'18 • PAC-SM-298
-
86
-
Error code
Remote control:
LED
Green
Red
Content
Indoor
Outdoor
Stays OFF
3-time flash
Keeps flashing
㧙
E58
Current safe stop
Error code
Remote controller: E58
LED
Green
Red
Indoor
Outdoor
―
Content
Current safe stop
(Model SRC50, 60)
Keeps flashing Stays Off
3 time flash
1. Applicable model
5. Troubleshooting
All models
When the current safe control
has operated at the compressor
speed of 30 rps or under:
Same as above
• Excessive refrigerant amount
• Indoor,outdoor unit installation
spaces
• Faulty compressor
• Defective outdoor air
temperature sensor
• Defective outdoor unit PCB
Diagnosis
Countermeasure
2. Error detection method
3. Condition of error displayed
4. Presumable cause
Note:
Is outdoor
ventilation condition
good ?
Inspect
outdoor air temperature
sensor
Is the refrigerant
amount nomal ?
Adjust the refrigerant
amount properly.
Secure space for inlet and
outlet.
Replace compressor.
Replace sensor.
Defective outdoor unit
PCB
→
Replace.
(Defective outdoor air
temperature sensor input
circuit)
Inspect
compressor
YES
YES
YES
NO
NO
NO
NO
YES
Summary of Contents for FDE40ZSXW1VH
Page 46: ... 18 PAC SM 298 45 ...