24
-
(1) External input and demand input (Master unit/Slave unit)
(a) Operation permission or prohibition mode
(Note) Following explanation is based on using CnS1 terminal and setting function [P11]-[0] with 7-segment display.
However other terminals can be used with following function setting of 7-segment display.
CnS2: [P12]-[0]
CnG1: [P13]-[0]
CnG2: [P14]-[0]
1) Opearation permission or prohibition mode is switched with the connector (CnS1) and the Jumper wire (J13) on the
outdoor control PCB after setting function [P11]-[0] (Factory setting) with 7-segment display
J13: Switching of CnS1 input method
J13 shorted: Level input by CnS1
J13 open : Pulse input by CnS1
2) Operation permission/prohibition control by the external input CnS1 to outdoor unit.
Note (1) Factory setting J13: Shorted, CnS1: Shorted (Short pin is connected)
3) The operation condition is displayed on the LCD of remote controller and it is transferred to optional centralized controller
4) When the operation command from remote controller is not accepted by this control, "Center" is displayed on the
LCD of remote controller. (See item 5 mentioned next page)
(B) Optional controls
• External input terminal
①
4 External input terminals (CnS1, CnS2, CnG1 and CnG2) are provided. (See fig-1)
②
Each external input terminal can be changed its function by allotting the external input function No. of P11-P14
selected
with 7-segment respectively. (External input functions of the code P11-P14 are shown in fig-2)
③
The following function is effective, when the external input function of PXX-"X" is allotted and the signal is input
to the
external terminal of CnXX.
(Example) If CnS1 terminal is used for demand control (pulse input), allot the "1" of P11 and open J13, and if CnS2 terminal is
used for demand control (level input), allot the "1" of P12 and short J13.
(Note) More than one function cannot operate at same time.
*1 "Setting" means;
Master : Set only the master unit. (No necessary to set the slave unit)
Master/Slave: Set both master/slave unit same.
External input terminal
External input function allotment of 7-segement
Terminal
Specification
Factory setting
Code
Function No.
Factory setting
CnS1
No volatage contact (DC12V)
Shorted
P11
"0"-"9"
"0"
CnS2
No volatage contact (DC12V)
Shorted
P12
"0"-"9"
"1"
CnG1
No volatage contact (DC12V)
Open
P13
"0"-"9"
"2"
CnG2
No volatage contact (DC12V)
Open
P14
"0"-"9"
"3"
Fig-1
Setting *1
Allotment of external input function (P11-P14) External input terminal
shorted
External input terminal
open
Master unit
"0": External operation input
Operation permission
Operation prohibition
Master unit
"1": Demand input
Invalid
Valid
Master unit
"2": Forced cooling/heating input
Heating
Cooling
Master unit
"3": Silent mode input 1
Valid
Invalid
Master unit
"4": Spare
-
-
Master/Slave unit "5": Outdoor fan snow protection control input
Valid
Invalid
Master unit
"6": Test run external input 1 (Equal to SW5-1)
Test run start
Normal operation
Master unit
"7": Test run external input 2 (Equal to SW5-2)
Cooling test run
Heating test run
Master unit
"8": Silent mode input 2
Valid
Invalid
Master unit
"9": Spare
-
-
Fig-2
Input: CnS1
Switching CnS1
input method:J13
CnS1: Switching operation
permission/prohibition mode
Shorted (Level input)
Shorted
Shorted
Open
Open
Operation prohibition mode
Operation permission mode
Operation permission mode
Operation prohibition mode
—
(NOP)
Switching operation permission/
Operation prohibitiion mode (Reversal)
Shorted (Level input)
Open (Pulse input)
Open (Pulse input)
Summary of Contents for FDE112KXE6A
Page 104: ... 102 ...
Page 111: ... 108 b Ceiling cassette 4 way Compact type FDTC Models All moddels B PJA003Z331 ...
Page 112: ... 109 c Ceiling cassette 2 way type FDTW Models FDTW28KXE6 45KXE6 56KXE6 B PJB001Z560 ...
Page 113: ... 110 Models FDTW71KXE6 90KXE6 B PJB001Z561 ...
Page 114: ... 111 Models FDTW112KXE6 140KXE6 B PJB001Z562 ...
Page 115: ... 112 d Ceiling cassette 1 way type FDTS Model FDTS45KXE6 A PJC001Z195 ...
Page 116: ... 113 Model FDTS71KXE6 A PJC001Z196 ...
Page 117: ... 114 e Ceiling cassette 1 way compact type FDTQ Models All models A PJC001Z190 ...
Page 118: ... 115 Models All models Duct panel A PJC001Z240 ...
Page 121: ... 118 Models FDU224KXE6 280KXE6 B PJD001Z230 ...
Page 123: ... 120 Models FDUM112KXE6 140KXE6 B PJR002Z259 ...
Page 124: ... 121 h Duct connected Ultra thin Low static pressure type FDQS Models All models C PJC001Z200 ...
Page 125: ... 122 i Wall mounted type FDK Models FDK22KXE6 28KXE6 36KXE6 45KXE6 56KXE6 B PHA000Z983 ...
Page 126: ... 123 Models FDK71KXE6 B PHA000Z984 ...
Page 127: ... 124 j Ceiling suspended type FDE Models FDE36KXE6A 45KXE6A 56KXE6A B PFA003Z826 ...
Page 128: ... 125 Models FDE71KXE6A 112KXE6A 140KXE6A B PFA003Z827 ...
Page 129: ... 126 k Floor standing with casing type FDFL Models All models B PGD000Z053 ...
Page 130: ... 127 l Floor standing without casing type FDFU Models All models A PGD000Z058 ...
Page 131: ... 128 m Duct Connected Compact and Flexible type FDUH Models All models A PJC001Z255 ...
Page 138: ... 135 ...
Page 139: ... 136 ...
Page 143: ... 140 b ...
Page 144: ... 141 ...
Page 191: ... 188 5 4 Installation of outdoor unit ...
Page 193: ... 190 ...
Page 194: ... 191 ...
Page 195: ... 192 ...
Page 196: ... 193 ...
Page 197: ... 194 ...
Page 198: ... 195 ...
Page 199: ... 196 ...
Page 200: ... 197 ...
Page 201: ... 198 ...
Page 202: ... 199 ...
Page 203: ... 200 ...
Page 204: ... 201 ...
Page 205: ... 202 ...
Page 206: ... 203 ...
Page 207: ... 204 ...
Page 208: ... 205 ...
Page 210: ... 207 ...
Page 211: ... 208 ...
Page 212: ... 209 ...
Page 215: ... 212 2 model type DIS model type HEAD ...
Page 216: ... 213 2 2 ...
Page 217: ... 214 2 2 2 2 2 ...