'17 • PAC-T-256
③
How to install the receiver (continued)
④
Wireless remote control
④
Wireless remote control
(continued)
⑤
Receiver
Installation tips for the remote control
holder
Fix the remote control holder using the screws supplied
with this product.
* Precautions for installing the holder
●
Adjust the position so that it is upright.
● E
nsure that the screw heads are not protruding.
●
Do not attach the holder on plaster wall.
How to insert batteries
1. Detach the back lid.
2. Insert the batteries. (two AAA batteries)
3. Reattach the back lid.
Setting to avoid mixed communication
1. Detach the back lid, and remove the batteries.
2. Cut off the switching wire in the battery compartment using nippers.
3. Insert the batteries, and attach the back lid.
Changing the wireless remote control setting
How to change the Auto Run setting
The Auto Run mode is not available on the building air-conditioner and gas heat
pump series (excluding the cooling/heating free multi system).
When using the wireless remote control to operate those models, set the wireless
remote control to disable the Auto Run mode.
To disable the Auto Run mode, press the ACL switch while holding down the MOD
E
button, or insert batteries while holding down the MOD
E
button.
* Note: Once the batteries are removed, the setting is reset to the factory default.
.
e
v
o
b
a
d
e
b
ir
c
s
e
d
s
p
e
t
s
e
h
t
t
a
e
p
e
r
,
d
e
v
o
m
e
r
e
r
a
s
e
ir
e
tt
a
b
e
h
t
n
e
h
W
Indoor function settings
1. How to set indoor functions
①
Press the ON/OFF button to stop the unit.
②
Press the desired one of the buttons shown below while holding down the
FUNCTION S
E
TTING switch.
③
Use the selection buttons
, ▲
and
▼
, to change the setting.
④
Press the S
E
T button.
The buzzer on the wireless remote control signal receiver beeps twice, and
the L
E
D lamp
fl
ashes four times at two-second intervals.
2. Setting details
The following functions can be set.
1 Control plural indoor units with one remote control
Up to 16 indoor units can be connected.
1. Connect the XY terminal with 2 cores wire. As for the
size, refer to the following note.
2. For Packaged air-conditioner series, set the indoor
unit address with SW2 on the indoor unit PCB from
[0] to [F] so as not to duplicate.
For the shop series
For VRF series, set the indoor unit address with SW1, SW2 and SW5-2 on the indoor unit PCB from [000]
to [127] so as not to duplicate.
KIT
Terminal block
Wireless remote control
Indoor unit (1)
Address (0)
Indoor unit (2)
Address (1)
Indoor unit (16)
Address ( F )
For the building air- conditioner and gas heat pump series
Set the indoor unit and outdoor unit numbers by manually specifying the addresses.
Use the rotary switchs SW1 and SW2 provided on the indoor unit PCB (printed circuit board) to set the
indoor unit numbers so that they are not duplicated.
Master/Slave setting when using plural remote control
Up to two receivers can be installed in one indoor unit group.
Indoor unit
Receiver
SW1[Master]
Receiver
SW1[Sla ve]
Remote control line
(No polarity)
Switch
Setting
Function
SW2
ON
Master
OFF
Slave
When installed on ceiling
1. Standard reachable area of the signa
[Condition] Illuminance at the receiver :
300lux
(when no lighting is installed within 1m of the receiver
in an ordinary of
fi
ce.)l
Receiver
Ceiling surface
Ceiling surface
Floor
Floor
Orientation of receiver
Receivable area
of the signal
Receivable area
of the signal
Orientation of receiver
2. Correlation between illuminance at the receiver and reachable area of the signal in a plain view.
[Condition] Correlation between the reachable area of the signal and illuminance at the receiver when the
wireless remote control is operated at 1m high under the condition of ceiling height of 2.4m.
When the illuminance becomes double, the area is narrowed down to two third.
When installed on wall
[Condition] Illuminance at the receiver : 800lux.
Receiver
Wireless
remote control
Floor
5m or less
60° or less
30°
or less
30°
or less
5m or less
Backup switch
A backup switch is provided on the receiver section of the panel surface.
When operation from the wireless remote control unit is not possible
(due to
fl
at batteries, a mislaid unit, a unit failure), you can use it as an
emergency means. You should operate this switch manually.
1. If pressed while the air-conditioner is in a halt, it will cause the air-
conditioner to start operation in the automatic mode (in the case of
cooling only, in the cooling mode). Wind speed: Hi fan, Temperature
setting: 23°C, Louver: horizontal
2. If pressed while the air-conditioner is in operation, it will stop the air-
conditioner.
