Error code
Remote controller:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
–
88
–
E43
E43-1, 2 *1
Excessive number of indoor units connected,
excessive total capacity of connection
Keeps flashing Stays Off
Keeps flashing
*1
1. Applicable model
5. Troubleshooting
Outdoor unit
Diagnosis
Countermeasure
Is E43 dispalyed?
Are there
any indoor units which
is not expected to exsist in
that signal
line?
Save data for 30 minutes before stopping in Mente PC
NO
NO
NO
Does
the number of
indoor units connected
and/or total capacity
exceed limitation?
Check the resistance
between A and B of signal
line as well.
Check the connected number
of indoor units with 7-segment
display code C50 or Mente PC
with reference to the utilities
drawing. (Check not only one
system, but also other systems)
YES
YES
YES
General checking of indoor/outdoor unit addresses by means of:
�
Outdoor unit: Mente PC, 7-Segemnt display and rorary
switch (SW1, 2)
�
Indoor unit: Remote controller, rotary switch
(SW1, 2, 3, 4)
* It is recommended to use means other than the rotary switch
which could be defective.
Reset the power.
Check and save the data of
operating condition.
Test run.
No action is taken because
it is judged that the power
reset was not done after
changing address.
Check indoor unit
addresses and correct.
In case that total capacity
of connected indoor units
exceeds the limitation,
if tentative operation is
required turn ON the dip
switch SW5-4 on the
outdoor control PCB.
(However since this
tentative solution could
cause trouble, be sure
to correct it as soon as
possible)
Signal wire may be
connected to other outdoor
unit system.
Correct the signal wire.
Correct addresses.
(Either one of addresses is
wrong.)
If the address corrected
with rotary switch is still
wrong, replace control PCB
(Defective rotary switch)
* Before replacement,
please confirm whether
the rotary switch for
address setting is not
damaged. (It was
experienced that No. 5
on rotary switch was not
recognized.)
2. Error detection method
When the number of connected
indoor units exceeds the
limitation.
When the total capacity of
connected indoor units exceeds
the limitation.
3.
Condition of error displayed
• Excessive number of
connected indoor units
• Excessive total capacity of
connected indoor units
• The total capacity of
connected indoor units
exceeds the limitation
4. Presumable cause
• Mistake in setting of indoor/
outdoor unit addresses
• Mistake in signal wire
connection
Note:
After completing the above procedure, reset the power and confirm that the error display does not recur. Unless the power
is reset for both indoor unit and outdoor unit, the set addresses will not be confirmed.
*1 E43-1/1 time flash: Excessive number of indoor units connected, E43-2/2 time flash:Excessive capacity of connection
Caution:
Address will not be confirmed,
unless the power is reset after
changing addess.
Summary of Contents for FDE112KXE6A
Page 104: ... 102 ...
Page 111: ... 108 b Ceiling cassette 4 way Compact type FDTC Models All moddels B PJA003Z331 ...
Page 112: ... 109 c Ceiling cassette 2 way type FDTW Models FDTW28KXE6 45KXE6 56KXE6 B PJB001Z560 ...
Page 113: ... 110 Models FDTW71KXE6 90KXE6 B PJB001Z561 ...
Page 114: ... 111 Models FDTW112KXE6 140KXE6 B PJB001Z562 ...
Page 115: ... 112 d Ceiling cassette 1 way type FDTS Model FDTS45KXE6 A PJC001Z195 ...
Page 116: ... 113 Model FDTS71KXE6 A PJC001Z196 ...
Page 117: ... 114 e Ceiling cassette 1 way compact type FDTQ Models All models A PJC001Z190 ...
Page 118: ... 115 Models All models Duct panel A PJC001Z240 ...
Page 121: ... 118 Models FDU224KXE6 280KXE6 B PJD001Z230 ...
Page 123: ... 120 Models FDUM112KXE6 140KXE6 B PJR002Z259 ...
Page 124: ... 121 h Duct connected Ultra thin Low static pressure type FDQS Models All models C PJC001Z200 ...
Page 125: ... 122 i Wall mounted type FDK Models FDK22KXE6 28KXE6 36KXE6 45KXE6 56KXE6 B PHA000Z983 ...
Page 126: ... 123 Models FDK71KXE6 B PHA000Z984 ...
Page 127: ... 124 j Ceiling suspended type FDE Models FDE36KXE6A 45KXE6A 56KXE6A B PFA003Z826 ...
Page 128: ... 125 Models FDE71KXE6A 112KXE6A 140KXE6A B PFA003Z827 ...
Page 129: ... 126 k Floor standing with casing type FDFL Models All models B PGD000Z053 ...
Page 130: ... 127 l Floor standing without casing type FDFU Models All models A PGD000Z058 ...
Page 131: ... 128 m Duct Connected Compact and Flexible type FDUH Models All models A PJC001Z255 ...
Page 138: ... 135 ...
Page 139: ... 136 ...
Page 143: ... 140 b ...
Page 144: ... 141 ...
Page 191: ... 188 5 4 Installation of outdoor unit ...
Page 193: ... 190 ...
Page 194: ... 191 ...
Page 195: ... 192 ...
Page 196: ... 193 ...
Page 197: ... 194 ...
Page 198: ... 195 ...
Page 199: ... 196 ...
Page 200: ... 197 ...
Page 201: ... 198 ...
Page 202: ... 199 ...
Page 203: ... 200 ...
Page 204: ... 201 ...
Page 205: ... 202 ...
Page 206: ... 203 ...
Page 207: ... 204 ...
Page 208: ... 205 ...
Page 210: ... 207 ...
Page 211: ... 208 ...
Page 212: ... 209 ...
Page 215: ... 212 2 model type DIS model type HEAD ...
Page 216: ... 213 2 2 ...
Page 217: ... 214 2 2 2 2 2 ...