183
-
⑥
Control mode switching
●
The control content of indoor units can be switched in following way. ( is the default setting)
Switch No.
control content
SW1
Indoor unit address (tens place)
SW2
Indoor unit address (ones place)
SW3
Outdoor unit address (tens place)
SW4
Outdoor unit address (ones place)
SW5
-
1 ON Fixed previous version of Super Link protocol
OFF Automatic adjustment of Super Link protocol
SW5
-
2 Indoor unit address (hundreds place)
SW6
-
1 ~ 4 Model capacity setting
SW7
-
1 ON Operation check, Drain motor test run
OFF Normal operation
⑦
Function of CNT connector of indoor printed circuit board
●
CNT connector (local) vendor model
Connector : Made by molex 5264-06
Terminals : Made by molex 5263 T
⑧
Troubleshooting
+12
Indoor units control box
(Blue 6P)
Printed circuit board
Red
Black
Yellow
Blue
Brown
Orange
Remote start/stop kit
Note (1): Do not use the length over 2 meter
White
Black
Yellow
Blue
Brown
Orange
Orange
Input
power
Remote start / stop button or timer point
Output 1: Operation output (there is output when unit is in operation.)
Output 2: Heating output (there is output when operation MODE is HEATING.)
Output 3: Thermo ON output
Output 4: Inspection output (there is out put when unit is stopped by error.)
Input 5:
X
R5
OFF ON UNIT ON
X
R5
ON OFF UNIT OFF
X
R5
OFF ON Receiving pulse signal, "ON/OFF"
is reversed.
Factory set
Local set
Refer to instruction manuals of "Branching controller", when the indoor unit is
connected to "Heat recovery 3-pipe systems".
Display on
remote
controller
LED on indoor circuit board
Content
Off
E1
E2
E3
E5
E6
E7
E9
E10
E11
E12
E16
E18
E19
E28
Over E30
E63
Off
Off
Off
Off
Off
Off
Off
Off
Not sure
Not sure
blinking once
blinking once
blinking once
blinking once
blinking once
blinking once
blinking once
blinking once
Duplication of indoor address No. (can only be detected during operation)
Excess number of remote controllers (can only be detected during operation)
Continuous blinking
Continuous blinking
Continuous blinking
Continuous blinking
Continuous blinking
Continuous blinking
Continuous blinking
Continuous blinking
Continuous blinking
Continuous blinking
Continuous blinking
Continuous blinking
Continuous blinking
Continuous blinking
Continuous blinking
blinking twice
blinking twice
Continuous
blinking
Fault on the transmission between indoor
circuit board and remote control
Indoor computer abnormal
Outdoor power off or lack phase
There is no corresponding outdoor unit address.
Fault on outdoor-indoor transmission
Indoor air inhaling sensor broken or short-circuit
Float SW actions (only with FS)
Excess number of remote controller connections
The master indoor unit is not set properly.
Fan motor abnormal
The address configuration fault for master-slave indoor units.
Configuration fault on running checking model
Remote controller sensor interrupted
Outdoor unit checking (outdoor circuit board LED checking)
Emergency stop.
Super link
New specification
Old specification
Indoor unit address SW
Indoor No.
Outdoor No.
Indoor heat exchange sensor interrupted or short-circuit
Off
Normal
Fault on power, indoor power off or lack phase
Continuous blinking
red (checking) green (normal)
001
~
127 49
0
~
47 48
,
49
48
,
49 0
~
47
Error code of indoor unit
Note
Butt splice
CNT
Common
Output
Output
Output
Output
●
Function
A
(Application coverage
0.75
~
1.25mm
2
)
PSB012D922
The initial function setting for typical using is performed automatically for a remote control unit and an indoor unit by the door unit connected, when
remote controller and inside unit are connected.
As long as they are used in a typical manner, there wiil be no need to change the initial settings.
If you would like to change the initial setting marked “ ”, set your desired setting as for the selected item.
The procedure of functional setting is shown as the following diagram.
As for detail of setting, refer to the installation manual of remote controller.
