-
177
-
⑦
Drain pipe
⑥
Refrigerant pipe
Caution
●
Use the new refrigerant pipe.
When re-using the existing pipe system for R22 or R407C, pay attention to the following items.
・
Change the flare nuts with the attached ones (JIS category 2), and reprocess the flare parts.
・
Do not use thin-walled pipes.
●
Use phosphorus deoxidized copper alloy seamless pipe (C1220T specified in JIS H3300) for
refrigeration pipe installation.
In addition, make sure there is no damage both inside and outside of the pipe, and no harmful
substances such as sulfur, oxide, dust or a contaminant stuck on the pipes.
●
Do not use any refrigerant other than R410A.
Using other refrigerant except R410A (R22 etc.) may degrade inside refrigeration oil. And air
getting into refrigeration circuit may cause over-pressure and resultant it may result in bursting,
etc.
●
Store the copper pipes indoors and seal the both end of them until they are brazed in order to
avoid any dust, dirt or water getting into pipe. Otherwise it will cause degradation of refrigeration
oil and compressor breakdown, etc.
●
Use special tools for R410 refrigerant.
Work procedure
1. Remove the flare nut and blind flanges on the pipe of the indoor unit.
※
Make sure to loosen the flare nut with holding the nut on pipe side with a spanner and giving
torque to the nut with another spanner in order to avoid unexpected stress to the copper pipe, and
then remove them.
(Gas may come out at this time, but it is not abnormal.)
●
Pay attention whether the flare nut pops out. (as the indoor unit is sometimes pressured.)
2. Make a flare on liquid pipe and gas pipe, and connect the refrigeration pipes on the indoor unit.
※
Bend the pipe with as big radius as possible and do not bend the pipe repeatedly. In
addition, do not twist and crush the pipes.
※
Do a flare connection as follows:
●
Make sure to loosen the flare nut with holding the nut on pipe side with a spanner and giving
torque to the nut with another spanner in order to avoid unexpected stress to the copper
pipe, and then remove them.
●
When fastening the flare nut, align the refrigeration pipe with the center of flare nut, screw
the nut for 3-4 times by hand and then tighten it by spanner with the specified torque
mentioned in the table below. Make sure to hold the pipe on the indoor unit securely by a
spanner when tightening the nut in order to avoid unexpected stress on the copper pipe.
3. Cover the flare connection part of the indoor unit with attached insulation material after a gas
leakage inspection, and tighten both ends with attached straps.
●
Make sure to insulate both gas pipes and liquid pipes completely.
※
Incomplete insulation may cause dew condensation or water dropping.
4. Refrigerant is charged in the outdoor unit.
As for the additional refrigerant charge for the indoor unit and piping, refer to the installation
manual attached to the outdoor unit.
Caution
●
Install the drain pipe according to the installation manual in order to drain properly.
Imperfection in draining may cause flood indoors and wetting the household goods
,
etc.
●
Do not put the drain pipe directly into the ditch where toxic gas such as sulfur, the other harmful and
inflammable gas is generated. Toxic gas would flow into the room and it would cause serious
damage to user’s health and safety (some poisoning or deficiency of oxygen). In addition, it may
cause corrosion of heat exchanger and bad smell.
●
Connect the pipe securely to avoid water leakage from the joint.
●
Insulate the pipe properly to avoid condensation drop.
●
Check if the water can flow out properly from both the drain outlet on the indoor unit and the end
of the drain pipe after installation.
●
Make sure to make descending slope of greater than 1/100 and do not make up-down bend and/or trap
in the midway. In addition, do not put air vent on the drain pipe. Check if water is drained out properly
from the pipe during commissioning. Also, keep sufficient space for inspection and maintenance.
Pipe diameter
Tightening torque N·m
φ
6.35
φ
9.52
φ
12.7
φ
15.88
φ
19.05
14 to 18
34 to 42
49 to 61
68 to 82
100 to 120
Strap (Accessory)
Pipe cover (Accessory)
The thickness of insulation should be 20mm or more.
