10
-
(2) Compressor control (Master unit/slave unit)
(a) Starting compressor
(i)
Compressor starting order (2 compressors specification)
After turning the power on, firstly CM1 compressor starts. (In case of the combination use, it is CM01 of master
unit) And corresponding to the condition of under-dome temperature and to the required capacity of indoor units
thermostat ON, the next compressor will start sequentially, and finally maximum 4 compressors ( in case of combi
-
nation use) will start simultaneously.
1) Single use
The range of frequency for each compressor corresponding to the heat load is shown in below mentioned table.
(The table shows the case that CM1 starts first. If CM2 starts first, the frequency of CM2 should be applied that
of CM1 shown in heat load zone 1 instead.)
Following tabel is shown the case that the maximum compressor frequency is 120Hz.
Note (1) Value in ( ) are for the models FDC615, 680KXE6
2) Combination use
The range of frequency for each compressor corresponding to the heat load is shown in below mentioned
table. (The table shows the case that CM01 starts first. If CM11 starts first, the frequency of CM11 should be
applied that of CM01 shown in heat load zone 1 instead.)
Note (1) Value in ( ) are for the models FDC1180~1360KXE6
(ii) Rotation of compressor start/stop order
1) The compressors will be changed over by determinating the start/stop order in each heat load zone.
2) In case of single use, the starting order of CM1 and CM2 will be changed over on each occasion when the out
-
door unit stops.
3) In case of combination use, the starting order of CM01(CM11) and CM02(CM12) will be changed over on each
occation when the master unit or slave unit stops all independently.
4) In case of combination use, the starting order of master and slave units will be changed over on each occasion
when the master unit or slave unit stops all independently.
Starting order of outdoor units
Master→Slave→Master
(Reference)
Change in number of compressors operating
Note (1) Value in ( ) are for the models FDC615, 680KXE6 and FDC1180~1360KXE6
(2) After recovery of power blackout, starting order of compressor is always CM01of master unit.
Model
FDC335~680
FDC735~1360
Starting Order of Outdoor Units Starting Order of Compressors
CM 1
→
CM 2
→
CM 1
Master
→
Slave
→
Master
CM 1
→
CM 2
→
CM 1
−
CM1
Heat load zone
CM2
0
0Hz
0Hz
1
20~112Hz (22~92Hz)
0Hz
2
42 (34)~120Hz
42 (34)~120Hz
Heat load zone
Master unit
Slave unit
CM01
CM02
CM11
CM12
0
0Hz
0Hz
0Hz
0Hz
1
20~112Hz (20~92Hz)
0Hz
0Hz
0Hz
2
42~112Hz (34~92Hz)
0Hz
42~112Hz (34~92Hz)
0Hz
3
42~120Hz (34~120Hz)
42~120Hz (34~120Hz)
42~120Hz (34~120Hz)
42~120Hz (34~120Hz)
1-Compressor
2-compressors
4-compressors
80Hz
(60Hz)
112Hz
(92Hz)
80Hz
×
2
(66Hz
×
2)
112Hz
×
2
(92Hz
×
2)
Summary of Contents for FDE112KXE6A
Page 104: ... 102 ...
Page 111: ... 108 b Ceiling cassette 4 way Compact type FDTC Models All moddels B PJA003Z331 ...
Page 112: ... 109 c Ceiling cassette 2 way type FDTW Models FDTW28KXE6 45KXE6 56KXE6 B PJB001Z560 ...
Page 113: ... 110 Models FDTW71KXE6 90KXE6 B PJB001Z561 ...
Page 114: ... 111 Models FDTW112KXE6 140KXE6 B PJB001Z562 ...
Page 115: ... 112 d Ceiling cassette 1 way type FDTS Model FDTS45KXE6 A PJC001Z195 ...
Page 116: ... 113 Model FDTS71KXE6 A PJC001Z196 ...
Page 117: ... 114 e Ceiling cassette 1 way compact type FDTQ Models All models A PJC001Z190 ...
Page 118: ... 115 Models All models Duct panel A PJC001Z240 ...
Page 121: ... 118 Models FDU224KXE6 280KXE6 B PJD001Z230 ...
Page 123: ... 120 Models FDUM112KXE6 140KXE6 B PJR002Z259 ...
Page 124: ... 121 h Duct connected Ultra thin Low static pressure type FDQS Models All models C PJC001Z200 ...
Page 125: ... 122 i Wall mounted type FDK Models FDK22KXE6 28KXE6 36KXE6 45KXE6 56KXE6 B PHA000Z983 ...
Page 126: ... 123 Models FDK71KXE6 B PHA000Z984 ...
Page 127: ... 124 j Ceiling suspended type FDE Models FDE36KXE6A 45KXE6A 56KXE6A B PFA003Z826 ...
Page 128: ... 125 Models FDE71KXE6A 112KXE6A 140KXE6A B PFA003Z827 ...
Page 129: ... 126 k Floor standing with casing type FDFL Models All models B PGD000Z053 ...
Page 130: ... 127 l Floor standing without casing type FDFU Models All models A PGD000Z058 ...
Page 131: ... 128 m Duct Connected Compact and Flexible type FDUH Models All models A PJC001Z255 ...
Page 138: ... 135 ...
Page 139: ... 136 ...
Page 143: ... 140 b ...
Page 144: ... 141 ...
Page 191: ... 188 5 4 Installation of outdoor unit ...
Page 193: ... 190 ...
Page 194: ... 191 ...
Page 195: ... 192 ...
Page 196: ... 193 ...
Page 197: ... 194 ...
Page 198: ... 195 ...
Page 199: ... 196 ...
Page 200: ... 197 ...
Page 201: ... 198 ...
Page 202: ... 199 ...
Page 203: ... 200 ...
Page 204: ... 201 ...
Page 205: ... 202 ...
Page 206: ... 203 ...
Page 207: ... 204 ...
Page 208: ... 205 ...
Page 210: ... 207 ...
Page 211: ... 208 ...
Page 212: ... 209 ...
Page 215: ... 212 2 model type DIS model type HEAD ...
Page 216: ... 213 2 2 ...
Page 217: ... 214 2 2 2 2 2 ...