(b) Demand control
(Note) Following explanation is based on using CnS2 terminal and setting function [P12]-[1] with 7-segment display.
However other terminals can be used with following function setting of 7-segment display
CnS1: [P11]-[1]
CnG1: [P13]-[1]
CnG2: [P14]-[1]
1) Demand control or normal control is switched with the connector (CnS2) and the jumper wire (J13) on the outdoor
control PCB after setting function [P12]-[1] (Factory setting) with 7-segment display.
J13: Switching of CnS2 input method
J13 shorted: Level input by CnS2
J13 open : Pulse input by CnS2
2) Demand control/Normal operation by the external input CnS2 to outdoor unit.
Note (1) Factory setting J13: Shorted, CnS2: Shorted (Short pin is connected)
3) The operation condition is displayed on the LCD of remote controller and it is transferred to optional centralized
controller
①
J13 − Shorted
②
J13 - Open
5) CnS1 performs the following operation according to switching the jumper wire (J13) shorted or open. In case of
pulse input, the pulse width is 500ms or larger.
PUSH
CnS1 input OFF (Open)
Remote controller operation
Remote controller display
Air-conditioner operation/stop
PUSH
PUSH
PUSH
OFF
Center
Remote
ON (Shorted)
Center
OFF
OFF (Open)
Air-conditioner ON OK
OFF
ON
ON
Remote controller operation
Remote controller display
Air-conditioner operation/stop
Center
Center
Center
Remote
Remote
Air-conditioner ON OK
CnS1 input
OFF
OFF
ON
ON
OFF
OFF
ON
OFF
ON
PUSH
PUSH
PUSH
PUSH
PUSH
Input: CnS2
Switching CnS2
input method:J13
CnS2: Switching operation
permission/prohibition mode
Shorted (Level input)
Shorted
Shorted
Open
Open
Demand control
Normal operation
Normal control
Demand operation
—
(NOP)
Switching Demand control/
Normal operation (Reversal)
Shorted (Level input)
Open (Pulse input)
Open (Pulse input)
Summary of Contents for FDE112KXE6A
Page 104: ... 102 ...
Page 111: ... 108 b Ceiling cassette 4 way Compact type FDTC Models All moddels B PJA003Z331 ...
Page 112: ... 109 c Ceiling cassette 2 way type FDTW Models FDTW28KXE6 45KXE6 56KXE6 B PJB001Z560 ...
Page 113: ... 110 Models FDTW71KXE6 90KXE6 B PJB001Z561 ...
Page 114: ... 111 Models FDTW112KXE6 140KXE6 B PJB001Z562 ...
Page 115: ... 112 d Ceiling cassette 1 way type FDTS Model FDTS45KXE6 A PJC001Z195 ...
Page 116: ... 113 Model FDTS71KXE6 A PJC001Z196 ...
Page 117: ... 114 e Ceiling cassette 1 way compact type FDTQ Models All models A PJC001Z190 ...
Page 118: ... 115 Models All models Duct panel A PJC001Z240 ...
Page 121: ... 118 Models FDU224KXE6 280KXE6 B PJD001Z230 ...
Page 123: ... 120 Models FDUM112KXE6 140KXE6 B PJR002Z259 ...
Page 124: ... 121 h Duct connected Ultra thin Low static pressure type FDQS Models All models C PJC001Z200 ...
Page 125: ... 122 i Wall mounted type FDK Models FDK22KXE6 28KXE6 36KXE6 45KXE6 56KXE6 B PHA000Z983 ...
Page 126: ... 123 Models FDK71KXE6 B PHA000Z984 ...
Page 127: ... 124 j Ceiling suspended type FDE Models FDE36KXE6A 45KXE6A 56KXE6A B PFA003Z826 ...
Page 128: ... 125 Models FDE71KXE6A 112KXE6A 140KXE6A B PFA003Z827 ...
Page 129: ... 126 k Floor standing with casing type FDFL Models All models B PGD000Z053 ...
Page 130: ... 127 l Floor standing without casing type FDFU Models All models A PGD000Z058 ...
Page 131: ... 128 m Duct Connected Compact and Flexible type FDUH Models All models A PJC001Z255 ...
Page 138: ... 135 ...
Page 139: ... 136 ...
Page 143: ... 140 b ...
Page 144: ... 141 ...
Page 191: ... 188 5 4 Installation of outdoor unit ...
Page 193: ... 190 ...
Page 194: ... 191 ...
Page 195: ... 192 ...
Page 196: ... 193 ...
Page 197: ... 194 ...
Page 198: ... 195 ...
Page 199: ... 196 ...
Page 200: ... 197 ...
Page 201: ... 198 ...
Page 202: ... 199 ...
Page 203: ... 200 ...
Page 204: ... 201 ...
Page 205: ... 202 ...
Page 206: ... 203 ...
Page 207: ... 204 ...
Page 208: ... 205 ...
Page 210: ... 207 ...
Page 211: ... 208 ...
Page 212: ... 209 ...
Page 215: ... 212 2 model type DIS model type HEAD ...
Page 216: ... 213 2 2 ...
Page 217: ... 214 2 2 2 2 2 ...