Error code
Remote controller:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
–
91
–
E48
E48-1, 2 *1
Outdoor DC fan motor anomaly
Keeps flashing
Stays Off
Keeps flashing
*1
1. Applicable model
5. Troubleshooting
Outdoor unit
Diagnosis
Countermeasure
Is 15V
of power for control PCB
detected? Is the outdoor fan motor
OK? (Refer the checking method of
15V in page
46)
Does the
fan rotate smoothly when turned
by hand?
NO
NO
NO
NO
YES
YES
YES
YES
Is E48
restored at 10 seconds after
compressor starting?
Interchange the connectors of fan motor
harnesses at the connectors on outdoor
control PCB side
Is the
fan motor failed to start up
switched?
Start operation again
Turn the power supply OFF
Reset power supply and restart
Save data for 30 minutes before stopping in Mente PC
Check and save the data of
operating conditions
Replace fan motor
Replace inverter PCB
or fan motor
Check it as much as
possible under the
operating conditions for
30 minutes before error
occurred
Wait and see.
Continue to obain data, if
possible
(Keep connecting the
Mente PC)
Replace fan motor
Replace outdoor control
PCB
2. Error detection method
• If 400 min
-1
or lower of the
fan rotation command and the
state of overcurent are detected
for 10 times continueously.
• If 100 min
-1
of the actual fan
rotation speed is detected
for 30 seconds (Fan motor is
locked)
3.
Condition of error displayed
Same as above.
4. Presumable cause
•
Breakage of harness
or loose conection of
connector
• Outdoor fan motor anomaly
•
Inverter PCB anomaly
•
Outdoor control PCB anomaly
Note:
If the error does not recur, connect the Mente PC and continue to collect data.
*1 E48-1: 1 time flash (FMO1), E48-2 : 2 time flash (FMO2)
Inspect also the fan motor 2 even if it is E48-1.
Inspect also the fan motor 1 even if it is E48-2.
(
)
Summary of Contents for FDE112KXE6A
Page 104: ... 102 ...
Page 111: ... 108 b Ceiling cassette 4 way Compact type FDTC Models All moddels B PJA003Z331 ...
Page 112: ... 109 c Ceiling cassette 2 way type FDTW Models FDTW28KXE6 45KXE6 56KXE6 B PJB001Z560 ...
Page 113: ... 110 Models FDTW71KXE6 90KXE6 B PJB001Z561 ...
Page 114: ... 111 Models FDTW112KXE6 140KXE6 B PJB001Z562 ...
Page 115: ... 112 d Ceiling cassette 1 way type FDTS Model FDTS45KXE6 A PJC001Z195 ...
Page 116: ... 113 Model FDTS71KXE6 A PJC001Z196 ...
Page 117: ... 114 e Ceiling cassette 1 way compact type FDTQ Models All models A PJC001Z190 ...
Page 118: ... 115 Models All models Duct panel A PJC001Z240 ...
Page 121: ... 118 Models FDU224KXE6 280KXE6 B PJD001Z230 ...
Page 123: ... 120 Models FDUM112KXE6 140KXE6 B PJR002Z259 ...
Page 124: ... 121 h Duct connected Ultra thin Low static pressure type FDQS Models All models C PJC001Z200 ...
Page 125: ... 122 i Wall mounted type FDK Models FDK22KXE6 28KXE6 36KXE6 45KXE6 56KXE6 B PHA000Z983 ...
Page 126: ... 123 Models FDK71KXE6 B PHA000Z984 ...
Page 127: ... 124 j Ceiling suspended type FDE Models FDE36KXE6A 45KXE6A 56KXE6A B PFA003Z826 ...
Page 128: ... 125 Models FDE71KXE6A 112KXE6A 140KXE6A B PFA003Z827 ...
Page 129: ... 126 k Floor standing with casing type FDFL Models All models B PGD000Z053 ...
Page 130: ... 127 l Floor standing without casing type FDFU Models All models A PGD000Z058 ...
Page 131: ... 128 m Duct Connected Compact and Flexible type FDUH Models All models A PJC001Z255 ...
Page 138: ... 135 ...
Page 139: ... 136 ...
Page 143: ... 140 b ...
Page 144: ... 141 ...
Page 191: ... 188 5 4 Installation of outdoor unit ...
Page 193: ... 190 ...
Page 194: ... 191 ...
Page 195: ... 192 ...
Page 196: ... 193 ...
Page 197: ... 194 ...
Page 198: ... 195 ...
Page 199: ... 196 ...
Page 200: ... 197 ...
Page 201: ... 198 ...
Page 202: ... 199 ...
Page 203: ... 200 ...
Page 204: ... 201 ...
Page 205: ... 202 ...
Page 206: ... 203 ...
Page 207: ... 204 ...
Page 208: ... 205 ...
Page 210: ... 207 ...
Page 211: ... 208 ...
Page 212: ... 209 ...
Page 215: ... 212 2 model type DIS model type HEAD ...
Page 216: ... 213 2 2 ...
Page 217: ... 214 2 2 2 2 2 ...