107
-
'19 • PAC-SM-334
E59
Compressor startup failure
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
NO
NO
Is power
source voltage
OK?
Is
the pressure balance
at starting OK?
NO
NO
Is the
insulation resistance and
resistance between terminals (1)
of compressor OK ?
Is power transistor
module OK?
Try to startup
several times
Does it start?
NO
NO
Is
the output of inverter
checker OK ?
Compressor does not start at all.
Neither noise nor vibration cannot be heard
Disconnect the outdoor fan motor
connector and try to startup
Does
compressor
startup?
YES
NO
Note: Several times restarting
may resolve it, because migrated
liquid refrigerant in the
compresser is discharged from
the compressor.
YES
YES
YES
YES
YES
(1) 0.724
Ω
or more at 20°C (Model FDC90, 100)
Replace outdoor fan motor.
Check power source
voltage.
Check refrigerant amount
and refrigerant circuit.
Repalce compressor.
Defective outdoor unit
PCB
➞
Replace.
Defective outdoor unit
PCB
➞
Replace.
Repalce compressor.
2. Error detection method
• If it fails to change over to the
rotor detection operation of
compressor motor
3. Condition of Error displayed
If compressor fails to startup for
42 times
4. Presumable cause
• Faulty outdoor fan motor
• Faulty outdoor unit PCB
• Anomalous power source
voltage
• Improper refrigerant amount
and refrigerant circuit
• Faulty compressor (Motor
bearing)
Note: Insulation resistance
• The unit is left for long period without power source or soon after installation, migrated liquid refrigerant may dissolve in the refrigerant oil in the compressor.
In such case insulation resistance decreases upto several M
Ω
or lower. If the electric leakage breaker is activated due to low insulation resistance,
check followings.
➀
Check whehter the insulation resistance can recover or not, ater 6 hours has passed since power ON.
(By energize the crankcase heater, migrated liquid refrigerant in the refrigerant oil in compressor can be evaporated)
➁
Check whether the electric leakage breake conforms to high-hermonic specifications
(As units has inverter, in order to prevent from improper operation, be sure to use high-hermonic one.)
Error code
Remote control:
LED
Green
Red
Content
Indoor
Stays OFF
Keeps flashing