Error code
Remote controller:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
–
81
–
E36
E36-3
Liquid flooding anomaly
Keeps flashing Stays Off
Keeps flashing 3 time flash
1. Applicable model
5. Troubleshooting
Outdoor units
Diagnosis
Countermeasure
Are there
any wrong connection of
refrigerant piping and/or signal wiring ?
. Check the numbers of connected indoor units
recognized by outdoor unit in comparison
with those numbers in
utility drawing
Are there any
excessive refrigerant charged at site?
. Check the calculation result of additional
refrigerant charging amount and the
record of additional refrigerant
charged amount
Are there any
leakage of refrigerant through
valve sheet of SV1, 2?
. Check the temperature difference between
before and after SV1, 2
Are there any
fault in subcooling coil circuit ?
. Check whether the EEVSC is kept open
(at cooling mode)
. Check whether the thermistor of Tho-H is
inserted in the thermistor holder properly
. Check whether the characteristics
of Tho-H and PSL
is OK
Is the
superheat control of
indoor unit OK at cooling mode?
. Check whether the indoor EEV is kept open or not
. Check whether Thi-R1, R2, R3 are installed at proper
position or the characteristics of them are OK
. Check whether the air filter is clogged
. Check whether the indoor
fan rotates
Is the
superheat control of
outdoor unit OK at heating mode?
. Check whether EEVH1 is kept open or not
. Check whether Tho-R1, R2, R3, R4 are installed at
proper position or the characteristics of them is OK
. Check whether the characteristics of PSL are OK
. Check whether the fin of outdoor heat exchanger
is clogged with snow, ice or dust
. Check whether the outdoor
fan rotates
Save data for 30 minutes before stopping in Mente PC
NO
NO
NO
NO
NO
NO
NO
YES
YES
YES
YES
YES
YES
YES
Is the
characteristics of Tho-C1, 2
OK ?
Check and save the data of
operating condition
Check the ROM version
Comfirmation of SV1, 2 operation
Correct the connection of
refrigerant piping and/or
signal wiring properly
Adjust refrigerant amount
properly
Replace SV1, 2
Replace the coil of SV1, 2
•
Replace EEVSC
•
Check the coil of EEVSC
Replace the coil of EEVSC
•
Replace Tho-H
•
Replace PSL
•
Replace indoor EEV
•
Check the coil of EEV
Replace the coil of EEV
•
Check the installed position
of Thi-R1, R2, R3
Replace Thi-R, if necessary
•
Check the air filter
•
Check the connection of indoor
fan motor connector
Replace indoor fan motor
*
By checking Thi-R1, R2, R3
from indoor unit operation data
of Mente PC, specify the indoor
unit which tends to be liquid
flooding (Thi-R3
.=.
Thi-R2 shows
the probability of liquid flooding)
•
Replace EEVH1, 2
•
Check the coil of EEVH1, 2
Replace the coil of EEVH1, 2
•
Check the installed position of
Tho-R1, R2, R3
Replace Tho-R, if necessary
•
Clean the fin of outdoor heat
exchanger
•
Check the connection of
outdoor fan motor connector
Replace outdoor fan motor
•
Replace Tho-C1, 2
Correct the data with Mente PC
and ask our consultation
2. Error detection method
When 5ºC or lower of the
under-dome temperature
superheat is detected for 15
minutes continuously or for 30
minutes continuously.
3.
Condition of error displayed
When above anomaly is
detected 3 times within 90
minutes.
4. Presumable cause
• Unmatching of refrigerant
piping and/or signal wiring
• Overcharging of refrigerant
• Anomalous control of
superheat
• Anomalous circuit of liquid
refrigerant by-pass
• Anomalous refrigerant circuit
of subcool coil
• Under-dome temperature
(Tho-D1, 2) anomaly
Note: If the error does not recur, connect the Mente PC and continue to collect data.
Summary of Contents for FDE112KXE6A
Page 104: ... 102 ...
Page 111: ... 108 b Ceiling cassette 4 way Compact type FDTC Models All moddels B PJA003Z331 ...
Page 112: ... 109 c Ceiling cassette 2 way type FDTW Models FDTW28KXE6 45KXE6 56KXE6 B PJB001Z560 ...
Page 113: ... 110 Models FDTW71KXE6 90KXE6 B PJB001Z561 ...
Page 114: ... 111 Models FDTW112KXE6 140KXE6 B PJB001Z562 ...
Page 115: ... 112 d Ceiling cassette 1 way type FDTS Model FDTS45KXE6 A PJC001Z195 ...
Page 116: ... 113 Model FDTS71KXE6 A PJC001Z196 ...
Page 117: ... 114 e Ceiling cassette 1 way compact type FDTQ Models All models A PJC001Z190 ...
Page 118: ... 115 Models All models Duct panel A PJC001Z240 ...
Page 121: ... 118 Models FDU224KXE6 280KXE6 B PJD001Z230 ...
Page 123: ... 120 Models FDUM112KXE6 140KXE6 B PJR002Z259 ...
Page 124: ... 121 h Duct connected Ultra thin Low static pressure type FDQS Models All models C PJC001Z200 ...
Page 125: ... 122 i Wall mounted type FDK Models FDK22KXE6 28KXE6 36KXE6 45KXE6 56KXE6 B PHA000Z983 ...
Page 126: ... 123 Models FDK71KXE6 B PHA000Z984 ...
Page 127: ... 124 j Ceiling suspended type FDE Models FDE36KXE6A 45KXE6A 56KXE6A B PFA003Z826 ...
Page 128: ... 125 Models FDE71KXE6A 112KXE6A 140KXE6A B PFA003Z827 ...
Page 129: ... 126 k Floor standing with casing type FDFL Models All models B PGD000Z053 ...
Page 130: ... 127 l Floor standing without casing type FDFU Models All models A PGD000Z058 ...
Page 131: ... 128 m Duct Connected Compact and Flexible type FDUH Models All models A PJC001Z255 ...
Page 138: ... 135 ...
Page 139: ... 136 ...
Page 143: ... 140 b ...
Page 144: ... 141 ...
Page 191: ... 188 5 4 Installation of outdoor unit ...
Page 193: ... 190 ...
Page 194: ... 191 ...
Page 195: ... 192 ...
Page 196: ... 193 ...
Page 197: ... 194 ...
Page 198: ... 195 ...
Page 199: ... 196 ...
Page 200: ... 197 ...
Page 201: ... 198 ...
Page 202: ... 199 ...
Page 203: ... 200 ...
Page 204: ... 201 ...
Page 205: ... 202 ...
Page 206: ... 203 ...
Page 207: ... 204 ...
Page 208: ... 205 ...
Page 210: ... 207 ...
Page 211: ... 208 ...
Page 212: ... 209 ...
Page 215: ... 212 2 model type DIS model type HEAD ...
Page 216: ... 213 2 2 ...
Page 217: ... 214 2 2 2 2 2 ...