-
49
-
'19 • PAC-SM-334
(iv) Display sequence of error codes or inspection indicator lamps
■
Occurrence of one kind of error
Displays are shown respectively according to errors.
■
Occurrence of plural kinds of error
Section
Category of display
Error code on remote
control
• Displays the error of higher priority (When plural errors are persisting)
• Displays the present errors. (When a new error has occurred after the former error was reset.)
Red LED on indoor unit
control PCB
■
Error detecting timing
Section
Error description
Error code
Error detecting timing
Indoor
Drain trouble (Float switch
activated)
Whenever float switch is activated after 30 seconds had past
since power ON.
Communication error at
initial operation
“
WAIT
” No communication between indoor and outdoor units is
established at initial operation.
Remote control
communication circuit error
Communication between indoor unit and remote control
is interrupted for more than 2 minutes continuously after
initial communication was established.
Communication error during
operation
Communication between indoor and outdoor units is
interrupted for more than 2 minutes continuously after
initial communication was established.
Excessive number of
connected indoor units by
controlling with one remote
control
Whenever excessively connected indoor units is detected
after power ON.
Return air temperature sensor
anomaly
-50°C or lower is detected for 5 seconds continuously
within 60 minutes after initial detection of this anomalous
temperature.
Indoor heat exchanger
temperature sensor anomaly
-50°C or lower is detected for 5 seconds continuously
within 60 minutes after initial detection of this anomalous
temperature.
Or 70°C or higher is detected for 5 seconds continuously.
Outdoor
Outdoor air temperature
sensor anomaly
-55°C or lower is detected for 5 seconds continuously
3 times within 40 minutes after initial detection of this
anomalous sensor.
Or -55°C or higher is detected for 5 seconds continuously
within 20 seconds after power ON.
Outdoor heat exchanger
temperature sensor anomaly
-55°C or lower is detected for 5 seconds continuously
3 times within 40 minutes after initial detection of this
anomalous sensor.
Or -55°C or lower is detected for 5 seconds continuously
within 20 seconds after power ON.
Discharge pipe temperature
sensor anomaly
-25°C or lower is detected for 5 seconds continuously
3 times within 40 minutes after initial detection of this
anomalous sensor.