Error code
Remote controller:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
–
84
–
E3
9
E39-1, 2
Discharge pipe temperature
thermistor anomaly (Tho-D1, D2)
Keeps flashing Stays Off
Keeps flashing
*
2
1. Applicable model
5. Troubleshooting
Outdoor unit
Diagnosis
Countermeasure
Is the
connector of
thermistor connected
properly?
Are the
characteristics of
thermistor
OK? *3
*3
Check several times to prove any poor connection
Temperature-resistance characteristics of discharge
pipe temperature thermistor (Tho-D1, D2)
Save data for 30 minutes before stopping in Mente PC
YES
NO
NO
YES
Temperature (°C)
Temperature thermisto
r
resistance (kΩ)
0
20
40
60
80
100
120
140
160
180
200
0
20
40
60
80 100 120 140 160
Check and save the data of
operating condition.
Check the conditions whether
it occurs immediately after the
power on or during operation
or stopping.
Check the sensed value.
Compare the temperature
on Mente PC with actual
measured value.
Insert the connector securely
Replace thermistor
(Tho-D1 or D2).
Replace outdoor control
PCB.
2. Error detection method
Detection of anomalously low
temperature (resistance) of
Tho-D1, D2
3.
Condition of error displayed
•
If 3°C or lower is detected for
5 seconds continuously within
10-minutes to 10-minutes
20-seconds after the compressor
ON, the compressor stops. And after
3-minutes delay, the compressor
starts again automatically, but if this
anomalous temperature is detected
3 times within 40 minutes after the
initial detection.
4. Presumable cause
• Broken thermistor harness or
the internal wire of sensing
section (Check the molded
section as well)
• Disconnection of thermistor
harness connection (connector)
• Outdoor control PCB anomaly
Note:
*1 E39-1: Tho-D1, E39-2: Tho-D2, *2 E39-1: 1 time flash, E39-2: 2 time flash
Summary of Contents for FDE112KXE6A
Page 104: ... 102 ...
Page 111: ... 108 b Ceiling cassette 4 way Compact type FDTC Models All moddels B PJA003Z331 ...
Page 112: ... 109 c Ceiling cassette 2 way type FDTW Models FDTW28KXE6 45KXE6 56KXE6 B PJB001Z560 ...
Page 113: ... 110 Models FDTW71KXE6 90KXE6 B PJB001Z561 ...
Page 114: ... 111 Models FDTW112KXE6 140KXE6 B PJB001Z562 ...
Page 115: ... 112 d Ceiling cassette 1 way type FDTS Model FDTS45KXE6 A PJC001Z195 ...
Page 116: ... 113 Model FDTS71KXE6 A PJC001Z196 ...
Page 117: ... 114 e Ceiling cassette 1 way compact type FDTQ Models All models A PJC001Z190 ...
Page 118: ... 115 Models All models Duct panel A PJC001Z240 ...
Page 121: ... 118 Models FDU224KXE6 280KXE6 B PJD001Z230 ...
Page 123: ... 120 Models FDUM112KXE6 140KXE6 B PJR002Z259 ...
Page 124: ... 121 h Duct connected Ultra thin Low static pressure type FDQS Models All models C PJC001Z200 ...
Page 125: ... 122 i Wall mounted type FDK Models FDK22KXE6 28KXE6 36KXE6 45KXE6 56KXE6 B PHA000Z983 ...
Page 126: ... 123 Models FDK71KXE6 B PHA000Z984 ...
Page 127: ... 124 j Ceiling suspended type FDE Models FDE36KXE6A 45KXE6A 56KXE6A B PFA003Z826 ...
Page 128: ... 125 Models FDE71KXE6A 112KXE6A 140KXE6A B PFA003Z827 ...
Page 129: ... 126 k Floor standing with casing type FDFL Models All models B PGD000Z053 ...
Page 130: ... 127 l Floor standing without casing type FDFU Models All models A PGD000Z058 ...
Page 131: ... 128 m Duct Connected Compact and Flexible type FDUH Models All models A PJC001Z255 ...
Page 138: ... 135 ...
Page 139: ... 136 ...
Page 143: ... 140 b ...
Page 144: ... 141 ...
Page 191: ... 188 5 4 Installation of outdoor unit ...
Page 193: ... 190 ...
Page 194: ... 191 ...
Page 195: ... 192 ...
Page 196: ... 193 ...
Page 197: ... 194 ...
Page 198: ... 195 ...
Page 199: ... 196 ...
Page 200: ... 197 ...
Page 201: ... 198 ...
Page 202: ... 199 ...
Page 203: ... 200 ...
Page 204: ... 201 ...
Page 205: ... 202 ...
Page 206: ... 203 ...
Page 207: ... 204 ...
Page 208: ... 205 ...
Page 210: ... 207 ...
Page 211: ... 208 ...
Page 212: ... 209 ...
Page 215: ... 212 2 model type DIS model type HEAD ...
Page 216: ... 213 2 2 ...
Page 217: ... 214 2 2 2 2 2 ...