Error code
Remote controller:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
None
Earth leakage breaker activated
Stays Off Stays Off
Stays Off Stays Off
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
NO
NO
Is insulation
of respective harnesses OK?
YES
Check of the outdoor unit grounding wire and earth leakage breaker
�
Run an independent grounding wire from the grounding screw
of outdoor unit to the grounding terminal on the distribution
panel. (Do not connect to another grounding wire.)
�
In order to prevent malfunction of the earth leakage breaker
itself, confirm the conformity of high harmonic regulation.
* Insulation resistance of compressor
• Immediately after installation or when the unit has been left
for long period without power supply, the insulation
resistance may drop to a few M
Ω
because of refrigerant
migrated in the compressor.
When the earth leakage breaker is activated at lower insulation
resistance, check the following points.
�
6 hours after power ON, check if the insulation resistance
recovers to normal.
When power ON, crankcase heater heat up compressor and
evaporates the refrigerant migrated in the compressor.
�
Check if the earth leakage breaker is conformed to higher
harmonic regulation or not.
Since the unit has inverter, it is necessary to use components
conformed to high harmonic regulation in order to prevent
malfunction of earth leakage breaker.
YES
Check the outdoor unit grounding
wire and earth leakage breaker
Is any hamess bitten
between pannel and casing
or etc?
NO
YES
Are the
insulation resistance
and and coil resistance of
compressor OK?
Replace compressor. *
Secure insulation
resistance.
Secure insulation
resistance.
2. Error detection method
3. Condition of error displayed
4. Presumable cause
• Compressor anomaly
• Noise
Note:
Summary of Contents for FDE112KXE6A
Page 104: ... 102 ...
Page 111: ... 108 b Ceiling cassette 4 way Compact type FDTC Models All moddels B PJA003Z331 ...
Page 112: ... 109 c Ceiling cassette 2 way type FDTW Models FDTW28KXE6 45KXE6 56KXE6 B PJB001Z560 ...
Page 113: ... 110 Models FDTW71KXE6 90KXE6 B PJB001Z561 ...
Page 114: ... 111 Models FDTW112KXE6 140KXE6 B PJB001Z562 ...
Page 115: ... 112 d Ceiling cassette 1 way type FDTS Model FDTS45KXE6 A PJC001Z195 ...
Page 116: ... 113 Model FDTS71KXE6 A PJC001Z196 ...
Page 117: ... 114 e Ceiling cassette 1 way compact type FDTQ Models All models A PJC001Z190 ...
Page 118: ... 115 Models All models Duct panel A PJC001Z240 ...
Page 121: ... 118 Models FDU224KXE6 280KXE6 B PJD001Z230 ...
Page 123: ... 120 Models FDUM112KXE6 140KXE6 B PJR002Z259 ...
Page 124: ... 121 h Duct connected Ultra thin Low static pressure type FDQS Models All models C PJC001Z200 ...
Page 125: ... 122 i Wall mounted type FDK Models FDK22KXE6 28KXE6 36KXE6 45KXE6 56KXE6 B PHA000Z983 ...
Page 126: ... 123 Models FDK71KXE6 B PHA000Z984 ...
Page 127: ... 124 j Ceiling suspended type FDE Models FDE36KXE6A 45KXE6A 56KXE6A B PFA003Z826 ...
Page 128: ... 125 Models FDE71KXE6A 112KXE6A 140KXE6A B PFA003Z827 ...
Page 129: ... 126 k Floor standing with casing type FDFL Models All models B PGD000Z053 ...
Page 130: ... 127 l Floor standing without casing type FDFU Models All models A PGD000Z058 ...
Page 131: ... 128 m Duct Connected Compact and Flexible type FDUH Models All models A PJC001Z255 ...
Page 138: ... 135 ...
Page 139: ... 136 ...
Page 143: ... 140 b ...
Page 144: ... 141 ...
Page 191: ... 188 5 4 Installation of outdoor unit ...
Page 193: ... 190 ...
Page 194: ... 191 ...
Page 195: ... 192 ...
Page 196: ... 193 ...
Page 197: ... 194 ...
Page 198: ... 195 ...
Page 199: ... 196 ...
Page 200: ... 197 ...
Page 201: ... 198 ...
Page 202: ... 199 ...
Page 203: ... 200 ...
Page 204: ... 201 ...
Page 205: ... 202 ...
Page 206: ... 203 ...
Page 207: ... 204 ...
Page 208: ... 205 ...
Page 210: ... 207 ...
Page 211: ... 208 ...
Page 212: ... 209 ...
Page 215: ... 212 2 model type DIS model type HEAD ...
Page 216: ... 213 2 2 ...
Page 217: ... 214 2 2 2 2 2 ...