17
-
(9) Protective control
(a) Discharge pipe temperature control (Master unit/slave unit)
(i)
If the discharge pipe temperature (detected with Tho-D1, D2) exceeds the set value, it makes the compressor capacity
control performed and the solenoid valves SV1, 2 (for cooling down the compressor) open according to the compressor
Hz in order to suppress the discharge pipe temperature rising.
1) Compressor capacity control
2) Solenoid valve (SV1, 2) control for cooling down compressor.
< ON conditions >
①
In the zone A: SV1 is turned ON when Td1 >= 115°C. SV2 is turned ON when Td2 >= 115°C.
②
In the zone B: SV1 is turned ON when Td1 >= 110°C. SV2 is turned ON when Td2 >= 110°C.
< OFF conditions>
①
In the zone A: SV1 is turned OFF when Td1 <= 108°C. SV2 is turned OFF when Td2 >= 108°C.
②
In the zone B: SV1 is turned OFF when Td1 <= 103°C. SV2 is turned OFF when Td2 <= 103°C.
(ii)
Discharge pipe temperature control and Error display
1) When the discharger temperature exceeds 130°C or higher for 2 seconds continuously, it makes the compressor
stopped. And when the discharge pipe temperature decreases to lower than 90°C, it makes the compressor restarted
automatcally.
2) If this control [mentioned in (ii)-1)] is activates 5 times within 60 minutes, it makes the compressor anomalous
stop and displays E36, In case of anomalous stop, it cannot be operated again until the discharge pipe temperature
decreases to lower than 90°C for 60 minutes continuously.
(b) Current safe control
• Current safe control is done by both Master and Slave unit individually.
< Compressor capacity control >
1) Compressor frequency is controlled by detecting the inverter primary current (T-phase) and the inverter secondary
current.
However under the following operating status
①
and
②
, it does not detect the inverter current.
①
Actual compressor frequency N < 20Hz
②
During the period that actual compressor frequency is decreasing or during the period of 1 second after the actual
compressor frequency decreased.
110
120
Discharge pipe temperature (°C) [Tho-D1, D2]
Retention
Compressor capacity is
reduced at 5-second intervals
Reset
40HZ
(33HZ)
45HZ
(38HZ)
• zone A
• zone B
zone A
zone B
108
115
Discharge pipe temperature (°C) [Tho-D1, D2]
ON
ON
SV1 : OFF
SV2 : OFF
SV1 : OFF
SV2 : OFF
103
110
Discharge pipe temperature (°C) [Tho-D1, D2]
Note (1) Value in ( ) are for the models FDC615, 680KXE6 and
FDC1180~1360KXE6
Summary of Contents for FDE112KXE6A
Page 104: ... 102 ...
Page 111: ... 108 b Ceiling cassette 4 way Compact type FDTC Models All moddels B PJA003Z331 ...
Page 112: ... 109 c Ceiling cassette 2 way type FDTW Models FDTW28KXE6 45KXE6 56KXE6 B PJB001Z560 ...
Page 113: ... 110 Models FDTW71KXE6 90KXE6 B PJB001Z561 ...
Page 114: ... 111 Models FDTW112KXE6 140KXE6 B PJB001Z562 ...
Page 115: ... 112 d Ceiling cassette 1 way type FDTS Model FDTS45KXE6 A PJC001Z195 ...
Page 116: ... 113 Model FDTS71KXE6 A PJC001Z196 ...
Page 117: ... 114 e Ceiling cassette 1 way compact type FDTQ Models All models A PJC001Z190 ...
Page 118: ... 115 Models All models Duct panel A PJC001Z240 ...
Page 121: ... 118 Models FDU224KXE6 280KXE6 B PJD001Z230 ...
Page 123: ... 120 Models FDUM112KXE6 140KXE6 B PJR002Z259 ...
Page 124: ... 121 h Duct connected Ultra thin Low static pressure type FDQS Models All models C PJC001Z200 ...
Page 125: ... 122 i Wall mounted type FDK Models FDK22KXE6 28KXE6 36KXE6 45KXE6 56KXE6 B PHA000Z983 ...
Page 126: ... 123 Models FDK71KXE6 B PHA000Z984 ...
Page 127: ... 124 j Ceiling suspended type FDE Models FDE36KXE6A 45KXE6A 56KXE6A B PFA003Z826 ...
Page 128: ... 125 Models FDE71KXE6A 112KXE6A 140KXE6A B PFA003Z827 ...
Page 129: ... 126 k Floor standing with casing type FDFL Models All models B PGD000Z053 ...
Page 130: ... 127 l Floor standing without casing type FDFU Models All models A PGD000Z058 ...
Page 131: ... 128 m Duct Connected Compact and Flexible type FDUH Models All models A PJC001Z255 ...
Page 138: ... 135 ...
Page 139: ... 136 ...
Page 143: ... 140 b ...
Page 144: ... 141 ...
Page 191: ... 188 5 4 Installation of outdoor unit ...
Page 193: ... 190 ...
Page 194: ... 191 ...
Page 195: ... 192 ...
Page 196: ... 193 ...
Page 197: ... 194 ...
Page 198: ... 195 ...
Page 199: ... 196 ...
Page 200: ... 197 ...
Page 201: ... 198 ...
Page 202: ... 199 ...
Page 203: ... 200 ...
Page 204: ... 201 ...
Page 205: ... 202 ...
Page 206: ... 203 ...
Page 207: ... 204 ...
Page 208: ... 205 ...
Page 210: ... 207 ...
Page 211: ... 208 ...
Page 212: ... 209 ...
Page 215: ... 212 2 model type DIS model type HEAD ...
Page 216: ... 213 2 2 ...
Page 217: ... 214 2 2 2 2 2 ...