water and dust Insert a too paintwork o Connect th connector correct dire CAUTION Do n Connect th and black Fix the wirin Connect Cn Connect Cn Install the m Place the c motion sen CAUTION Con In c pan This manual describes how to install the motion sensor kit Instruct the customer how to operate it correctly referring to the instruction manual For the install...

Page 136: ... activity area Use the separate motion sensor when using both wireless remote control and motion sensor together Motion sensor Height of the ceiling h m 2 7 3 5 4 0 Detectable area A m 2 9 3 9 4 5 Detectable area φ A m 4 5 6 4 7 6 Detectable area B m 3 9 4 8 5 4 Detectable area φ B m 6 4 8 3 9 5 φB Ceiling plane 0 8 h A φA Floor face B Wall surface The motion sen Set the function Refer to the ma N...

Page 137: ...ack to the PCB Connect the wiring 3P white Attached wiring to the indoor unit Clips Clip CnG connector 4P blue CnV2 connector 4P black Connector 3P white Clip Control box Attached wiring to the motion sensor kit Wiring from the motion sensor Install the motion sensor Place the connector under the panel and install it to the panel with careful attention to the direction of the motion sensor CAUTION...

Page 138: ...ocedure Note It is not possible to set by the following remote control models or older Wired RC EX1A RC E5 RCH E3 Wireless RCN E1R Connect the wiring 3P white Attached wiring to the indoor unit Clips Clip CnG connector 4P blue CnV2 connector 4P black Connector 3P white Clip Control box Attached wiring to the motion sensor kit Wiring from the motion sensor Install the motion sensor Place the connec...

Page 139: ...n the message display Menu Direction Heating 20 20 Tue F1 High power F2 Energy saving Timer Power control ON Set temp Menu Direction Cooling 16 32 Mon F1 High power F2 Energy saving Timer In auto off mode Set temp Control s Refer to the Cooling 16 14 Mon F1 High power Timer Now stopping Infrared sensor control Se Disab Disab Select the item Power control Auto off 1 Indoor funct 1 How to set i Pres...

Page 140: ...ared sensor control screen and contents of the current settings are displayed Enable disable power control Enable disable auto off After you set each item tap the Set button The display returns to the Energy saving setting menu screen Infrared sensor control Set Back Enable Disable Enable Disable Select the item Power control Auto off 3 1 2 Indoor function settings 1 How to set indoor functions Pr...

Page 141: ...ton Button to start stop the air conditioner FAN SPEED button Button to set the fan speed AIR CON No button Indicates the No of air conditioner which is connected MODE button Use to select the mode TEMP button Use to raise the setting temperature TEMP button Use to lower the setting temperature Operation mode display Indoor unit No display VRF series outdoor unit No display Central control display...

Page 142: ...tion 2 Maximum prolongation of remote control wiring is 600m If the prolongation is over 100m change to the size below But the wiring in the remote control case should be 0 3mm2 recommended to 0 5mm2 Change the wire size outside of the case according to wire connecting Waterproof treatment is necessary at the wire connecting section Be careful about contact failure Thin part The remote control wir...

Page 143: ...ct failure 100 200m 0 5mm2 2 cores Under 300m 0 75mm2 2 cores Under 400m 1 25mm2 2 cores Under 600m 2 0mm2 2 cores SettheswitchSW1 1ofthe Note The remote control the Install the master rem The air conditioner op master slave setting 3 Master slave setting w Up to two remote control 4 The indication when po At the time of turning the becomes as shown below The number displayed on and this is not an...

Page 144: ...te control 5 Confirmation method for return air temperature Return air temperature can be confirmed by the remote control operation Press AIR CON No button for over 5 seconds 88 blinks on the temperature setting indicator 88 blinks for approximately 2 seconds while data is read Then the return air temperature is displayed Example return air temperature 27 C blinking Note For the return air tempera...

Page 145: ... control thermistor enabled offset temperature at 3 0 C 05 Ventilation setting 01 No ventilator connection 02 Ventilator links air conditioner In case of Single split series by connecting ventilation device to CNT of the indoor printed circuit board in case of VRF series by connecting it to CND of the indoor printed circuit board the operation of ventilation device is linked with the operation of ...

