44
-
'17 • PAC-T-256
'10 • PAC-DB-136
9.2 Correction of cooling and heating capacity in relation to air flow rate control
(fan speed)
9.3 Correction of cooling and heating capacity in relation to one way length of
refrigerant piping
It is necessary to correct the cooling and heating capacity in relation to the one way equivalent piping length between the indoor
and outdoor units.
Note (1) Calculate the equivalent length using the following formula.
However, install the piping so that the piping length is 5 m of the limit length (actual length) for the respective types.
• Equivalent length =Actual (Equivalent bend length x number of bends in the piping.)
Equivalent length per bend. (Model 71-140 only)
(2) Models 71-140
0.20
0.25
0.30
Gas pipe diameter (mm)
Equivalent bend length
φ
19.05
φ
15.88
φ
12.7
1.00
0.97
0.95
Fan speed
Coefficient
Lo
Me
P-Hi
55
0.988
0.933
0.870
0.824
0.810
0.979
0.963
0.941
0.935
40
45
50
0.993
0.954
0.910
0.878
0.868
0.988
0.980
0.967
0.964
0.993
0.947
0.897
0.860
0.849
0.985
0.974
0.958
0.954
0.988
0.940
0.883
0.842
0.829
0.982
0.969
0.950
0.945
30
35
0.998
0.968
0.937
0.914
0.907
0.994
0.991
0.984
0.983
0.998
0.961
0.924
0.896
0.888
0.991
0.985
0.975
0.973
15
20
25
1
0.989
0.978
0.968
0.966
1.003
1.007
1.009
1.011
1
0.982
0.964
0.950
0.946
1
1.002
1.001
1.002
1
0.975
0.951
0.932
0.927
0.997
0.996
0.992
0.992
7.5
10
1
1
1
1
1
1.008
1.016
1.022
1.026
1
0.996
0.991
0.986
0.985
0.680
0.654
0.662
0.634
0.644
0.615
0.716
0.693
0.698
0.673
0.770
0.751
0.752
0.732
0.734
0.712
0.788
0.771
0.806
0.968 0.963 0.963
0.973 0.968
0.978 0.978 0.973
0.983
0.983
0.762 0.749 0.736
0.789 0.776
0.829 0.816 0.803
0.843
0.856
0.932 0.929 0.926
0.940 0.936
0.951 0.948 0.944
0.955
0.959
0.897 0.892 0.887
0.908 0.902
0.924 0.919 0.912
0.929
0.935
0.882 0.876 0.870
0.894 0.888
0.913 0.907 0.900
0.920
0.928
0.790
1.006
1.013
1.018
1.021
Equivalent piping length (m)
Cooling
Heating
71 model
100 model
125 model
140 model
71 model
100 model
125 model
140 model
φ
15.88
φ
19.05
(1)
105
ー
ー
90
95
100
ー
ー
ー
ー
ー
ー
80
85
ー
ー
ー
ー
65
70
75
ー
ー
ー
ー
ー
ー
60
ー
ー
Equivalent piping length (m)
Cooling
Heating
71 model
100 model
125 model
140 model
71 model
100 model
125 model
140 model
φ
15.88
φ
19.05
(1)
Note (1) SRK series only.
5m
10m
15m
20m
25m
30m
0.99
0.98
0.97
0.96
0.95
0.94
When the outdoor unit is located below indoor units in cooling mode, or when the outdoor unit is located above indoor units in
heating mode, the correction coefficient mentioned in the below table should be subtracted from the value in the above table.
Height difference between the indoor unit and
outdoor unit in the vertical height difference
9.4 Height difference between the indoor unit and outdoor unit
Adjustment coefficient
7
10
15
20
25
30
1
1
1
1
1
1
1
0.99 0.975 0.965 0.95 0.935
Piping length (m)
Heating
Cooling
'10 • PAC-DB-136
9.2 Correction of cooling and heating capacity in relation to air flow rate control
(fan speed)
9.3 Correction of cooling and heating capacity in relation to one way length of
refrigerant piping
It is necessary to correct the cooling and heating capacity in relation to the one way equivalent piping length between the indoor
and outdoor units.
