47
-
'19 • PAC-SM-334
(1) Selfdiagnosis function
(a) Check indicator table
Whether a failure exists or not on the indoor unit can be know by the contents of remote control error code, indoor unit
green LED (power pilot lamp and microcomputer normality pilot lamp) or red LED (check pilot lamp).
(i) Indoor unit
Remote control
Indoor unit control PCB
Location of trouble
Description of trouble
Repair method
Reference
page
Error code Red LED Red LED
Green
LED (1)
No-indication Stays OFF
Stays OFF
Keeps
flashing
—
• Normal operation
—
—
Stays OFF Stays OFF
Indoor unit power source
• Power OFF, broken wire/blown fuse, broken transformer wire
Repair
73
*
3-time
flash
Keeps
flashing
Remote control wires
• Poor connection, breakage of remote control wire * For wire breaking at power ON, the LED is OFF.
Repair
74
Remote control
• Defective remote control PCB
Replacement of
remote control
WAIT
or
INSPECT I/U
Stays OFF
Keeps
flashing
Indoor-outdoor units connection
wire
• Poor connection, breakage of indoor-outdoor units connection wire
Repair
75
-
79
Remote control
• Improper setting of master and slave by remote control
Keeps
flashing
Stays OFF
*
Keeps
flashing
Remote control wires (Noise)
•
Poor connection of remote control signal wire (White)
•
Intrusion of noise in remote control wire
* For wire breaking at power ON, the LED is OFF
Repair
80
Remote control indoor unit control
PCB
*
• Defective remote control or indoor unit control PCB (defective communication circuit)?
Replacement of
remote control or
PCB
2-time
flash
Keeps
flashing
Indoor-outdoor units connection
wire
•
Poor connection of wire between indoor-outdoor units during operation
(disconnection, loose connection)
•
Anomalous communication between indoor-outdoor units by noise, etc.
Repair
81
2-time
flash
Keeps
flashing
(Noise)
•
CPU-runaway on outdoor PCB
Power reset or
Repair
Outdoor unit PCB
*
• Occurrence of defective outdoor unit PCB on the way of power source (defective communication circuit)?
Replacement of
PCB
2-time
flash
Keeps
flashing
Outdoor unit PCB
•
Defective outdoor unit PCB on the way of power source
Replacement
Fuse
•
Blown fuse
1-time
flash
Keeps
flashing
Indoor heat exchanger tempera-
ture sensor
•
Defective indoor heat exchanger temperature sensor
(defective element, broken wire, short-cir-
cuit)
• Poor contact of temperature sensor connector
Replacement, repair
of temperature
thermistor
82
Indoor unit control PCB
*
•
Defective indoor unit control PCB (Defective temperature sensor input circuit)?
Replacement of
PCB
1-time
flash
Keeps
flashing
Indoor return air temperature
sensor
•
Defective indoor return air temperature sensor
(defective element, broken wire, short-circuit)
• Poor contact of temperature sensor connector
Replacement, repair
of temperature
thermistor
83
Indoor unit control PCB
*
•
Defective indoor unit control PCB (Defective temperature sensor input circuit)?
Replacement of
PCB
1-time
flash
Keeps
flashing
Installation or operating condi-
tion
•
Heating over-load
(Anomalously high indoor heat exchanger temperature)
Repair
84
Indoor heat exchanger tempera-
ture sensor
•
Defective indoor heat exchanger temperature sensor (short-circuit)
Replacement of
temperature therm-
istor
Indoor unit control PCB
*
•
Defective indoor unit control PCB
(Defective temperature sensor input circuit)?
Replacement of
PCB
1-time
flash
Keeps
flashing
Drain trouble
•
Defective drain pump (DM), broken drain pump wire
, disconnected connector
Replacement, repair
of DM
85
Float switch
•
Anomalous float switch operation
(malfunction)
Repair
Indoor unit control PCB
*
•
Defective indoor unit control PCB
(Defective float switch input circuit)
*
•
Defective indoor unit control PCB
(Defective DM drive output circuit)?
Replacement of
PCB
Option
•
Defective option parts
(At option anomalous input setting)
Repair
Stays OFF
Keeps
flashing
Number of connected indoor
units
•
When multi-unit control by remote control is performed, the number of units is over
Repair
86
Keeps
flashing
Keeps
flashing
Address setting error
• Address setting error of indoor units
Repaie
87
3-time
flash
Keeps
flashing
Indoor unit No. setting
• No master is assigned to slaves.
Repair
88
Rcmote control wires
• Anomalous remote control wire connection. broken wire between master and slave units
1(2)-time
flash
Keeps
flashing
Fan motor
•
Defective fan motor
Replacement, repair
89
Indoor unit power PCB
•
Defective indoor unit power PCB
Replacement
1-time
flash
Keeps
flashing
Address setting error
• Address setting error of master and slave indoor units
Repair
90
1-time
flash
Keeps
flashing
Indoor unit control PCB
•
Improper operation mode setting
Repair
91
2. MAINTENANCE DATA
2.1 FDT, FDU, FDUM, FDE series
2.1.1 Diagnosing of microcomputer circuit