[Flow of function setting]
Start
: While indoor unit do not operate, press “ ” (SET) and “ ” (MODE) button for 3 seconds at the same time.
Finalize : Press “ ” (SET) button.
Reset : Press “ ” (RESET) button.
Select : Press button.
End
: Press button.
It is possible to finish above setting on the way, and unfinished change of setting is unavailable.
“ ” : Initial settings
“ ” : Automatic criterion
As for detail, refer to the installation manual of remote controller.
⑤
Function Setting by Remote Controller
Only when plural indoor units are connected
Indoor No. selection
01
02
When you use at 50Hz area
When you use at 60Hz area
Automatic operation is impossible
(Remote controller function)
Temperature setting button is not working
02
03
03
04
04
05
05
06
06
07
07
08
09
08
10
09
11
10
12
11
13
12
13
14
14
15
16
15
17
16
18
19
Make permission/prohibition control of function be in effect.
Function
setting
Mode button is not working
On/Off button is not working
Fan speed button is not working
Louver button is not working
Timer button is not working
Heating preparation indication should not be indicated.
ON/OFF button
(finished)
The filter sign is indicated after running for 180 hours.
The filter sign is indicated after running for 600 hours.
The filter sign is indicated after running for 1000 hours.
The filter sign is indicated after running for 1000 hours, then it will be stopped by compulsion after 24 hours.
If to change the indoor function "04 ",
The remote control function "14 " should be changed accordingly.
Select the louver stop position in four.
The louver can stop at any positon.
With the VRF series, it is used to stop all indoor units connected with the same outdoor unit immediately.
When stop signal is inputed from remote on-off terminal "CNT-6", all indoor units are stopped immediately.
To be reset for pro3.0°C increase in temperature during heating.
To be reset for pro2.0°C increase in temperature during heating.
To be reset for pro1.0°C increase in temperature during heating.
To be reset pro2.0°C increase in return air temperature of indoor unit.
To be reset pro1.5°C increase in return air temperature of indoor unit.
To be reset pro1.0°C increase in return air temperature of indoor unit.
To be reset producing -1.0°C increase in return air temperature of indoor unit.
To be reset producing -1.5°C increase in return air temperature of indoor unit.
To be reset producing -2.0°C increase in return air temperature of indoor unit.
When heating thermostat is off, to be operated with low air flow.
When heating thermostat is off, to be operated with set air flow.
When heating thermostat is off, to be operated intermittently.
When heating thermostat is off, the fan stops.
When the remote thermistor is working, "FAN OFF" is set automatically.
Do not set when the indoor unit's thermistor is working.
Drain pump is on during cooling and dry.
Drain pump is on during cooling, dry and heating.
Drain pump is on during cooling, dry, heating and fan.
Drain pump is on during cooling, dry and fan.
After cooling is stopped or cooling thermostat is off, the fan does not perform extra operation.
After cooling is stopped or cooling thermostat is off, the fan perform extra operation for half an hour.
After cooling is stopped or cooling thermostat is off, the fan perform extra operation for an hour.
After cooling is stopped or cooling thermostat is off, the fan perform extra operation for six hours.
After heating is stopped or heating thermostat is off, the fan does not perform extra operation.
After heating is stopped or heating thermostat is off,the fan perform extra operation for half an hour.
After heating is stopped or heating thermostat is off,the fan perform extra operation for two hours.
After heating is stopped or heating thermostat is off, the fan perform extra operation for six hours.
During heating is stopped or heating thermostat is off, the fan perform intermittent operation for five minutes after twenty minutes' off
with low airflow.
During heating is stopped or heating thermostat is off, the fan perform intermittent operation for five minutes after five minutes' off with
low airflow.
Working only with the single split series.
To control frost prevention, the indoor fan tap is raised.
Change of indoor heat exchanger temperature to start frost prevention control.
Function
setting
Remote thermistor is not working.
Remote thermistor is working.
Remote thermistor is working, and to be set for pro3.0°C increase in temperature.
Remote thermistor is working, and to be set for pro2.0°C increase in temperature.
Remote thermistor is working, and to be set for pro1.0°C increase in temperature.
