30
-
(7) Pump down control (Master unit/slave unit)
This control is for recovering refrigerrant to outdoor unit quickly in case of replacement or relocation of the outdoor unit.
(a) This control is performed from the master unit side. It cannot be controlled from the slave unit side. If this control is at
-
tempted from the slave unit side, the following codes are displayed on the 7-segment LED of the slave unit.
Note (1) The display returns to normal if the pump-down control switch is reset.
(b) Pump down operation can be performed with the operation of 3 dip switches SW5-1(Test run switch), SW5-2 (Test run
operation mode) and SW5-3 (Pump down switch)
(c) Pump down procedure
1) Shut the liquid side service valve on the outdoor units
2) Turn SW5-2 (test run operation mode) ON (cooling)
3) Turn SW5-3 (pump down switch) ON
4) Turn SW5-1 (test run switch) ON
(d) End condition
If any of the following conditions is satisfied, this control ends.
(i) If the low pressure (LP) ≤ 0.01MPa is detected for 5 seconds continuously, this control ends normally, and indicates
followings
①
Red LED: Keeps lighting
②
Green LED: Keeps flashing
③
7-segment display: PdE
④
Remote controller: Stop
(ii) Anomalous all stop by the error detection control
(iii) If the cumulative compressor operation time under pump down control is 15minutes (End control because time is
up), this control ends and indicates followings
①
Red LED: Stays OFF
②
Green LED: Keeps flashing
③
7-segment display: No display
④
Remote controller: Stop
(iv) When any of setting switch (SW5-1, SW5-2, SW5-3) is turned OFF during pump down control.
(Note) Even if only SW5-3 is turned OFF, it is not recognized as the cooling test run mode and it stops.
Code display area
Data display area
Contents of invalid operation
OPE
10
Setting from the slave unit is invalid
Summary of Contents for FDE112KXE6A
Page 104: ... 102 ...
Page 111: ... 108 b Ceiling cassette 4 way Compact type FDTC Models All moddels B PJA003Z331 ...
Page 112: ... 109 c Ceiling cassette 2 way type FDTW Models FDTW28KXE6 45KXE6 56KXE6 B PJB001Z560 ...
Page 113: ... 110 Models FDTW71KXE6 90KXE6 B PJB001Z561 ...
Page 114: ... 111 Models FDTW112KXE6 140KXE6 B PJB001Z562 ...
Page 115: ... 112 d Ceiling cassette 1 way type FDTS Model FDTS45KXE6 A PJC001Z195 ...
Page 116: ... 113 Model FDTS71KXE6 A PJC001Z196 ...
Page 117: ... 114 e Ceiling cassette 1 way compact type FDTQ Models All models A PJC001Z190 ...
Page 118: ... 115 Models All models Duct panel A PJC001Z240 ...
Page 121: ... 118 Models FDU224KXE6 280KXE6 B PJD001Z230 ...
Page 123: ... 120 Models FDUM112KXE6 140KXE6 B PJR002Z259 ...
Page 124: ... 121 h Duct connected Ultra thin Low static pressure type FDQS Models All models C PJC001Z200 ...
Page 125: ... 122 i Wall mounted type FDK Models FDK22KXE6 28KXE6 36KXE6 45KXE6 56KXE6 B PHA000Z983 ...
Page 126: ... 123 Models FDK71KXE6 B PHA000Z984 ...
Page 127: ... 124 j Ceiling suspended type FDE Models FDE36KXE6A 45KXE6A 56KXE6A B PFA003Z826 ...
Page 128: ... 125 Models FDE71KXE6A 112KXE6A 140KXE6A B PFA003Z827 ...
Page 129: ... 126 k Floor standing with casing type FDFL Models All models B PGD000Z053 ...
Page 130: ... 127 l Floor standing without casing type FDFU Models All models A PGD000Z058 ...
Page 131: ... 128 m Duct Connected Compact and Flexible type FDUH Models All models A PJC001Z255 ...
Page 138: ... 135 ...
Page 139: ... 136 ...
Page 143: ... 140 b ...
Page 144: ... 141 ...
Page 191: ... 188 5 4 Installation of outdoor unit ...
Page 193: ... 190 ...
Page 194: ... 191 ...
Page 195: ... 192 ...
Page 196: ... 193 ...
Page 197: ... 194 ...
Page 198: ... 195 ...
Page 199: ... 196 ...
Page 200: ... 197 ...
Page 201: ... 198 ...
Page 202: ... 199 ...
Page 203: ... 200 ...
Page 204: ... 201 ...
Page 205: ... 202 ...
Page 206: ... 203 ...
Page 207: ... 204 ...
Page 208: ... 205 ...
Page 210: ... 207 ...
Page 211: ... 208 ...
Page 212: ... 209 ...
Page 215: ... 212 2 model type DIS model type HEAD ...
Page 216: ... 213 2 2 ...
Page 217: ... 214 2 2 2 2 2 ...