Work procedure
1. Connect the drain pipe (VP-20) to drain socket using “transparent soft tube (accessory)” and
secure firmly with a clamp.
●
Do not apply adhesives on both side.
{*1 If the drain tube is directly connected with drain socket, the drain socket and drain pan
would not be able to be removed.}
{*2 As optional setting, rubber hose (inside diameter
F
19) can be connected directly with clamp
to above drain socket under the later condition.}
2. Make sure to make descending slope of greater than 1/100 and do not make up-down bend
and/or trap in the midway.
●
Pay attention not to give stress on the pipe on the indoor unit side, and support and fix
the pipe as close place to the unit as possible when connecting the drain pipe.
●
Do not set up air vent.
●
When sharing a drain pipe for more than
one unit, lay the main pipe 100mm
below the drain outlet of the unit. In
addition, select VP-30 or bigger size for
main drain pipe.
Descending slope greater than 1/100
VP-30 or bigger
As wide as possible
(about100mm)
⑧
Wiring-out position and wiring connection
●
Electrical installation work must be performed according to the installation manual by an
electrical installation service provider qualified by a power provider of the country, and be
executed according to the technical standards and other regulations applicable to electrical
installation in the country.
Be sure to use an exclusive circuit.
●
Use specified cord, fasten the wiring to the terminal securely, and hold the cord securely in
order not to apply unexpected stress on the terminal.
●
Do not put both power source line and signal line on the same route. It may cause miscom-
munication and malfunction.
●
Be sure to do D type earth work.
●
For the details of electrical wiring work, see attached instruction manual for electrical wiring work.
1. Remove a lid of the control box (2 screws).
2. Hold each wiring inside the unit and fasten them to terminal block securely.
3. Fix the wiring with clamps.
4. Install the removed parts back to original place.
Power source
side terminal
block
Earth (Signal line)
Signal line
(Shielded cord)
Remote
controller line
Earth
Indoor power source line
Clamp
Earth
Indoor power
source line
Signal side terminal block
⑨
Check list after installation
●
Check the following items after all installation work completed.
Check if;
Expected trouble
Check
The indoor and outdoor units are fixed securely?
Falling, vibration, noise
Inspection for leakage is done?
Insufficient capacity
Insulation work is properly done?
Water leakage
Water is drained properly?
Water leakage
Supply voltage is same as mentioned in the model name plate? PCB burnt out, not working at all
There is mis-wiring or mis-connection of piping?
PCB burnt out, not working at all
Earth wiring is connected properly?
Electric shock
Cable size comply with specified size?
PCB burnt out, not working at all
Any obstacle blocks airflow on air inlet and outlet?
Insufficient capacity
Drain socket
Pipe cover for insulation {t10}
(Prepare on site)
Transparent soft tube
(Accessory)
VP-20 (Prepare on site)
Clamp (Accessory)
Supporting metal
No bump
No trap
Not touching the water
Trapped air will
generate noises.
Air vent
Insulation material
1.5m ~ 2m
⑤
Duct work
Request
①
●
Calculate air capacity and the outside static pressure to select the
duct’s length
and shape, and blow outlet.
Caution
●
Take care that the outside static pressure does not exceed 30 Pa.
The unit has condensation owing to the decrease in air capacity,
possibly causing the ceiling and household goods to become wet.
②
The main body of the air conditioner is not provided with an air filter.
Assemble it into the suction grill for which cleaning is easy.
③
Blow duct
●
Make the duct the shortest in length.
●
Bend a lot less abruptly. (Make the bend radius a lot larger.)
●
When connecting the main body to the duct flange of the blow outlet, attach the insulation
material to the fixed portion to protect it from condensation.
●
Conduct the duct work before ceiling attachment.
④
Inlet port
●
When placing the inlet port to carry out suction from the bottom side, use the following proce-
dure to replace the suction duct joint (prepare on site) and the bottom plate.