Note (1) Calculate the equivalent length using the following formula.
However, install the piping so that the piping length is 5 m of the limit length (actual length) for the respective types.
• Equivalent length =Actual (Equivalent bend length x number of bends in the piping.)
Equivalent length per bend. (Model 71-140 only)
(2) Models 71-140
0.20
0.25
0.30
Gas pipe diameter (mm)
Equivalent bend length
φ
19.05
φ
15.88
φ
12.7
1.00
0.97
0.95
Fan speed
Coefficient
Lo
Me
P-Hi
55
0.988
0.933
0.870
0.824
0.810
0.979
0.963
0.941
0.935
40
45
50
0.993
0.954
0.910
0.878
0.868
0.988
0.980
0.967
0.964
0.993
0.947
0.897
0.860
0.849
0.985
0.974
0.958
0.954
0.988
0.940
0.883
0.842
0.829
0.982
0.969
0.950
0.945
30
35
0.998
0.968
0.937
0.914
0.907
0.994
0.991
0.984
0.983
0.998
0.961
0.924
0.896
0.888
0.991
0.985
0.975
0.973
15
20
25
1
0.989
0.978
0.968
0.966
1.003
1.007
1.009
1.011
1
0.982
0.964
0.950
0.946
1
1.002
1.001
1.002
1
0.975
0.951
0.932
0.927
0.997
0.996
0.992
0.992
7.5
10
1
1
1
1
1
1.008
1.016
1.022
1.026
1
0.996
0.991
0.986
0.985
0.680
0.654
0.662
0.634
0.644
0.615
0.716
0.693
0.698
0.673
0.770
0.751
0.752
0.732
0.734
0.712
0.788
0.771
0.806
0.968 0.963 0.963
0.973 0.968
0.978 0.978 0.973
0.983
0.983
0.762 0.749 0.736
0.789 0.776
0.829 0.816 0.803
0.843
0.856
0.932 0.929 0.926
0.940 0.936
0.951 0.948 0.944
0.955
0.959
0.897 0.892 0.887
0.908 0.902
0.924 0.919 0.912
0.929
0.935
0.882 0.876 0.870
0.894 0.888
0.913 0.907 0.900
0.920
0.928
0.790
1.006
1.013
1.018
1.021
Equivalent piping length (m)
Cooling
Heating
71 model
100 model
125 model
140 model
71 model
100 model
125 model
140 model
φ
15.88
φ
19.05
(1)
105
ー
ー
90
95
100
ー
ー
ー
ー
ー
ー
80
85
ー
ー
ー
ー
65
70
75
ー
ー
ー
ー
ー
ー
60
ー
ー
Equivalent piping length (m)
Cooling
Heating
71 model
100 model
125 model
140 model
71 model
100 model
125 model
140 model
φ
15.88
φ
19.05
(1)
Note (1) SRK series only.
5m
10m
15m
20m
25m
30m
0.99
0.98
0.97
0.96
0.95
0.94
When the outdoor unit is located below indoor units in cooling mode, or when the outdoor unit is located above indoor units in
heating mode, the correction coefficient mentioned in the below table should be subtracted from the value in the above table.
Height difference between the indoor unit and
outdoor unit in the vertical height difference
9.4 Height difference between the indoor unit and outdoor unit
Adjustment coefficient
7
10
15
20
25
30
1
1
1
1
1
1
1
0.99 0.975 0.965 0.95 0.935
Piping length (m)
Heating
Cooling
'10 • PAC-DB-136
Piping length limitations
Capacity
Item
Max. one way piping length
40, 50, 60
30m
Max. vertical height difference
Outdoor unit is higher 20m
Outdoor unit is lower 20m
Note (1) Values in the table indicate the one way piping length between the indoor and outdoor units.
How to obtain the cooling and heating capacity
Net cooling capacity =
4.0
×
1.00
×
×
0.975 0.99 .
=.
