115
-
'17 • PAC-T-256
Replace and set up the PCB according to this instruction.
①
Set to an appropriate address and function using switch on PCB.
Select the same setting with the removed PCB.
②
Set to an appropriate capacity using the model selector switch(SW6).
Select the same capacity with the PCB removed from the unit.
③
Replace the PCB
1. Exchange PCB after detaching all connectors connected with the PCB.
2. Fix the PCB so as not to pitch the wiring.
3. Connect connectors to the PCB. Match the wiring connector to the connector color on the PCB and connect it.
④
Control PCB
Parts mounting are different by the kind of PCB.
〇:ON -:OFF
item
switch
Address
SW2
-
〇
Content of control
Plural indoor units control by 1 remote control
Test run
SW7-1
Normal
Operation check/drain motor test run
SW6
-1
-2
-3
-4
50V
〇
-
〇
-
60V
〇
〇
〇
-
40V
〇
〇
-
-
SW6
ON
1 2 3 4
Example setting fro 50V
Part number
SW5
Master/Slave
setting
SW2(Blue)
Address setting
CNI(Blue)
Float SW
CNH(Black)
Thermistor
(Return air)
CNB(White)
Remote
control
CNTA(Blue)
External
input
CNW2(White)
Power PWB
CNR(White)
Drain motor
C
NT(
Blue
)
External switch
C
N
J(Whit
e)
Louver moto
r
CNZ(White)
HA
CNN(Y
e
llow)
Thermistor
(Heat exchanger)
SW6
Capacity setting
SW7
Function setting
SW8
Function setting
CNE(White)
RAM checker
323
a)
Control PCB
1)
Model FDE, FDUM series
PSB012D990
B
PSB012D990B
C