●
Remove the screws which fasten the
●
Replace the removed bottom plate
bottom plate and the duct joint (prepare
and duct joint (prepare on site).
on site) on the inlet port side of the unit.
●
Fit the duct join (prepare on site) with a screw;
fit the bottom plate.
⑤
Make sure to keep the suction duct warm to protect it from condensation.
⑥
Install the blowout hole where air can flow all over the room.
⑦
Make sure to install the inspection opening in the ceiling. It is needed for the maintenance of
electrical parts, the motor and other parts.
Descending slope greater than 1/100
“U” shape space
The previous
“U” shape space
Air conditioner main unit
Ceiling suriace
Suction hole
(marketed item)
(with air filter)
Inspection hole
Suction duct
(marketed item)
Blow outlet
Blowout duct
(optional or marketed item)
⑤
Duct work (continued)
Example of bad duct work
①
If the suction duct is made in the ceiling without using the suction side duct, the temperature
inside the ceiling will be high owing to the ventilating fan’s performance, the strength of any
wind blowing against the outdoor air louver, weather (on a rainy day) and other factors.
●
The outside plate of the unit may have condensation, causing water to drip on the ceiling.
Also, in the case of a new house of a concrete structure, the temperature may be high
without a duct inside the ceiling. In such a case, keep the whole unit warm using glass wool
(25mm). (Cover the glass wool with wire netting or the like.)
●
The unit may be beyond its operation limit, causing overloading of the compressor, and other
trouble.
●
Because the blowing capacity of the unit increases, owing to the ventilating fan’s perfor-
mance and any wind blowing against the outdoor air louver, up to its use limit, draining liquid
from the heat exchanger does not flow into the drain pan, possibly flowing to the outside and
causing water leaks (in which drained liquid drips on the ceiling).
Bad example of duct work
For ventilation
Louver to
outdoor air
④
Installation of indoor unit (continued)
xä
{ä
Îä
Óä
£ä
ä
È°x
È°ä
Ç
Ç°x
Ç°n
-Ì>ÌVÊ*ÀiÃÃÕÀiÊ*>®
ÀÊvÜÊ
Î
É®
}
`Õ
Ü
/Ê "8
> Procedure for optional setting of control box
(i) Remove bottom plate.
(ii) Unfasten two (2) “straps” for wire.
(iii) Remove the plate for control box. (2 screws), and set it at optional position (oposite side).
(iv) Remove the control box (2 screws), and set it at optional position (oposite side).
(v) Cut insulation of “U” shape space.
Through this cutting, set and fix all wires by four (4) “clamps” and two (2) “straps”.
(vi) Close the previous “U” shape wiring space by insulation, and set the bottom plate again.
3. Insulate the drain pipe.
●
Be sure to insulate the drain socket and rigid PVC pipe installed indoors otherwise it may
cause dew condensation and water leakage.
※
After drainage test implementation, cover the drain socket part with pipe cover (small size), then
use the pipe cover (big size) to cover the pipe cover (small size), clamps and part of the drain
hose, and fix and wrap it with tapes to wrap and make joint part gapless.
0*#$
Drain test
●
After installation of drain pipe, make sure that drain system work in good condition and no
water leakage from joint and drain pan.
●
Do drain test even if installation of heating season.
●
For new building cases, make sure to complete the test before hanging the ceiling.
1. Remove the drain grommet, and pour water of about 1000cc into the drain pan in the
indoor unit by pump so as not to get the electrical component wet.
2. Make sure that water is drained out properly and there is no water leakage from any joints
of the drain pipe at the test.
3. Make sure to install the grommet back to original
place.
4. Insulate the drain pipe properly finally.
Pump
Remove grommet
Make sure to install
it back after test.
Insert the edge of water pump
hose in the drain pan.
