2.2 Troubleshooting flow
(1) List of troubles
Remote control display
Description of trouble
Reference page
None
Operates but does not cool.
47
None
Operates but does not heat.
48
None
Earth leakage breaker activated
49
None
Excessive noise/vibration (1/3)
50
None
Excessive noise/vibration (2/3)
51
None
Excessive noise/vibration (3/3)
52
None
Louver motor failure (FDTC and FDE series)
53
None
Power source system error (Power source to indoor unit control PCB)
54
None
Power source system error (Power source to remote control)
55
INSPECT I/U
INSPECT I/U (When 1 or 2 remote controls are connected)
56
INSPECT I/U
INSPECT I/U (Connection of 3 units or more remote controls)
57
WAIT
Communication error at initial operation
58
・
60
None
No display
61
E1
Remote control communication circuit error
62
E5
Communication error during operation
63
E6
Indoor heat exchanger temperature sensor anomaly
64
E7
Return air temperature sensor anomaly
65
E8
Heating overload operation
66
E9
Drain trouble (FDTC and FDUM series)
67
E10
Excessive number of connected indoor units (more than 17 units) by controlling with one remote control
68
E11
Address setting error of indoor units
69
E16
Indoor fan motor anomaly
70
E19
Indoor unit operation check, drain pump motor check setting error
71
E20
Indoor fan motor rotation speed anomaly
72
E28
Remote control temperature sensor anomaly
73
E35
Cooling overload operation
74
E36
Discharge pipe temperature error
75
E37
Outdoor heat exchanger temperature sensor anomaly
76
E38
Outdoor air temperature sensor anomaly
77
E39
Discharge pipe temperature sensor anomaly
78
E40
Service valve (gas side) closing operation
79
E42
Current cut
80
・
81
E47
Active filter voltage error
82
E48
Outdoor fan motor anomaly
83
E51
Power transistor anomaly
84
E57
Insufficient refrigerant amount or detection of service valve closure
85
E58
Current safe stop
86
E59
Compressor startup failure
87
E60
Compressor rotor lock error
88