Error code
Remote controller:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
E5
-
Communication error during operation
Keeps flashing
*See below
Keeps flashing 2 time flash
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
Does the
remote controller
LCD becomes
normal?
Reset the power supply and restart.
YES
NO
* In case that indoor red LED stays OFF
Is the
connection of signal wires
at the outdoor unit side
OK?
Is the
connection of signal wires
between indoor and outdoor
units OK?
Does the
remote controller LCD
becomes normal?
Note (1) Check the connection (disconnection, looseness)
of signal wires at outdoor terminal block
Reset the power supply and restart.
Note (2) Check the connection (disconnection, looseness,
brakage) of signal wires between indoor and
outdoor units
YES
NO
YES
NO
YES
NO
* In case that indoor red LED flashes 2 times
Repair signal wires.
Repair signal wires.
Go to the diagnosis of
WAIT
(1)
Unit is normal.
(Malfunction by temporary
noise, etc.)
Outdoor control PCB anomaly
(Network communicaion
circuit anomaly)
→
Replace it
Unit is normal.
(Malfunction by temporary
noise, etc.)
2. Error detection method
When the communication
between indoor and outdoor
units is interupted for more than
2 minutes
3. Condition of error displayed
When this anomaly is detected
during operation.
4. Presumable cause
• Unit address No. setting error
•
Remote controller wires broken
• Poor connection/disconnection
of remote controller wires
• Indoor control PCB anomaly
Note:
When the pump down switch is turned on, communication between indoor and outdoor units is cancelled so that
"Communication error E5" will be displayed on the remote controller and indoor control PCB, but this is normal.
Summary of Contents for FDE112KXE6A
Page 104: ... 102 ...
Page 111: ... 108 b Ceiling cassette 4 way Compact type FDTC Models All moddels B PJA003Z331 ...
Page 112: ... 109 c Ceiling cassette 2 way type FDTW Models FDTW28KXE6 45KXE6 56KXE6 B PJB001Z560 ...
Page 113: ... 110 Models FDTW71KXE6 90KXE6 B PJB001Z561 ...
Page 114: ... 111 Models FDTW112KXE6 140KXE6 B PJB001Z562 ...
Page 115: ... 112 d Ceiling cassette 1 way type FDTS Model FDTS45KXE6 A PJC001Z195 ...
Page 116: ... 113 Model FDTS71KXE6 A PJC001Z196 ...
Page 117: ... 114 e Ceiling cassette 1 way compact type FDTQ Models All models A PJC001Z190 ...
Page 118: ... 115 Models All models Duct panel A PJC001Z240 ...
Page 121: ... 118 Models FDU224KXE6 280KXE6 B PJD001Z230 ...
Page 123: ... 120 Models FDUM112KXE6 140KXE6 B PJR002Z259 ...
Page 124: ... 121 h Duct connected Ultra thin Low static pressure type FDQS Models All models C PJC001Z200 ...
Page 125: ... 122 i Wall mounted type FDK Models FDK22KXE6 28KXE6 36KXE6 45KXE6 56KXE6 B PHA000Z983 ...
Page 126: ... 123 Models FDK71KXE6 B PHA000Z984 ...
Page 127: ... 124 j Ceiling suspended type FDE Models FDE36KXE6A 45KXE6A 56KXE6A B PFA003Z826 ...
Page 128: ... 125 Models FDE71KXE6A 112KXE6A 140KXE6A B PFA003Z827 ...
Page 129: ... 126 k Floor standing with casing type FDFL Models All models B PGD000Z053 ...
Page 130: ... 127 l Floor standing without casing type FDFU Models All models A PGD000Z058 ...
Page 131: ... 128 m Duct Connected Compact and Flexible type FDUH Models All models A PJC001Z255 ...
Page 138: ... 135 ...
Page 139: ... 136 ...
Page 143: ... 140 b ...
Page 144: ... 141 ...
Page 191: ... 188 5 4 Installation of outdoor unit ...
Page 193: ... 190 ...
Page 194: ... 191 ...
Page 195: ... 192 ...
Page 196: ... 193 ...
Page 197: ... 194 ...
Page 198: ... 195 ...
Page 199: ... 196 ...
Page 200: ... 197 ...
Page 201: ... 198 ...
Page 202: ... 199 ...
Page 203: ... 200 ...
Page 204: ... 201 ...
Page 205: ... 202 ...
Page 206: ... 203 ...
Page 207: ... 204 ...
Page 208: ... 205 ...
Page 210: ... 207 ...
Page 211: ... 208 ...
Page 212: ... 209 ...
Page 215: ... 212 2 model type DIS model type HEAD ...
Page 216: ... 213 2 2 ...
Page 217: ... 214 2 2 2 2 2 ...