Remote thermistor is working, and to be set for producing -1.0°C increase in temperature.
Remote thermistor is working, and to be set for producing -2.0°C increase in temperature.
Remote thermistor is working, and to be set for producing -3.0°C increase in temperature.
Airflow of fan becomes the three speed of - -
.
Airflow of fan becomes the two speed of -
.
Airflow of fan becomes the two speed of -
.
Airflow of fan is fixed at one speed.
If you want to change the remote control function "14 ",
You must change the indoor function "04 " accordingly.
You can select the louver stop position in the four.
The louver can stop at any position.
Temperature indication is by degree C
Temperature indication is by degree F
If to change re-set with other indoor
unit, push AIRCON NO.
button, and indoor selection indication
(for example: I/U 000) is set back.
Consult the technical data etc. for each control details
Record and save the
setting
(Note3)
(Note2)
The functional setting
Connect the Single split series and the VRF series to the indoor board CNT and indoor board CND respectively. If a
ventilation device is connected, been geared with the motion of indoor device, the ventilation device is operated/stopped.
By connecting the ventilation device with the Single split series device to indoor board CNT, the VRF series device to
CND, you can operate/stop the ventilation device independently by the handling of ventilation button.
If you change the range of set temperature, the indication of set temperature will vary following the control.
If you change the range of set temperature, the indication of set temperature will not vary following the control, and
keep the set temperature.
If you input into the indoor printed circuit board CNT from outside, the indoor device will be operated independently
following the input from outside.
If you input into indoor printed circuit board CNT from outside, All units which share the same one remote control
network work following the input from outside.
During air-conditioner stopping push
(SET) + (MODE) button
simultaneously for 3 seconds
In normal working indication, indoor unit temperature is indicated instead of airflow.
(Only the master remote control can be indicated. )
Hi-Lo
Hi-MID
HI-MID-Lo
UH-Hi-MID
UH-MID
UH-Hi
STANDARD
FAN SPEED SET
Note 2: Fan setting of “HIGH SPEED”
Initial function setting of some indoor unit is “HIGH SPEED”
Indoor unit air flow setting
Fan tap
HIGH SPEED1, 2
Note 1: The initial setting marked “ ” is decided by connected indoor and outdoor unit, and is automatically defined as following table.
Function No.
Function 02 of
remote controller
Function 06 of
remote controller
Function 07 of
remote controller
Function 13 of
remote controller
Function 15 of
remote controller
Default
Model
"Auto-RUN" mode selectable indoor unit.
Item
Indoor unit with two or three step of air flow setting
Indoor unit with only one of air flow setting
Indoor unit with automatically swing louver
Indoor unit without automatically swing louver
Indoor unit with three step of air flow setting
Indoor unit with two step of air flow setting
Indoor unit with two step of air flow setting
Indoor unit with only one of air flow setting
Heat pump unite
Exclusive cooling unite
Indoor unit without "Auto-RUN" mode
(Indoor unit function)
The operation data is saved when the situation of abnormal operation happen,
and the data can be confirmed by remote controller.
[Operating procedure]
1. Press the button.
The display change “ ”
2. Once, press the button, and the display change “ ”.
3. Press the (SET) button and abnormal operation data mode is started.
4. When only one indoor unit is connected to remote controller, following is
displayed.
①
The case that there is history of abnormal operation.
Error code and “ ” is displayed.
[Example]: [E8] (ERROR CODE)
“ ” is displayed (blinking indication during data loading).
Next, the abnormal operation data of the indoor unit will be displayed.
Skip to step 7.
②
The case that there is not history of abnormal operation.
“ ” is displayed for 3 seconds and this mode is closed.
5. When plural indoor units is connected, following is displayed.
①
The case that there is history of abnormal operation.
Error code and the smallest address number of indoor unit among all
connected indoor unit is displayed.
[Example]: [E8] (ERROR CODE)
“ ” blinking
②
The case that there is not history of abnormal operation.
Only address number is displayed.
6. Select the indoor unit number you would like to have data displayed with the
button.
