74
-
'19 • PAC-SM-334
Error code
Remote control:
LED
Green
Red
Indoor
Content
None
Power source system error
(Power source to remote control)
Keeps flashing
Stays OFF
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
Isn't there any
loose connection of remote
control wires?
Isn't remote
control wire broken or
short-circuited?
Is DC180V
between
➀
-
➁
of
CNW2?
Disconnect remote
control wires.
NO
Is DC15V or
higher detected between X-Y
of indoor unit terminal
block?
YES
YES
YES
YES
NO
NO
NO
Correct.
Replace wires.
Replace remote control.
Defective indoor unit
power PCB
➞
Replace.
Defective indoor unit
control PCB
➞
Replace.
2. Error detection method
3. Condition of Error displayed
4. Presumable cause
• Remote control wire
breakage/short-circuit
• Defective remote control
• Malfunction by noise
• Faulty indoor unit power PCB
• Broken harness
• Faulty indoor unit control PCB
Note: