Error code
Remote controller:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
–
87
–
E42
E42-1, 2*
Current cut (CM1, CM2)
Keeps flashing Stays Off
Keeps flashing
*
2
1. Applicable model
5. Troubleshooting
Outdoor unit
Diagnosis
Countermeasure
Is the
coil resistance and insulation
(megger check) of compressor
motor OK?
Do you
have inverter checker for
judging whether inverter PCB is
OK or not?
After power OFF,
Remove the 1-3 layers
of control box
Is the
checked result by measuring
the resistance beween each terminal
of power transistor module OK?
(Are there any short-
circuit?)
Is the
checked result by
inverter checker
OK?
NO
NO
NO
NO
NO
NO
NO
NO
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
Save data for 30 minutes before stopping in Mente PC
Does the outdoor fan run ?
Reset power supply and restart
Does E42 recur?
Is it the unit with 2 compressors?
When
interchanging the
cables between inverter and
compressor, is the compressor
failed to startup
switched?
Is 15V
of power for control PCB
detected? Is the outdoor fan motor OK?
(Refer the checking method of
15V in page 46)
Check and save the data of
operating conditions
Check pressure anomaly
Check the operation of
outdoor fan
Replace compressor.
Check the capillary tube
and stariner of oil separator.
If necessary, replace the
capillary tube and strainer
as well.
Repair it according to the
troubleshooting of E48
Replace inverter PCB or
outdoor fan motor
Check it as much as
possible under the
operating conditions for
30 minutes before error
occurred
Wait and see.
Continue to obain data, if
possible
(Keep connecting the
Mente PC)
Replace compressor that is
failed to startup
Replace power transistor
module
Replace inverter PCB
Replace power transistor
module.
Refer Page 46.
(Remove the power cable from
compressor and check the
resistance between P-U,
P-V, P-W, N-U, N-V, N-W
respectively.
Replace inverter PCB
2. Error detection method
When anomalously high output
current of inverter is detected
by the current sensor mounted
in the power transistor
3.
Condition of error displayed
When 88A or higher output
current of inverter is detected 4
times within 15 minutes.
4. Presumable cause
• Compressor anomaly
• Leakage of refrigerant
• Power transistor module
anomaly
• Anomalous power supply for
inverter PCB
• Outdoor fan motor anomaly
Note:
In case that there is no the insulation resistance anomaly, the compressor anomaly could be considered.
If this anomaly occurs after replacement of power transistor module and/or inverter PCB, try to replace compressor as well.
If the error does not recur, connect the Mente PC and continue to collect data
*1 E42-1: CM1, E42-2: CM2 *2 E42-1: 1 time flash, E42-2: 2 time flash
Summary of Contents for FDE112KXE6A
Page 104: ... 102 ...
Page 111: ... 108 b Ceiling cassette 4 way Compact type FDTC Models All moddels B PJA003Z331 ...
Page 112: ... 109 c Ceiling cassette 2 way type FDTW Models FDTW28KXE6 45KXE6 56KXE6 B PJB001Z560 ...
Page 113: ... 110 Models FDTW71KXE6 90KXE6 B PJB001Z561 ...
Page 114: ... 111 Models FDTW112KXE6 140KXE6 B PJB001Z562 ...
Page 115: ... 112 d Ceiling cassette 1 way type FDTS Model FDTS45KXE6 A PJC001Z195 ...
Page 116: ... 113 Model FDTS71KXE6 A PJC001Z196 ...
Page 117: ... 114 e Ceiling cassette 1 way compact type FDTQ Models All models A PJC001Z190 ...
Page 118: ... 115 Models All models Duct panel A PJC001Z240 ...
Page 121: ... 118 Models FDU224KXE6 280KXE6 B PJD001Z230 ...
Page 123: ... 120 Models FDUM112KXE6 140KXE6 B PJR002Z259 ...
Page 124: ... 121 h Duct connected Ultra thin Low static pressure type FDQS Models All models C PJC001Z200 ...
Page 125: ... 122 i Wall mounted type FDK Models FDK22KXE6 28KXE6 36KXE6 45KXE6 56KXE6 B PHA000Z983 ...
Page 126: ... 123 Models FDK71KXE6 B PHA000Z984 ...
Page 127: ... 124 j Ceiling suspended type FDE Models FDE36KXE6A 45KXE6A 56KXE6A B PFA003Z826 ...
Page 128: ... 125 Models FDE71KXE6A 112KXE6A 140KXE6A B PFA003Z827 ...
Page 129: ... 126 k Floor standing with casing type FDFL Models All models B PGD000Z053 ...
Page 130: ... 127 l Floor standing without casing type FDFU Models All models A PGD000Z058 ...
Page 131: ... 128 m Duct Connected Compact and Flexible type FDUH Models All models A PJC001Z255 ...
Page 138: ... 135 ...
Page 139: ... 136 ...
Page 143: ... 140 b ...
Page 144: ... 141 ...
Page 191: ... 188 5 4 Installation of outdoor unit ...
Page 193: ... 190 ...
Page 194: ... 191 ...
Page 195: ... 192 ...
Page 196: ... 193 ...
Page 197: ... 194 ...
Page 198: ... 195 ...
Page 199: ... 196 ...
Page 200: ... 197 ...
Page 201: ... 198 ...
Page 202: ... 199 ...
Page 203: ... 200 ...
Page 204: ... 201 ...
Page 205: ... 202 ...
Page 206: ... 203 ...
Page 207: ... 204 ...
Page 208: ... 205 ...
Page 210: ... 207 ...
Page 211: ... 208 ...
Page 212: ... 209 ...
Page 215: ... 212 2 model type DIS model type HEAD ...
Page 216: ... 213 2 2 ...
Page 217: ... 214 2 2 2 2 2 ...