Error code
Remote controller:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
–
95
–
E56
E56-1, 2 *1
Power transitor temperature
thermistor anomaly (Tho-P1, P2)
Keeps flashing
Stays Off
Keeps flashing
*1
1. Applicable model
5. Troubleshooting
Outdoor unit
Diagnosis
Countermeasure
Is the
connector of
thermistor connected
properly OK
?
Are the
characteristics of
thermistor OK?
*1
(1)
Regarding the characteristics of
the thermistor, see the following.
Temperature-resistance characreristics of power transistor
temperature thermisor (Tho-P1, P2)
*1. Check several times to prove any poor connection
Save data for 30 minutes before stopping in Mente PC
YES
NO
NO
YES
Temperature (°C)
Temperature thermistor resistance (kΩ)
0
20
40
60
80
100
120
140
160
180
200
0
20
40
60
80
100
120
140
Check and save the data of
operating condition.
Check the conditions
whether it occurs
immediately after the
power on or during
operation or stopping.
Check the sensed value.
Compare the temperature
of Mente PC data with
actual measured value
Insert the connector
securely
Replace power transistor
temperature thermistor
(Tho-P1, P2).
Replace outdoor control
PCB.
2. Error detection method
Detection of anomalously low
temperature (resistance) of
Tho-P1, P2
3.
Condition of error displayed
When the outdoor air temperature
is above 0ºC, if -10ºC or lower
is detected for 20 seconds
continuously within 10 minutes
to 10 minutes 30 seconds after
compressor ON, compressor stops.
When the compressor is restarted
automatically after 3-minutes
delay, if this anomaly occurs 3
times within 40 minutes
4. Presumable cause
•
Broken thermistor harness or
the internal wire of sensing
section (Check the molded
section as well)
•
Disconnection of thermistor
harness connection
(connector)
•
Outdoor control PCB
anomaly
Note:
*1 E56-1/1 time flash:Tho-P1 anomaly, E56-2/2 time flash: Tho-P2 anomaly
Summary of Contents for FDE112KXE6A
Page 104: ... 102 ...
Page 111: ... 108 b Ceiling cassette 4 way Compact type FDTC Models All moddels B PJA003Z331 ...
Page 112: ... 109 c Ceiling cassette 2 way type FDTW Models FDTW28KXE6 45KXE6 56KXE6 B PJB001Z560 ...
Page 113: ... 110 Models FDTW71KXE6 90KXE6 B PJB001Z561 ...
Page 114: ... 111 Models FDTW112KXE6 140KXE6 B PJB001Z562 ...
Page 115: ... 112 d Ceiling cassette 1 way type FDTS Model FDTS45KXE6 A PJC001Z195 ...
Page 116: ... 113 Model FDTS71KXE6 A PJC001Z196 ...
Page 117: ... 114 e Ceiling cassette 1 way compact type FDTQ Models All models A PJC001Z190 ...
Page 118: ... 115 Models All models Duct panel A PJC001Z240 ...
Page 121: ... 118 Models FDU224KXE6 280KXE6 B PJD001Z230 ...
Page 123: ... 120 Models FDUM112KXE6 140KXE6 B PJR002Z259 ...
Page 124: ... 121 h Duct connected Ultra thin Low static pressure type FDQS Models All models C PJC001Z200 ...
Page 125: ... 122 i Wall mounted type FDK Models FDK22KXE6 28KXE6 36KXE6 45KXE6 56KXE6 B PHA000Z983 ...
Page 126: ... 123 Models FDK71KXE6 B PHA000Z984 ...
Page 127: ... 124 j Ceiling suspended type FDE Models FDE36KXE6A 45KXE6A 56KXE6A B PFA003Z826 ...
Page 128: ... 125 Models FDE71KXE6A 112KXE6A 140KXE6A B PFA003Z827 ...
Page 129: ... 126 k Floor standing with casing type FDFL Models All models B PGD000Z053 ...
Page 130: ... 127 l Floor standing without casing type FDFU Models All models A PGD000Z058 ...
Page 131: ... 128 m Duct Connected Compact and Flexible type FDUH Models All models A PJC001Z255 ...
Page 138: ... 135 ...
Page 139: ... 136 ...
Page 143: ... 140 b ...
Page 144: ... 141 ...
Page 191: ... 188 5 4 Installation of outdoor unit ...
Page 193: ... 190 ...
Page 194: ... 191 ...
Page 195: ... 192 ...
Page 196: ... 193 ...
Page 197: ... 194 ...
Page 198: ... 195 ...
Page 199: ... 196 ...
Page 200: ... 197 ...
Page 201: ... 198 ...
Page 202: ... 199 ...
Page 203: ... 200 ...
Page 204: ... 201 ...
Page 205: ... 202 ...
Page 206: ... 203 ...
Page 207: ... 204 ...
Page 208: ... 205 ...
Page 210: ... 207 ...
Page 211: ... 208 ...
Page 212: ... 209 ...
Page 215: ... 212 2 model type DIS model type HEAD ...
Page 216: ... 213 2 2 ...
Page 217: ... 214 2 2 2 2 2 ...