3.9kW
Example : The net cooling capacity of the model FDTC40ZSXVF with the air flow “P-Hi”, the piping length of 15m, the outdoor unit
located 5m lower than the indoor unit, indoor wet-bulb temperature at 19.0
℃
and outdoor dry-bulb temperature 35
℃
is
Net cooling total capacity
of FDTC40ZSXVF
(Outdoor temp. : 35
℃
DB
Indoor temp. : 19
℃
WB)
shown in table 9.1
Air flow : P-High
shown in table 9.2
Piping length :15m
(Gas pipe size is 15.88)
shown in table 9.3
Height diff. :5m
(Outdoor unit : below)
shown in table 9.4
φ
'10 • PAC-DB-136
9.2 Correction of cooling and heating capacity in relation to air flow rate control
(fan speed)
9.3 Correction of cooling and heating capacity in relation to one way length of
refrigerant piping
It is necessary to correct the cooling and heating capacity in relation to the one way equivalent piping length between the indoor
and outdoor units.
Note (1) Calculate the equivalent length using the following formula.
However, install the piping so that the piping length is 5 m of the limit length (actual length) for the respective types.
• Equivalent length =Actual (Equivalent bend length x number of bends in the piping.)
Equivalent length per bend. (Model 71-140 only)
(2) Models 71-140
0.20
0.25
0.30
Gas pipe diameter (mm)
Equivalent bend length
φ
19.05
φ
15.88
φ
12.7
1.00
0.97
0.95
Fan speed
Coefficient
Lo
Me
P-Hi
55
0.988
0.933
0.870
0.824
0.810
0.979
0.963
0.941
0.935
40
45
50
0.993
0.954
0.910
0.878
0.868
0.988
0.980
0.967
0.964
0.993
0.947
0.897
0.860
0.849
0.985
0.974
0.958
0.954
0.988
0.940
0.883
0.842
0.829
0.982
0.969
0.950
0.945
30
35
0.998
0.968
0.937
0.914
0.907
0.994
0.991
0.984
0.983
0.998
0.961
0.924
0.896
0.888
0.991
0.985
0.975
0.973
15
20
25
1
0.989
0.978
0.968
0.966
1.003
1.007
1.009
1.011
1
0.982
0.964
0.950
0.946
1
1.002
1.001
1.002
1
0.975
0.951
0.932
0.927
0.997
0.996
0.992
0.992
7.5
10
1
1
1
1
1
1.008
1.016
1.022
1.026
1
0.996
0.991
0.986
0.985
0.680
0.654
0.662
0.634
0.644
0.615
0.716
0.693
0.698
0.673
0.770
0.751
0.752
0.732
0.734
0.712
0.788
0.771
0.806
0.968 0.963 0.963
0.973 0.968
0.978 0.978 0.973
0.983
0.983
0.762 0.749 0.736
0.789 0.776
0.829 0.816 0.803
0.843
0.856
0.932 0.929 0.926
0.940 0.936
0.951 0.948 0.944
0.955
0.959
0.897 0.892 0.887
0.908 0.902
0.924 0.919 0.912
0.929
0.935
0.882 0.876 0.870
0.894 0.888
0.913 0.907 0.900
0.920
0.928
0.790
1.006
1.013
1.018
1.021
Equivalent piping length (m)
Cooling
Heating
71 model
100 model
125 model
140 model
71 model
100 model
125 model
140 model
φ
15.88
φ
19.05
(1)
105
ー
ー
90
95
100
ー
ー
ー
ー
ー
ー
80
85
ー
ー
ー
ー
65
70
75
ー
ー
ー
ー
ー
ー
60
ー
ー
Equivalent piping length (m)
Cooling
Heating
71 model
100 model
125 model
140 model
71 model
100 model
125 model
140 model
φ
15.88
φ
19.05
(1)
Note (1) SRK series only.
5m
10m
15m
20m
25m
30m
0.99
0.98
0.97
0.96
0.95
0.94
When the outdoor unit is located below indoor units in cooling mode, or when the outdoor unit is located above indoor units in
heating mode, the correction coefficient mentioned in the below table should be subtracted from the value in the above table.
