'18 • PAC-SM-297
-
83
-
Error code
Remote control:
LED
Green
Red
Content
Indoor
Outdoor
Stays OFF
ON
Keeps flashing
㧙
E48
Outdoor fan motor anomaly
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
YES
NO
Does any
foreign material intervene
in rotational area of fan
propeller?
NO
Does the
fan rotate smoothly when turned
by hand?
NO
Is DC308~336V
detected between (CNFAN
➃
(black)-
➅
(red)) of fan motor
connector?
Is F3 (250V1A) fuse blown?
Is normal state restored?
YES
YES
NO
YES
NO
YES
Power source reset
Remove foreign matter.
Replace fan motor.
If resistance between
➀
(FG):blue -
➃
(GND):black
is detected 1k
Ω
or lower, it
is faulty.
Check power source
voltage.
Replace faulty fan motor
and outdoor unit PCB.
Replace fan motor (If
anomaly persists after
replacing fan motor, replace
outdoor unit PCB.)
Malfunction by temporary
noise
2. Error detection method
Detected by rotation speed of
outdoor fan motor
3. Condition of error displayed
When actual rotation speed
of outdoor fan motor drops to
75min
-1
or lower for 30 minutes
continuously, the compressor
and the outdoor fan motor stop.
After 3-minute delay, it starts
again automatically, but if this
anomaly occurs 3 times within
60 minutes after the initial
detection.
4. Presumable cause
• Defective outdoor unit PCB
• Foreign material at rotational
area of fan propeller
• Defective fan motor
• Dust on outdoor unit PCB
• Blown F3 fuse
Note: When E48 error occurs, in almost cases F3 fuse (1A) on the outdoor unit PCB is blown. There are a lot of cases that fuse is blown and E48
occurs due to defective fan motor. And even though only the outdoor unit PCB ( or fuse) is replaced, another trouble could occur. Therefore
when fuse is blown, check whether the fan motor is OK or not.
After confirming the fan motor normal, check by power ON. (Don't power ON without confirming the fan motor normal.)
Summary of Contents for FDE40ZSXVH
Page 46: ... 18 PAC SM 297 45 ...