35
-
'17 • PAC-T-256
Preset point of the protective devices
Parts name
Mark
Equipped
unit
40, 50, 60 model
Temperature sensor
(for protection
overloading in heating)
Thi-R
Thi-R
Indoor unit
Temperature sensor
(for frost prevention)
Temperature sensor
(for protection high
pressure in cooling.)
TH1
Outdoor unit
ON 63
℃
OFF 53
℃
Temperature sensor
(for detecting discharge
pipe temp.)
TH3
Outdoor unit
ON 115
℃
OFF 95
℃
ON 63
℃
OFF 56
℃
ON 1.0
℃
OFF 10
℃