Backup switch
Cooling test run operation
●
After safety con
fi
rmation, turn on the power.
●
Transmit a cooling operation command with the wireless remote control unit, while the backup switch
on the receiver is depressed.
●
If the backup switch on the receiver is pressed during a test run, it will end the test run.
●
If you cannot operate the unit properly during a test run, please check wiring by consulting with
inspection guides.
How to read the 6-digit display
A 6-digit indicator (7-segment indicator) is provided on the receiver section.
1. An indication will be displayed for one hour after power on.
2. An indication appears for 3.5 seconds when a “Stop” command is sent from the wireless remote
control unit while the air-conditioner is not running.
3. An indication appearing in (1) or (2) above will go off as soon as the unit starts operation.
4. When there are no error records to indicate, addresses are displayed for all of the connected units.
5. When there are some error records remaining, the error records are displayed.
6.
E
rror records can be cleared by transmitting a “Stop” command from the wireless remote control unit,
while the backup switch is depressed.
⑤
Receiver (continued)
⑤
Receiver (continued)
5
7
6
Wood screw
Cutting
Holder for
remote control
Ensure the correct
polarity when
inserting.
①
④
②
③
Button
Number indicator
Function setting
Button
Number indicator
Function setting
F
AN SPEED
00
Fun speed setting : Standard
ON
TIMER
00
Cooling fan residual-period running : Disable
01
Fun speed setting : Setting 1 *
01
Cooling fan residual-period running : 0.5 hours
02
Fun speed setting : Setting 2 *
02
Cooling fan residual-period running : 2 hours
MODE
00
Room heating temperature adjustment : Disable
03
Cooling fan residual-period running : 6 hours
01
Room heating temperature adjustment : +1°C
OFF
TIMER
00
Heating fan residual-period running : Disable
02
Room heating temperature adjustment : +2°C
01
Heating fan residual-period running : 0.5 hours
03
Room heating temperature adjustment : +3°C
02
Heating fan residual-period running : 2 hours
FIL
TER
00
Filter sign display : OFF
03
Heating fan residual-period running : 6 hours
01
Filter sign display : 180 hours
NIGHT
SETBACK
00
Remote control signal receiver LED : Brightness High
02
Filter sign display : 600 hours
01
Remote control signal receiver LED : Brightness Low
03
Filter sign display : 1000 hours
02
Remote control signal receiver LED : OFF
04
Filter sign display :
Operation stop after 1000 hours have elapsed
U/P
00
Anti draft setting : Disable
01
Anti draft setting : Enable
SILENT
00
Infrared sensor setting (Motion sensor setting) : Disable
01
Infrared sensor setting (Motion sensor setting) : Enable
HI POWER
00
Infrared sensor control (Motion sensor control) : Disable
01
Infrared sensor control (Motion sensor control) :
Power control only
02
Infrared sensor control (Motion sensor control) :
Auto OFF only
03
Infrared sensor control (Motion sensor control) :
Power control and Auto OFF
Restrictions on the thickness and length of wire
(Maximun total extension 600m.)
Standard Within 0.3 mm² × 100m
Within 0.5 mm² × 200m
Within 0.75mm² × 300m
Within 1.25mm² × 400m
Within 2.0 mm² × 600m
The receivable area of the signal when
the illuminance at the receiver is 300lux.
The receivable area of the signal when
the illuminance at the receiver is 600lux.
8
PJZ012D112
Band (enclosed)
Hole
Lower case
Cord clamp
Wiring
Fix with band
Hole
Upper case
Lower case
Approx. 100mm or more
(C) Exposed installation
Use the following procedure when installing the case with the wiring exposed.
①
Cut off the thin section on the side of the upper case with a pair of nippers or a knife, and remove the
burrs with a
fi
le, etc. (The wiring is passed through this section.)
②
Pass the enclosed band through the wiring outlet hole on the lower case.
③
Use on of the light detection adaptor installation methods (A) or (B) explained in section 3, and
fi
x the
lower case onto the wall. Do not pass the wiring through the hole on the lower case.
④
Fix the wiring using the band while leaving the wiring length from the band
fi
xing section to the end of
the wiring connector at 100mm or more.
⑤
Connect the wiring with the wiring protruding front the upper case using a connector.
⑥
Pass the connected connector and the excess wiring through the hole on the lower case.
⑦
Fit the upper case onto the lower case, and tighten the screws.
⑧
Adequately
fi
x the wiring with the enclesed cord clamp.
* Refer to technical data.
Auto Run setting