'17 • PAC-T-256
Replace and set up the PCB according to this instruction.
①
Set to an appropriate address and function using switch on PCB.
Select the same setting with the removed PCB.
②
Set to an appropriate capacity using the model selector switch(SW6).
Select the same capacity with the PCB removed from the unit.
③
Replace the PCB
1. Fix the PCB so as not to pitch the cords.
2. Connect connectors to the PCB. Connect a cable connector with the PCB connector of the same color.
3.Do not pass CPU surrounding about wirings.
④
Control PCB
Parts mounting are different by the kind of PCB.
〇:ON -:OFF
item
switch
Address
SW2
-
〇
Content of control
Plural indoor units control by 1 remote control
Test run
SW7-1
Normal
Operation check/drain motor test run
SW6
ON
1 2 3 4
Example setting fro 40VF
SW6
-1
-2
-3
-4
40VF
〇
-
-
〇
-
50VF
〇
〇
-
〇
〇
60VF
〇
-
Part number
SW2 (Blue)
Address setting
SW5
Master/Slave
setting
SW7
Function setting
CNT(Blue)
External switch
CNJ(White)
Louver motor
CNN(Yellow)
Thermistor
(Heat exchanger)
CNI(Blue)
Float
SW
CNH(Black)
Thermist
or
(Ret
urn a
ir)
CNW3(Red)
Power PCB
CNB(White)
Remot
e
control
CNG(Blue)
CNZ(White)
HA
CNE(White)
RAM checker
CNW4(Blue)
Power PCB
SW6
Capacity setting
PSB012D976C
a)
Control PCB
2)
Model FDTC series