7. Determine the indoor unit number with the (SET) button.
[Example]: [E8] (ERROR CODE)
“ ” (The address of selected indoor unit is blinking for 2 seconds.)
[E8] “ ” (A blinking indication appears while data loaded.)
Next, the abnormal operation data is indicated.
If the indoor unit doing normal operation is selected, “ ” is displayed for 3 seconds and address of indoor unit is displayed.
8. By the button, the abnormal operation data is displayed.
Displayed data item is based on
④
Trial operation
.
※
Depending on models, the items that do not have corresponding data are not displayed.
9. To display the data of a different indoor unit, press the AIR CON No. button, which allows you to go back to the indoor unit slection screen.
10.Pressing the button will stop displaying data.
Pressing the (RESET) button during remote control unit operation will undo your last operation and allow you to go back to the previous screen.
◎
If two (2) remote controllers are connected to one (1) inside unit, only the master controller is available for trial operation and confirmation of operation
data. (The slave remote controller is not available.)
A
PSB012D922
Summary of Contents for FDE112KXE6A
Page 104: ... 102 ...
Page 111: ... 108 b Ceiling cassette 4 way Compact type FDTC Models All moddels B PJA003Z331 ...
Page 112: ... 109 c Ceiling cassette 2 way type FDTW Models FDTW28KXE6 45KXE6 56KXE6 B PJB001Z560 ...
Page 113: ... 110 Models FDTW71KXE6 90KXE6 B PJB001Z561 ...
Page 114: ... 111 Models FDTW112KXE6 140KXE6 B PJB001Z562 ...
Page 115: ... 112 d Ceiling cassette 1 way type FDTS Model FDTS45KXE6 A PJC001Z195 ...
Page 116: ... 113 Model FDTS71KXE6 A PJC001Z196 ...
Page 117: ... 114 e Ceiling cassette 1 way compact type FDTQ Models All models A PJC001Z190 ...
Page 118: ... 115 Models All models Duct panel A PJC001Z240 ...
Page 121: ... 118 Models FDU224KXE6 280KXE6 B PJD001Z230 ...
Page 123: ... 120 Models FDUM112KXE6 140KXE6 B PJR002Z259 ...
Page 124: ... 121 h Duct connected Ultra thin Low static pressure type FDQS Models All models C PJC001Z200 ...
Page 125: ... 122 i Wall mounted type FDK Models FDK22KXE6 28KXE6 36KXE6 45KXE6 56KXE6 B PHA000Z983 ...
Page 126: ... 123 Models FDK71KXE6 B PHA000Z984 ...
Page 127: ... 124 j Ceiling suspended type FDE Models FDE36KXE6A 45KXE6A 56KXE6A B PFA003Z826 ...
Page 128: ... 125 Models FDE71KXE6A 112KXE6A 140KXE6A B PFA003Z827 ...
Page 129: ... 126 k Floor standing with casing type FDFL Models All models B PGD000Z053 ...
Page 130: ... 127 l Floor standing without casing type FDFU Models All models A PGD000Z058 ...
Page 131: ... 128 m Duct Connected Compact and Flexible type FDUH Models All models A PJC001Z255 ...
Page 138: ... 135 ...
Page 139: ... 136 ...
Page 143: ... 140 b ...
Page 144: ... 141 ...
Page 191: ... 188 5 4 Installation of outdoor unit ...
Page 193: ... 190 ...
Page 194: ... 191 ...
Page 195: ... 192 ...
Page 196: ... 193 ...
Page 197: ... 194 ...
Page 198: ... 195 ...
Page 199: ... 196 ...
Page 200: ... 197 ...
Page 201: ... 198 ...
Page 202: ... 199 ...
Page 203: ... 200 ...
Page 204: ... 201 ...
Page 205: ... 202 ...
Page 206: ... 203 ...
Page 207: ... 204 ...
Page 208: ... 205 ...
Page 210: ... 207 ...
Page 211: ... 208 ...
Page 212: ... 209 ...
Page 215: ... 212 2 model type DIS model type HEAD ...
Page 216: ... 213 2 2 ...
Page 217: ... 214 2 2 2 2 2 ...