Height difference between the indoor unit and
outdoor unit in the vertical height difference
9.4 Height difference between the indoor unit and outdoor unit
Adjustment coefficient
7
10
15
20
25
30
1
1
1
1
1
1
1
0.99 0.975 0.965 0.95 0.935
Piping length (m)
Heating
Cooling
'10 • PAC-DB-136
9.2 Correction of cooling and heating capacity in relation to air flow rate control
(fan speed)
9.3 Correction of cooling and heating capacity in relation to one way length of
refrigerant piping
It is necessary to correct the cooling and heating capacity in relation to the one way equivalent piping length between the indoor
and outdoor units.
Note (1) Calculate the equivalent length using the following formula.
However, install the piping so that the piping length is 5 m of the limit length (actual length) for the respective types.
• Equivalent length =Actual (Equivalent bend length x number of bends in the piping.)
Equivalent length per bend. (Model 71-140 only)
(2) Models 71-140
0.20
0.25
0.30
Gas pipe diameter (mm)
Equivalent bend length
φ
19.05
φ
15.88
φ
12.7
1.00
0.97
0.95
Fan speed
Coefficient
Lo
Me
P-Hi
55
0.988
0.933
0.870
0.824
0.810
0.979
0.963
0.941
0.935
40
45
50
0.993
0.954
0.910
0.878
0.868
0.988
0.980
0.967
0.964
0.993
0.947
0.897
0.860
0.849
0.985
0.974
0.958
0.954
0.988
0.940
0.883
0.842
0.829
0.982
0.969
0.950
0.945
30
35
0.998
0.968
0.937
0.914
0.907
0.994
0.991
0.984
0.983
0.998
0.961
0.924
0.896
0.888
0.991
0.985
0.975
0.973
15
20
25
1
0.989
0.978
0.968
0.966
1.003
1.007
1.009
1.011
1
0.982
0.964
0.950
0.946
1
1.002
1.001
1.002
1
0.975
0.951
0.932
0.927
0.997
0.996
0.992
0.992
7.5
10
1
1
1
1
1
1.008
1.016
1.022
1.026
1
0.996
0.991
0.986
0.985
0.680
0.654
0.662
0.634
0.644
0.615
0.716
0.693
0.698
0.673
0.770
0.751
0.752
0.732
0.734
0.712
0.788
0.771
0.806
0.968 0.963 0.963
0.973 0.968
0.978 0.978 0.973
0.983
0.983
0.762 0.749 0.736
0.789 0.776
0.829 0.816 0.803
0.843
0.856
0.932 0.929 0.926
0.940 0.936
0.951 0.948 0.944
0.955
0.959
0.897 0.892 0.887
0.908 0.902
0.924 0.919 0.912
0.929
0.935
0.882 0.876 0.870
0.894 0.888
0.913 0.907 0.900
0.920
0.928
0.790
1.006
1.013
1.018
1.021
Equivalent piping length (m)
Cooling
Heating
71 model
100 model
125 model
140 model
71 model
100 model
125 model
140 model
φ
15.88
φ
19.05
(1)
105
ー
ー
90
95
100
ー
ー
ー
ー
ー
ー
80
85
ー
ー
ー
ー
65
70
75
ー
ー
ー
ー
ー
ー
60
ー
ー
Equivalent piping length (m)
Cooling
Heating
71 model
100 model
125 model
140 model
71 model
100 model
125 model
140 model
φ
15.88
φ
19.05
(1)
Note (1) SRK series only.
5m
10m
15m
20m
25m
30m
0.99
0.98
0.97
0.96
0.95
0.94
When the outdoor unit is located below indoor units in cooling mode, or when the outdoor unit is located above indoor units in
heating mode, the correction coefficient mentioned in the below table should be subtracted from the value in the above table.
Height difference between the indoor unit and
outdoor unit in the vertical height difference
9.4 Height difference between the indoor unit and outdoor unit
Adjustment coefficient
7
10
15
20
25
30
1
1
1
1
1
1
1
0.99 0.975 0.965 0.95 0.935
Piping length (m)
Heating
Cooling