(8)
Filter sign
As the operation time (when ON/OFF switch is at ON) accumulates to 180 hours (1), “Filter cleaning” is displayed on the
remote controller. (This is also displayed when the unit is in trouble and under the centralized control, regardless of ON/OFF)
Note (1) Time setting for the filter sign can be made as shown below using the indoor function of wired remote controller “Filter sign setting”. (It is set at 1 at the
shipping from factory.)
Filter Sign Setting
Setting 1
Setting 2
Setting 3
Setting 4
Function
Setting time: 180 hrs (Factory default)
Setting time: 600 hrs
Setting time: 1,000 hrs
Setting time: 1,000 hrs (Unit stop)
(2)
(2) After the setting time has elapsed, the “Filter cleaning” is displayed and, after operating for 24 hours further (counted also during the stop), the unit stops.
(9)
Auto swing control [Applicable model: FDT, FDTC, FDTW, FDTS, FDTQ (Excepted duct panel model) FDK
and FDE]
(a) Louver control
(i) Press the [Louver] button to operate the swing louver when the air conditioner is operating.
“Auto wind direction” is displayed for 3 seconds and then the swing louver moves up and down continuously.
(ii) To fix the swing louver at a position, press one time the [Louver] button while the swing louver is moving so that
four stop positions are displayed one after another per second.
When a desired stop position is displayed, press the [Louver] button again. The display stops, changes to show the
“Louver stop” for 5 seconds and then the swing louver stops.
(iii) Louver operation at the power on
The louver swings one time automatically (without operating the remote controller) at the power on.
This allows inputting the louver motor (LM) position, which is necessary for the microcomputer to recognize the
louver position.
Note (1) If you press the Louver button, the swing motion is displayed on the louver position LCD for 10 second. The display changes to the “Auto wind
direction” display 3 seconds later.
(b) Automatic louver level setting during heating
While hot start operation and heating thermostat OFF operation, the louver keeps the level position (In order to prevent
the cold draft) whether the auto swing switch is operated or not (auto swing or louver stop), The louver position display
LCD continues to show the display which has been shown before entering this control.
(c) Louver-free stop control
When the louver-free stop has been selected with the indoor function of wired remote controller “Louver control setting”,
the louver motor stops when it receives the stop signal from the remote controller. If the auto swing signal is received
from the remote controller, the auto swing will start from the position where it was before the stop.
Note (1) When the indoor function of wired remote controller “Louver control setting” has been switched, switch also the remote control function “Louver
control setting” in the same way.
(10) Compressor inching prevention control
(a) 3-minutes timer
When the compressor has been stopped by the thermostat, remote controller operation switch or anomalous condition, its
restart will be inhibited for 3 minutes. However, the 3-minute timer is invalidated at the power on.
(b) 3-minutes forced operation timer
• Compressor will not stop for 3 minutes after the compressor ON. However, it stops immediately when the thermostat is
turned OFF by the stop command by means of the ON/OFF switch or the change of operation mode.
• If the thermostat is turned OFF during the forced compressor operation in heating mode, the louver position (with the
auto swing) is returned to the level position.
Note (1) The compressor stops when it has entered the protective control.
Summary of Contents for FDE112KXE6A
Page 104: ... 102 ...
Page 111: ... 108 b Ceiling cassette 4 way Compact type FDTC Models All moddels B PJA003Z331 ...
Page 112: ... 109 c Ceiling cassette 2 way type FDTW Models FDTW28KXE6 45KXE6 56KXE6 B PJB001Z560 ...
Page 113: ... 110 Models FDTW71KXE6 90KXE6 B PJB001Z561 ...
Page 114: ... 111 Models FDTW112KXE6 140KXE6 B PJB001Z562 ...
Page 115: ... 112 d Ceiling cassette 1 way type FDTS Model FDTS45KXE6 A PJC001Z195 ...
Page 116: ... 113 Model FDTS71KXE6 A PJC001Z196 ...
Page 117: ... 114 e Ceiling cassette 1 way compact type FDTQ Models All models A PJC001Z190 ...
Page 118: ... 115 Models All models Duct panel A PJC001Z240 ...
Page 121: ... 118 Models FDU224KXE6 280KXE6 B PJD001Z230 ...
Page 123: ... 120 Models FDUM112KXE6 140KXE6 B PJR002Z259 ...
Page 124: ... 121 h Duct connected Ultra thin Low static pressure type FDQS Models All models C PJC001Z200 ...
Page 125: ... 122 i Wall mounted type FDK Models FDK22KXE6 28KXE6 36KXE6 45KXE6 56KXE6 B PHA000Z983 ...
Page 126: ... 123 Models FDK71KXE6 B PHA000Z984 ...
Page 127: ... 124 j Ceiling suspended type FDE Models FDE36KXE6A 45KXE6A 56KXE6A B PFA003Z826 ...
Page 128: ... 125 Models FDE71KXE6A 112KXE6A 140KXE6A B PFA003Z827 ...
Page 129: ... 126 k Floor standing with casing type FDFL Models All models B PGD000Z053 ...
Page 130: ... 127 l Floor standing without casing type FDFU Models All models A PGD000Z058 ...
Page 131: ... 128 m Duct Connected Compact and Flexible type FDUH Models All models A PJC001Z255 ...
Page 138: ... 135 ...
Page 139: ... 136 ...
Page 143: ... 140 b ...
Page 144: ... 141 ...
Page 191: ... 188 5 4 Installation of outdoor unit ...
Page 193: ... 190 ...
Page 194: ... 191 ...
Page 195: ... 192 ...
Page 196: ... 193 ...
Page 197: ... 194 ...
Page 198: ... 195 ...
Page 199: ... 196 ...
Page 200: ... 197 ...
Page 201: ... 198 ...
Page 202: ... 199 ...
Page 203: ... 200 ...
Page 204: ... 201 ...
Page 205: ... 202 ...
Page 206: ... 203 ...
Page 207: ... 204 ...
Page 208: ... 205 ...
Page 210: ... 207 ...
Page 211: ... 208 ...
Page 212: ... 209 ...
Page 215: ... 212 2 model type DIS model type HEAD ...
Page 216: ... 213 2 2 ...
Page 217: ... 214 2 2 2 2 2 ...