68
-
Error code
Remote control:
LED
Green
Red
Indoor
Outdoor
Content
'18 • PAC-SM-297
E10
Excessive number of connected
indoor units (more than 17 units)
by controlling with one remote control
Keeps flashing Stays OFF
Keeps flashing Stays OFF
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
Aren't more than 17
indoor units connected to one
remote control?
NO
YES
Defective remote control
➞
Replace.
Reduce to 16 or less units.
2. Error detection method
When it detects more than 17 of
indoor units connected to one
remote control
3. Condition of error displayed
Same as above
4. Presumable cause
• Excessive number of indoor
units connected
• Defective remote control
Note:
Summary of Contents for FDE40ZSXVH