'18 • PAC-SM-297
-
5
-
1.2 Operation control function by the wired remote control
-
114
-
'16 • PAC-T-251
Service & Maintenance
Special settings
Indoor unit capacity display
Back
Select the item.
前ページ
Previous
Back
Erase IU address
CPU reset
Restore of default setting
Touch panel calibration
Special settings
Select the item.
R/C function settings
Ventilation setting
Auto-restart
Auto temp setting
Back
Select the item.
Previous
Auto fan speed
②
Auto-restart
Auto-restart
Back
Select the item.
Enable
Disable
1.10.2 Operation control function by the wired remote control
●
Model RC-EX3A
(1) Switching sequence of the operation mode switches of remote control
(a) Tap the change operation mode button on the TOP screen.
(b) When the change operation mode screen is displayed, tap the button of desired mode.
(c) When the operation mode is selected, the display returns to the TOP screen.
Icons displayed have the following meanings.
Notes
(1) Operation modes which cannot be selected depending on combinations of indoor
unit and outdoor unit are not displayed.
(2) When the Auto is selected,the cooling and heating switching operation is performed
automatically according to indoor and outdoor temperatures.
(2) CPU reset
Reset CPU from the remote control as follows.
TOP screen Menu
Service setting
Service & Maintenance
Service password
The selected screen is
displayed.
The selected screen is
displayed.
①
Service & Maintenance #2
②
Special settings
⇒
⇒
⇒
CPU reset
Microcomputers of indoor unit and outdoor unit connected are reset
(State of restoration after power failure).
(3) Power failure compensation function (Electric power source failure)
Enable the Auto-restart function from the remote control as follows.
TOP screen Menu
⇒
Service setting
⇒
R/C function settings
Service password
⇒
①
R/C function settings menu #3
If the unit stops during operation,
It returns to the state before the power failure as soon as
the power
source is restored (After the end of the primary control at the power
on).
It stops after the restoration of power source.
Enable
Disable
●Since the status of remote control is retained in memory
always, it restarts operations according to the contents of memory
as soon as the power source is restored. Although the timer mode is cancelled, the weekly timer, peak cut timer and silent
mode timer operate according to the following contents:
・
When the clock setting is valid : These timer settings are also valid.
・
When the clock setting is invalid : These timer settings become “Invalid” since the clock setting is invalid.
These timer settings have to be changed to “Valid” after the timer setting.
Cooling
Fan
Dry
Heating
Auto