Caution
●
Do not adjust the height by adjusting upper nuts. It will cause unexpected stress on the indoor
unit and it will lead to deformation of the unit, failure of attaching a panel, and generating noise
from the fan.
●
Make sure to install the indoor unit horizontally and set the gap between the unit underside and
the ceiling plane properly. Improper installation may cause air leakage, dew condensation,
water leakage and noise.
3. Make sure to install the indoor unit horizontally. Confirm the
levelness of the indoor unit with a level gauge or transpar-
ent hose filled with water. Keep the height difference at
both ends of the indoor unit within 3mm.
4. Tighten four upper nuts and fix the unit after height and
levelness adjustment.
Indoor unit
hose
!
/Ê "8
①
Wiring Location (Original)
②
Wiring Location (Optional)
After fix
○
, the modification of wiring length should be done, by
○
A
PJC012D200
Summary of Contents for FDE112KXE6A
Page 104: ... 102 ...
Page 111: ... 108 b Ceiling cassette 4 way Compact type FDTC Models All moddels B PJA003Z331 ...
Page 112: ... 109 c Ceiling cassette 2 way type FDTW Models FDTW28KXE6 45KXE6 56KXE6 B PJB001Z560 ...
Page 113: ... 110 Models FDTW71KXE6 90KXE6 B PJB001Z561 ...
Page 114: ... 111 Models FDTW112KXE6 140KXE6 B PJB001Z562 ...
Page 115: ... 112 d Ceiling cassette 1 way type FDTS Model FDTS45KXE6 A PJC001Z195 ...
Page 116: ... 113 Model FDTS71KXE6 A PJC001Z196 ...
Page 117: ... 114 e Ceiling cassette 1 way compact type FDTQ Models All models A PJC001Z190 ...
Page 118: ... 115 Models All models Duct panel A PJC001Z240 ...
Page 121: ... 118 Models FDU224KXE6 280KXE6 B PJD001Z230 ...
Page 123: ... 120 Models FDUM112KXE6 140KXE6 B PJR002Z259 ...
Page 124: ... 121 h Duct connected Ultra thin Low static pressure type FDQS Models All models C PJC001Z200 ...
Page 125: ... 122 i Wall mounted type FDK Models FDK22KXE6 28KXE6 36KXE6 45KXE6 56KXE6 B PHA000Z983 ...
Page 126: ... 123 Models FDK71KXE6 B PHA000Z984 ...
Page 127: ... 124 j Ceiling suspended type FDE Models FDE36KXE6A 45KXE6A 56KXE6A B PFA003Z826 ...
Page 128: ... 125 Models FDE71KXE6A 112KXE6A 140KXE6A B PFA003Z827 ...
Page 129: ... 126 k Floor standing with casing type FDFL Models All models B PGD000Z053 ...
Page 130: ... 127 l Floor standing without casing type FDFU Models All models A PGD000Z058 ...
Page 131: ... 128 m Duct Connected Compact and Flexible type FDUH Models All models A PJC001Z255 ...
Page 138: ... 135 ...
Page 139: ... 136 ...
Page 143: ... 140 b ...
Page 144: ... 141 ...
Page 191: ... 188 5 4 Installation of outdoor unit ...
Page 193: ... 190 ...
Page 194: ... 191 ...
Page 195: ... 192 ...
Page 196: ... 193 ...
Page 197: ... 194 ...
Page 198: ... 195 ...
Page 199: ... 196 ...
Page 200: ... 197 ...
Page 201: ... 198 ...
Page 202: ... 199 ...
Page 203: ... 200 ...
Page 204: ... 201 ...
Page 205: ... 202 ...
Page 206: ... 203 ...
Page 207: ... 204 ...
Page 208: ... 205 ...
Page 210: ... 207 ...
Page 211: ... 208 ...
Page 212: ... 209 ...
Page 215: ... 212 2 model type DIS model type HEAD ...
Page 216: ... 213 2 2 ...
Page 217: ... 214 2 2 2 2 2 ...