14
-
(6) Compressor pre-start control (Master unit/slave unit)
(a) The following control is performed when the compressor ON conditions are established.
(i) Pre-start control when the operation mode is same as previous operation mode:
1) In case of "Cooling /Dehumidifying" mode, 4-way valve is turned OFF. In case of "Heating" mode, 4-way
valve
is turned ON.
However if the operation mode is same as previous operation mode and 4-way valve is retaing prescribed condi
-
tion, the control status of 4-way valve is unchanged.
2) Solenoide valve SV6 and SV7 are turned ON.
3) The opening degree of EEVH1, 2 for heating and EEVSC for subcooling coil are set to the initial opening degree
mentioned in following table. The expansion valves EEVH1, 2 are operated first, and after those operations are
completed, the expansion valve EEVSC will be operated.
Note (1) Expansion valves of master unit and slave unit are operated respectively.
4) Fan motors FMo1, FMo2 and compressor start 15 seconds after the compressor ON conditions are satisfied.
�
Cooling
�
Heating
Heating
Cooling
FM
O
1,2
OFF
OFF
ON
ON
ON
20S
SV6
EEVH1,2
470
EEVSC
CM1
ON
CM2
ON
3 minutes
3 minutes
Open/close control
Opening degree control
Initial opening degree
Full-close or 100
pulse
Opening degree control
Full-close
OFF
OFF
Min. of 3 minutes
15 seconds
6 seconds
Compressor stop
Compressor start
Starting conditions are satisfied
Operation mode
Cooling
EEVH1, 2
EEVSC
Name
Item
470
32
10
0
(Unit: Pulse)
Heating
Summary of Contents for FDE112KXE6A
Page 104: ... 102 ...
Page 111: ... 108 b Ceiling cassette 4 way Compact type FDTC Models All moddels B PJA003Z331 ...
Page 112: ... 109 c Ceiling cassette 2 way type FDTW Models FDTW28KXE6 45KXE6 56KXE6 B PJB001Z560 ...
Page 113: ... 110 Models FDTW71KXE6 90KXE6 B PJB001Z561 ...
Page 114: ... 111 Models FDTW112KXE6 140KXE6 B PJB001Z562 ...
Page 115: ... 112 d Ceiling cassette 1 way type FDTS Model FDTS45KXE6 A PJC001Z195 ...
Page 116: ... 113 Model FDTS71KXE6 A PJC001Z196 ...
Page 117: ... 114 e Ceiling cassette 1 way compact type FDTQ Models All models A PJC001Z190 ...
Page 118: ... 115 Models All models Duct panel A PJC001Z240 ...
Page 121: ... 118 Models FDU224KXE6 280KXE6 B PJD001Z230 ...
Page 123: ... 120 Models FDUM112KXE6 140KXE6 B PJR002Z259 ...
Page 124: ... 121 h Duct connected Ultra thin Low static pressure type FDQS Models All models C PJC001Z200 ...
Page 125: ... 122 i Wall mounted type FDK Models FDK22KXE6 28KXE6 36KXE6 45KXE6 56KXE6 B PHA000Z983 ...
Page 126: ... 123 Models FDK71KXE6 B PHA000Z984 ...
Page 127: ... 124 j Ceiling suspended type FDE Models FDE36KXE6A 45KXE6A 56KXE6A B PFA003Z826 ...
Page 128: ... 125 Models FDE71KXE6A 112KXE6A 140KXE6A B PFA003Z827 ...
Page 129: ... 126 k Floor standing with casing type FDFL Models All models B PGD000Z053 ...
Page 130: ... 127 l Floor standing without casing type FDFU Models All models A PGD000Z058 ...
Page 131: ... 128 m Duct Connected Compact and Flexible type FDUH Models All models A PJC001Z255 ...
Page 138: ... 135 ...
Page 139: ... 136 ...
Page 143: ... 140 b ...
Page 144: ... 141 ...
Page 191: ... 188 5 4 Installation of outdoor unit ...
Page 193: ... 190 ...
Page 194: ... 191 ...
Page 195: ... 192 ...
Page 196: ... 193 ...
Page 197: ... 194 ...
Page 198: ... 195 ...
Page 199: ... 196 ...
Page 200: ... 197 ...
Page 201: ... 198 ...
Page 202: ... 199 ...
Page 203: ... 200 ...
Page 204: ... 201 ...
Page 205: ... 202 ...
Page 206: ... 203 ...
Page 207: ... 204 ...
Page 208: ... 205 ...
Page 210: ... 207 ...
Page 211: ... 208 ...
Page 212: ... 209 ...
Page 215: ... 212 2 model type DIS model type HEAD ...
Page 216: ... 213 2 2 ...
Page 217: ... 214 2 2 2 2 2 ...