Page 146: ...unction number 07 lighting for 3 to 20 seconds Setting number 01 lighting for 3 to 20 seconds Then the screen goes back to the function number blinking indication if the setting is sequentially conducted continue with the same procedures If the setting is finished proceed to Stop air conditioner and simultaneously press AIR CON No and MODE buttons at the same time for over three seconds The functi...

Page 147: ...on or there is a danger of being entangled in the rotating parts and getting injured Clean the air filter regularly Be sure to entrust qualified serviceman to performance on the air filter Be sure to cut off the power and stop the unit before performing maintenance 1 Table of filter kit parts No and corresponding object models Small model Medium model Large model Single type 50 60 71 100 140 Multi...

Page 148: ...side 2 Install the rail on both inner sides of the duct with the screw 3 Install the air filter on the rails Installation procesure 4 Install the bracket on the rail with the screw PJZ012D076 When the unit is installed bottom side of the unit is located at the lower side Insulation Rail Screw Air filter Bracket Screw Insulation Duct Sticking standard position for insulation Insu Duct lation 3 Inst...

Page 149: ...ad these Safety precautions thoroughly before installation All the cautionary items mentioned below are important safety related items to be taken into consideration so be sure to observe them at all times Incorrect installation could lead to serious consequences such as death major injury or envirommental destruction Symbols used in these precautions After completed installation carry out trial o...

Page 150: ...cable length approximately 1 3m from the indoor unit Be sure not to extend the connection cable on site If the connection cable is extended malfunction may occur Fix the interface on the wall pillar or the like Cut out the punch outs for the connection cables running into the casing with cutter Recess the electrical box procured locally and connection cables in the wall Mount the lower casing of t...

Page 151: ...ssion prohibition mode switch OFF the DIP switch SW2 3 on the interface PCB Connection of Superlink E board Functions of CnT connector Switch ON the DIP switch SW2 2 Factory setting ON on the interface PCB Wiring connection between the interface and the Superlink E board Clamp the connection cables with cable clamps Regarding the connection of Superlink E board refer to the installation manual of ...

Page 152: ...control with reference to the attached installation manual of wired remote control B 0 3mm2 x 2 cores cable should be used for the wiring of wired remote control C Maximum length of wiring is 600m If the length of wiring exceeds 100m change the size of cable as mentioned below 100m 200m 0 5mm2 x 2 cores 300m or less 0 75mm2 x 2 cores 400m or less 1 25mm2 x 2 cores 600m or less 2 0mm2 x 2 cores How...

Page 153: ... 19 PAC DB 333 l l l l l l er central control SL4N AE BE to control l l A 11 6 Superlink E board SC ADNA E K K 152 ...

Page 154: ... 19 PAC DB 333 l l l l l l l l DIP 153 ...

Page 155: ...mer season at indoor Declared coefficient of performance Warmer season at indoor temperature 20 and outdoor temperature Tj temperature 20 and outdoor temperature Tj Tj 2 Pdh kW Tj 2 COPd Tj 7 Pdh kW Tj 7 COPd Tj 12 Pdh kW Tj 12 COPd Tj bivalent temperature Pdh kW Tj bivalent temperature COPd Tj operating limit Pdh kW Tj operating limit COPd Declared capacity for heating Colder season at indoor Dec...

Page 156: ...lared capacity for heating Warmer season at indoor Declared coefficient of performance Warmer season at indoor temperature 20 and outdoor temperature Tj temperature 20 and outdoor temperature Tj Tj 2 Pdh kW Tj 2 COPd Tj 7 Pdh kW Tj 7 COPd Tj 12 Pdh kW Tj 12 COPd Tj bivalent temperature Pdh kW Tj bivalent temperature COPd Tj operating limit Pdh kW Tj operating limit COPd Declared capacity for heati...

Page 157: ...ng Warmer season at indoor Declared coefficient of performance Warmer season at indoor temperature 20 and outdoor temperature Tj temperature 20 and outdoor temperature Tj Tj 2 Pdh kW Tj 2 COPd Tj 7 Pdh kW Tj 7 COPd Tj 12 Pdh kW Tj 12 COPd Tj bivalent temperature Pdh kW Tj bivalent temperature COPd Tj operating limit Pdh kW Tj operating limit COPd Declared capacity for heating Colder season at indo...

Page 158: ...lared capacity for heating Warmer season at indoor Declared coefficient of performance Warmer season at indoor temperature 20 and outdoor temperature Tj temperature 20 and outdoor temperature Tj Tj 2 Pdh kW Tj 2 COPd Tj 7 Pdh kW Tj 7 COPd Tj 12 Pdh kW Tj 12 COPd Tj bivalent temperature Pdh kW Tj bivalent temperature COPd Tj operating limit Pdh kW Tj operating limit COPd Declared capacity for heati...

Page 159: ...armer season at indoor Declared coefficient of performance Warmer season at indoor temperature 20 and outdoor temperature Tj temperature 20 and outdoor temperature Tj Tj 2 Pdh kW Tj 2 COPd Tj 7 Pdh kW Tj 7 COPd Tj 12 Pdh kW Tj 12 COPd Tj bivalent temperature Pdh kW Tj bivalent temperature COPd Tj operating limit Pdh kW Tj operating limit COPd Declared capacity for heating Colder season at indoor D...

Page 160: ...lared capacity for heating Warmer season at indoor Declared coefficient of performance Warmer season at indoor temperature 20 and outdoor temperature Tj temperature 20 and outdoor temperature Tj Tj 2 Pdh kW Tj 2 COPd Tj 7 Pdh kW Tj 7 COPd Tj 12 Pdh kW Tj 12 COPd Tj bivalent temperature Pdh kW Tj bivalent temperature COPd Tj operating limit Pdh kW Tj operating limit COPd Declared capacity for heati...

Page 161: ...for heating Warmer season at indoor Declared coefficient of performance Warmer season at indoor temperature 20 and outdoor temperature Tj temperature 20 and outdoor temperature Tj Tj 2 Pdh kW Tj 2 COPd Tj 7 Pdh kW Tj 7 COPd Tj 12 Pdh kW Tj 12 COPd Tj bivalent temperature Pdh kW Tj bivalent temperature COPd Tj operating limit Pdh kW Tj operating limit COPd Declared capacity for heating Colder seaso...

Page 162: ...lared capacity for heating Warmer season at indoor Declared coefficient of performance Warmer season at indoor temperature 20 and outdoor temperature Tj temperature 20 and outdoor temperature Tj Tj 2 Pdh kW Tj 2 COPd Tj 7 Pdh kW Tj 7 COPd Tj 12 Pdh kW Tj 12 COPd Tj bivalent temperature Pdh kW Tj bivalent temperature COPd Tj operating limit Pdh kW Tj operating limit COPd Declared capacity for heati...

Page 163: ...ty for heating Warmer season at indoor Declared coefficient of performance Warmer season at indoor temperature 20 and outdoor temperature Tj temperature 20 and outdoor temperature Tj Tj 2 Pdh kW Tj 2 COPd Tj 7 Pdh kW Tj 7 COPd Tj 12 Pdh kW Tj 12 COPd Tj bivalent temperature Pdh kW Tj bivalent temperature COPd Tj operating limit Pdh kW Tj operating limit COPd Declared capacity for heating Colder se...

Page 164: ...t we reserve the right to make changes in all specifications without notice INVERTER WALL MOUNTED TYPE RESIDENTIAL AIR CONDITIONERS Copyright MITSUBISHI HEAVY INDUSTRIES THERMAL SYSTEMS LTD Because of our policy of continuous improvement we reserve the right to make changes in all specifications without notice C MITSUBISHI HEAVY INDUSTRIES THERMAL SYSTEMS LTD 2 3 Marunouchi 3 chome Chiyoda ku Toky...

Reviews: